Dwyer Instruments CDTA-2E000, CDTA-2N000, CDTA Series, CDTA-2N000-LCD, CDTA-2E000-LCD Installation And Operating Instructions Manual

...
Series CDTA Communicating Carbon Dioxide Detector
1.10
[71.12]
[92.72]
[90.42]
®
Specications - Installation and Operating Instructions
1.08
[27.33]
4.50
3.65
[114.30]
Bulletin AQ-CDTA-QS
[27.96]
European style North American style
The Series CDTA Communicating Carbon Dioxide Detector combines the function of three room sensors into a single, compact housing. Parameters include carbon dioxide, humidity, temperature, and temperature set point with override. By having
eld selectable Modbus® and BACnet Communications, only four wires are needed
for power and the communication signal. The communicating detectors can be daisy­chained together to further reduce installation cost. In order to reduce the set up time,
the RS-485 MAC address is set up using on board dip switches. A second set of dip switches are used to select whether output is Modbus® RTU or BACnet MS/TP
communication protocols and to limit access to the set up menu.
Like our Series CDT Carbon Dioxide Transmitter, the Series CDTA uses a Single Beam Dual Wavelength Non-Dispersive Infrared (NDIR) sensor to measure the carbon
dioxide level. This technology can be used in installations that will be occupied 24
hours per day. For improved accuracy, the transmitter can be eld calibrated to the environmental conditions of the installation. Also, the barometric pressure can be
programmed to correct for altitude. The humidity uses a capacitive polymer sensor and
the temperature is measured using a 10KΩ thermistor sensor. The humidity sensor is eld replaceable without the need for additional calibration.
Optional local and remote displays are available to display any of the parameters. For
applications in which the building occupants aren’t familiar with CO the LCD can be programmed to display temperature, humidity, or temperature set
point instead.
Installation
CAUTION
Make sure all connections are in accordance with the job wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.
Disconnect power supply before installation to prevent electrical
shock and equipment damage.
2 concentrations,
3.56
SPECIFICATIONS Sensor (CO
Temperature: Solid state band gap. Range: CO 100% RH; Temperature: 32 to 122°F (0 to 50°C). Accuracy: CO ±1°C @ 25°C.
Temperature Dependence (CO Non-Linearity (CO Pressure Dependence (CO Response Time (CO Temperature Limits: 32 to 122°F (0 to 50°C). Humidity Limits: 10 to 95% RH (non-condensing).
Power Requirements: 10 to 42 VDC / 10 to 30 VAC. Power Consumption: Average: 0.5 watts; Peak: 1.2 watts.
Output: 2-wire RS-485, Modbus
Weight: 4.4 oz (125 g).
Agency Approvals: BTL, CE.
2): Single-beam, dual-wavelength NDIR; Humidity: Capacitive polymer;
2: 0 to 2000 or 5000 PPM CO2 (depending on model); Humidity: 0 to
2: ±40 ppm ±3% of reading; RH: ±2% (10 to 90% RH); Temperature:
2): 16 ppm.
2): 2 minutes for 99% step change.
2): ±8 ppm / °C at 1100 ppm.
2): 0.13% of reading per mm of Hg.
®
RTU or BACnet MS/TP communication protocol.
2.80
Use electrostatic discharge precautions (e.g., use of wrist straps)
during installation and wiring to prevent equipment damage.
For optimal performance, self calibration feature of the transmitter requires exposure to normal outdoor equivalent carbon dioxide
Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present.
Do not exceed ratings of this device, permanent damage not
covered by warranty may result.
Upon powering the transmitter, the rmware version will ash on the display. A warm up period of 30 minutes is required for the
2 concentration.
NOTICE
NOTICE
level once every thirty days.
