rESO
(Resolution) SUB MENU
The DH3 is capable of displaying four digits of resolution. However, at very low pressures the instability of the
pressure may cause uctuations in the least signicant digit causing the least signicant digit to be of little value.
Three digit resolution (
3DIG
) can only be active when there is at least one digit to the right of a decimal.
3DIG
- Set display for 3 digit resolution
4DIG
- Set display for 4 digit resolution
Pd.S
(Process Display) SUB MENU
STD
- Display reads pressure, velocity, or ow values
PCT
- Display reads % of full scale value
When the display is reading percent,
PCT
is displayed in the upper right of the display. The percent display is only
available in pressure operation.
DAMP
(Dampening) SUB MENU
Adjust from 1-16
Dampening stabilizes the display from instabilities due to things such as vibration and excessive pressure
uctuations. The dampening setting adjusts the amount of readings that are averaged for each display update.
Adjust the dampening value until the display reads a stable value for the application.
AdU
(Advanced) MAIN MENU
POL
- Process output low
ZERO
- Zero calibration
POH
- Process output high
SPAN
- Span calibration
MSP1
- Maintenance set point 1
MSP2
- Maintenance set point 2
POL
and
POH
(Process Output Low and High) SUB MENUS
This feature is used in pressure operation only.
Process output low and high are used to scale the 4-20 mA output. Set
POL
to the desired display reading for 4mA
output, and set
POH
to the desired display reading for 20 mA output.
POH
must be higher than
POL. POL
may be
adjusted 2% BELOW minimum scale up to
POH. POH
may be adjusted from
POL
to 2% ABOVE maximum scale.