Dwyer Instruments AVUL Operating Manual

Bulletin P-AVUL-M
®
Series AVUL Air Velocity Transmitter with Modbus® Communication
Specications - Installation and Operating Instructions
The SERIES AVUL Air Velocity Transmitter quickly and accurately measures air
velocity or volumetric ow in imperial or metric units. Simultaneous current and voltage outputs on all models provide universal inputs to monitoring equipment while the output range, units, and 0 to 5/10 VDC output can be congured via local DIP switches. The optional integral display, or the portable remote display tool, provide a convenient way to locally monitor process values and congure the unit.
Models are available in 3% and 5% accuracy models to suit a variety of needs, and the optional BACnet MS/TP or Modbus to be daisy-chained while providing access to all of the velocity and ow data, as well as additional information such as air temperature.
MODEL CHART
Model AVUL -3 D A1 -LCD AVUL-3DA1-LCD Accuracy 5
3
Mounting D Duct mount Output A1
Options LCD
®
RTU/ASCII communication protocol allows units
±(0.2 m/s + 5% of reading) @ standard
conditions
±(0.2 m/s + 3% of reading) @ standard
conditions
Analog universal (0 to 5 VDC, 0 to 10 VDC,
B1 M1
4 to 20 mA) Analog + BACnet MS/TP Analog + Modbus
LCD display
FC
Factory calibration certicate
NIST
NIST certicate
GLD
Electrical cable gland
®
RTU/ASCII
3-49/64
[95.71]
3-33/64
[89.13]
SPECIFICATIONS
Service: Clean air and non-combustible, compatible gases. Wetted Materials: Consult Factory.
Range: 1000, 2000, 3000, 4000 FPM (5, 10, 15, 20 m/s); Field selectable.
Accuracy: ±(5% of reading + 0.2 m/s) or ±(3% of reading + 0.2 m/s) @ standard conditions, depending on model.
Temperature Limits: 32 to 122°F (0 to 50°C). Power Requirements: 24 VDC ±20% or 24 VAC ±20%. Humidity Limits: 5 to 95% RH, non-condensing.
Output Signals: 4 to 20 mA, 0 to 5 VDC, 0 to 10 VDC .
Response Time (90%): 10 seconds, typical. Zero & Span Adjustments: Digital push buttons.
Output Load Resistance: Current Output: 0 to 1100 Ω max.; Voltage Output: Minimum load resistance 1 kΩ.
Current Consumption: 60 mA Max. Display (optional): 5 Digit LCD.
Electrical Connections (Analog): Power and output: four wire removable European style terminal block for 16 to 26 AWG. Communication (optional): Connections: BACnet MS/TP or Modbus three wire removable European style terminal block for 16 to 26 AWG; Supported Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200.
Device Load: 1/8th unit load. Electrical Entry: 1/2˝ NPS thread. Accessory (A-151): Cable gland for 5 to 10 mm
diameter cable.
Enclosure Rating: NEMA 4X (IP66). Mounting Orientation: Flow direction must be parallel to the sensor tip;
See Installation section for details.
Weight: 6.0 oz (160 g). Agency Approval: CE, RoHS.
1/2 NPS
2-43/64
[67.92]
7-41/64
[194.07]
7-17/64 [184.60]
39/64
[15.32]
Ø15/32
[80.81]
1-19/32
[40.59]
®
RTU/ASCII:
2-5/32 [54.82]
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
INSTALLATION
Duct Mount:
The transmitter should be mounted away from fans, corners, heating and cooling coils, and other equipment that will effect the measurement of the air velocity. It is recommended that the AVUL is mounted 10 duct diameters downstream of any disturbances and 5 duct diameters upstream of any disturbances, if possible.
1. Mark and drill a 0.750-0.938˝ (20-24 mm) diameter hole into the duct.
2. Insert and center the duct mount ange in the previously drilled hole and mark location of the three mounting screw holes.
3. Remove the mounting ange and drill or punch the mounting holes in the marked locations.
4. Fasten the ange to the duct using three #8 x 1/2 pan head sheet metal screws. Do not over tighten screws.
5. Insert the AVUL probe into the ducts mount ange and set the desired insertion depth.
6. Note the ow direction and unit alignment as shown on sensor tip and product label, tighten probe retention set screw on the duct mount ange screw to afx the probe in place.
Electrical Connection:
The Series AVUL is powered and simultaneously transmits a two-wire 4 to 20 mA current output and a three-wire 0 to 5 VDC or 0 to 10 VDC voltage output via a removable four conductor terminal block. The transmitter power supply common is used to reference the current and voltage outputs so either current, voltage, or current and voltage may be wired according to the application. The range of the voltage output can be selected using the on board DIP switches as described in the Analog DIP Switch Settings section of this manual.