NOTICE
NOTICE
NOTICE
transmitter to adjust to the current CO
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Modbus® is a registered trademark of Schneider Automation, Inc.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
COMMON POWER SUPPLY
TO
NEXT
LOCAL POWER SUPPLY
TO
SUPPLY
NEXT
supplies. Use a cable containing a twisted pair and a single conductor. The pair is to be used for B(+) and A(-). The single conductor is to be used for common. Both AC and DC supplies are suitable for this conguration.
In either conguration you must use shielded cable. Connect the shield to earth ground
at one location only to prevent ground loops.
All devices in the network should be daisy chained. Star connections and T connections
are not permitted.
The B(+) and A(-) lines must be terminated at both ends with a 120 ohm resistor. If the CDTA is an end device it has an on-board resistor that may be used. See DIP SWITCH SETTINGS to enable it.
Figure 1: Removal of cover from back plate
MOUNTING
1. Push tab on top and bottom of cover and lift cover from back plate (See Figure 1).
2. Select the mounting location, away from diffusers, lights or any external inuences.
3. Mount transmitter on a vertical surface to a standard electrical box using the two #6 M2C type screws provided.
4. Pull wires through sub base hole and make necessary connections.
5. Reattach cover to base plate.
WIRING
NOTICE
Wiring should comply with Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems, TIA/
EIA-485-A-1998, Telecommunications Industry Association, 1998.
BACnet installations should comply with ANSI/ASHRAE Standard 135-2010 BACnet A Data Communication Protocol for Building Automation and Control Networks, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 2010.
®
installations should comply with Modbus® Communication Protocol over
Modbus Serial Line Specication and Implementation Guide V1.02, Modbus
®
Organization,
Inc., 2006
Communications wiring must be in a daisy-chain fashion. Star connections are not
permitted.
Cable shield must be connected to earth ground at one location only.
PWR COM B(+) A(-)
PREVIOUS
DEVICE
PWR COM
B(+) A(-)
1 2 3 4
TO
DEVICE
PWR COM
B(+)
A(-)
Figure 2
Figure 2 shows how to connect the CDTA in a network containing a common power supply. Use a cable containing two twisted pairs. One pair is to be used for B(+) and A(­). The other pair is to be used for power and common. This conguration is not suitable for AC supplies. Use a DC supply only. Care should be taken that there are not too
many devices powered from the same supply as voltage drops will occur in the wiring.
be a better choice.
Dip Switch Conguration
ON
1 2 3 4 5 6 7 8
Figure 4: Dip switch SW2 (center-left)
Use DIP Switch SW2 (see Figure 4) to congure the RS-485 MAC address of the device. A valid address depends on the protocol selected. Valid BACnet addresses range from 0 to 127. Valid Modbus
®
addresses range from 1 to 247. By default, the
device is shipped with BACnet selected and the address set to 127 (as shown in Figure 4). A valid and unused address should be set before connecting to an existing network. The device will not function properly if an invalid address is set. During the power up sequence, the LCD (if present) will display the RS-485 address as the primary value with “ADR” as the primary text and either “BAC” to indicate BACnet or “MOD” to indicate Modbus
®
as the secondary text. If the RS-485 MAC address is
invalid, the invalid value is shown as the primary value with “ERR” as the primary text.
PROTOCOL RESERVED
ON
1 2 3 4
MENU ENABLE NETWORK TERMINATION
Figure 5: Dip switch SW1 (bottom-center)
Use DIP Switch SW1 (see Figure 5) to congure other hardware and software options.
Switch ON OFF 1 - Menu Enable
2 - Protocol
Access to the setup
menu is enabled.
Modbus
Access to the setup
menu is disabled.
BACnet
3 - Reserved 4 - Terminating
Resister
120Ω Between A (-) and B (+)
Open
PWR COM B(+) A(-)
PREVIOUS
DEVICE
COM
B(+) A(-)
1 2 3 4
POWER
Figure 3
TO
DEVICE
COM
B(+)
A(-)
Dip switch
SW2
Dip switch
SW1
Internal view of transmitter
Figure 6
Loading...
+ 2 hidden pages