Series 4000 Capsuhelic®Differential Pressure Gage
Specifications - Installation and Operating Instructions
Bulletin A-32
3/4 [19.05] TYP
1/4 FEMALE NPT HIGH
PRESSURE CONNECTION
(AIR OR GAS)
(4) #6-32 X 3/8 [9.53] DP
HOLE ON A 4-11/32 [110.33]
BOLT CIRCLE
1/4 FEMALE NPT HIGH
PRESSURE CONNECTION
(LIQUID)
1/4 FEMALE NPT LOW
PRESSURE CONNECTION
(LIQUID)
CAUTION: Use of a line filter (Dwyer Instruments, Inc. model A-391 or
equivalent) is recommended to prevent entry of liquid borne particles
into gage. Dwyer Instruments, Inc. cannot assume responsibility for
failure of gages due to clogging of internal passages.
Note: May be used with hydrogen where pressures are less than 35 psi.
Order with Buna-N diaphragm.
CAPSUHELIC®GAGE INSTALLATION
1. Select a location free from excessive vibration and where the ambient
temperature will not exceed 200°F. Sensing lines may be run any
necessary distance. For example, 250 foot lines will not affect accuracy
but will damp the reading slightly. Do not restrict lines. If pulsating
pressures or vibration cause excessive pointer oscillation, consult
factory for means of providing additional damping.
2. All standard models are calibrated for use with the diaphragm and
scale in a vertical position. Special factory calibration is necessary for
operation in an inclined or horizontal position. The exceptions are ranges
under 5 in. w.c., (or metric equivalents) which can only be calibrated for
vertical operation.
1/4 FEMALE NPT LOW
PRESSURE CONNECTION
(AIR OR GAS)
35° TYP
Ø4-45/64
[119.46]
13/32
[10.32] TYPE
2-19/32
[65.86]
1/2
[12.70]
Ø5
[127.00]
SPECIFICATIONS
Service: Aluminum Case: Air and compatible gases and oil based
liquids. Brass Case: Air and compatible gases and water based
liquids.
Wetted Materials: Consult factory.
Housing: Die cast aluminum with impregnated hard coating, standard.
Optional forged brass housing is required for water or water based
fluids. Special material diaphragms available, contact factory.
Accuracy: ±3% of full scale at 70°F (21.1°C). (±2% on 4000S models,
±4% on 4200, 4210, 4215, 4220, 4300, 4400, and 4500).
Pressure Limits: -20˝ Hg to 500 psig.
(-0.677 bar to 34.4 bar).
Temperature Limits: 20 to 200°F. (-6.67 to 93.3°C).
Size: 4˝ (101.6 mm) diameter dial face.
Mounting Orientation: Diaphragm in vertical position. Consult factory
for other position orientations.
Process Connections: 1/4˝ female NPT high and low pressure taps,
duplicated -one pair top for air and gas, and one pair bottom for liquids.
Weight: 3 lb, 3 oz (1.45 kg) aluminum case; 7 lb, 13 oz (3.54 kg) brass
case.
Standard Accessories: Two 1/4˝ NPT plugs for duplicate pressure
taps, four flush mounting adapters with screws and four surface
mounting screws.
DWYER INSTRUMENTS, INC.
3. Surface Mounting
Locate 4 mounting holes, 35° from horizontal centerline on a 4-11/32˝
dia. circle. Use No. 6-32 machine screws of appropriate length. Be sure
to drill 1/4˝ holes for blowout protection as shown in the diagram.
CAUTION
Note location of blowout or vent holes in the surface mounting diagram.
Do not block these holes as their function is to vent overpressure failure
out the back of the gage rather than blowing off the front cover.
Important Notes:
Two pairs of high and low pressure taps are provided, one pair on the
top and a duplicate pair on the bottom. These fittings may be utilized
according to the type of service for which the gage will be used. For gas
or vapor service the gage should be connected from the pressure
source to the top pressure fittings so that any accumulation of
condensate may be drained or bled out the bottom fittings. For liquid
service the pressure source should bee connected to the bottom taps so
that any trapped gas may be vented out the top fittings. Optional bleed
fittings may be obtained to replace the standard 1/4˝ NPT plugs for
installations requiring frequent draining or venting of the gage. Note that
the unused pair of pressure taps must be plugged in order for the gage
to operate. For straight pressure or vacuum applications where only one
of a pair of high and low pressure taps are being utilized, the other tap
must be open to atmosphere.
For portable use or temporary installation use 1/4 male NPT to male
flare fitting and connect to pressure source with high pressure hose or
tubing will flare nut connectors.
For permanent installation 1/4˝ OD copper or stainless steel tubing is
recommended.
Proper installation of fittings and plugs is important. Sparingly apply pipe
thread sealant to threads. Excessive amounts can fall into pressure
passages and cause blockage. We recommend Loctite
®
69-31 Hydraulic
Sealant. Install using torque wrench. Tighten only to 20 ft/lbs. Overtightening can damage case.
MAINTENANCE
Upon final installation of the Series 4000 Capsuhelic® Differential
Pressure Gage, no routine maintenance is required. The Series 4000 is
not field serviceable and should be returned if repair is needed (field
repair should not be attempted and may void warranty). Be sure to
include a brief description of the problem plus any relevant application
notes. Contact customer service to receive a return goods authorization
number before shipping.
4. Flush Mounting
Loctite®is a registered trademark of Henkel Corporation and Company.
Provide a 4-13/16˝ dia. opening in panel. Insert gage and secure in
place with No. 6-32 machine screws of appropriate length, with
mounting lugs firmly secured in place.
5. To zero the gage after Installation
Set the indicating pointer exactly on the zero mark, using the external
zero adjust screw on the cover at the bottom. Note that the zero check
or adjustment can only be made with the high and low pressure taps
both open to atmosphere.
©Copyright 2010 Dwyer Instruments, Inc. Printed in U.S.A. 7/10 FR# 15-440306-00 Rev.13