Power Supply
Choose a power supply with a voltage and current rating sufcient to meet the power specications under all operating conditions. If the power supply is unregulated, make sure the output voltage remains within the required voltage range under all power line conditions. Ripple on the supply should not exceed 100 mV.
Although low loop resistances are recommended, the absolute maximum current loop load resistance, R
R
MAX = (VPS – 2.0) / 0.02 where VPS is the power supply voltage
For a 24 VDC nominal power supply, this evaluates to R
MAX , is dened by the following the equation:
MAX = 1100 ohms.
Shielded two wire cable is recommended for current output loop wiring. Ground the shield at the power supply end only.
The maximum length of connecting wire between the current transmitter and the receiver is a function of wire size and receiver resistance. That portion of the total current loop resistance represented by the resistance of the connecting wires themselves should not exceed 10% of the receiver resistance. For extremely long runs (over 1,000 ft.), it is desirable to select receivers with higher resistances in order to keep the size and cost of the connecting leads as low as possible. In installations where the connecting run is no more than 100 ft, connecting lead wire as small as No. 22 Ga. can be used.
Voltage Output Operation
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL
RESULT.
The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. The voltage output and the power supply must have separate wire leads that are only joined at terminal 2 of the transmitter, as shown in Figure 2. Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. The connections to the transmitter are made to terminals 1, 2, and 4 (PWR, GND, and VOUT respectively) on the terminal block as shown in Figure 4.
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL
RESULT.
Current Output Operation
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL
RESULT.
The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. As the power supply and outputs share the same common signal (GND), the outputs may have separate wires but must effectively join at terminal 2 of the transmitter, as shown in Figure 1. The connections to the transmitter are made to terminals 1, 2, and 3 (PWR, GND, and IOUT respectively) on the terminal block as shown in Figure 4.
Figure 2
Voltage Output Wiring
The minimum receiver load is 1 kΩ. The resistance due to the wire should be low compared to the receiver load resistance. While the voltage at the terminal block remains unchanged with a 10 mA current ow, resistive losses in the wiring do cause errors in the voltage delivered to the receiver. For a 1% accurate gauge, the resistance of the wires should be less than 0.1% of the value of the receiver load resistance. This will keep the error caused by the current ow below 0.1%.
The output across VOUT and COM will be either 0 to 5 VDC, 0 to 10 VDC, or the inverse depending on the DIP switch setting. See the Analog DIP Switch Settings section for more information.
Figure 1
Current Output Wiring
Simultaneous Current and Voltage Output Operation
RANGE
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL
RESULT.
The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. The voltage output and the power supply must have separate wire leads that are only joined at terminal 2 of the transmitter, as shown in Figure 3. Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. The connections to the transmitter are made to terminals 1, 2, 3 and 4 (PWR, GND, IOUT, and VOUT respectively) on the terminal block as shown in Figure 4, which reects both the 4-20 mA and 0-5/10 VDC outputs in the same circuit. Details of each output are detailed in their electrical connection sections.
Setting the Air Velocity Range
The range of the instrument is selected by using DIP switches 1 and 2 on SW1. Table 1 shows the maximum full scale value for the selected range and unit. Refer to Setting the Engineering Units section for information on setting the unit.
DIP Switch SW1 Full Scale Range 1 2 Imperial (FPM) Metric (m/s)
ON
ON ON OFF OFF
OFF
ON
OFF
4000 3000 2000 1000
20 15 10 5
Table 1: DIP Switch SW1 Settings for Full Scale Range
Setting the Engineering Units
The Series AVUL can be congured to indicate velocity in imperial (FPM, CFM) or metric (m/s, m
3
/h) units using DIP switches 4 and 5 on SW1, and Table 2 shows the
values. The units will be displayed on the optional LCD display if connected.
DIP Switch SW1 Units 4 5 Velocity Mode Air Flow Mode
ON
ON ON OFF OFF
OFF
ON
OFF
FPM m/s m/s m/s
CFM
3
m
3
m
3
m
/h /h /h
Table 2: DIP Switch SW1 Settings for Units
The default operating mode is velocity, but changes can be made, such as ow mode, via the menu system while an optional display or remote display accessory is connected. Please refer to Appendix VI for a full menu ow chart.
Setting the Output Voltage Range
Voltage Output can be either 0 to 5 VDC or 0 to 10 VDC depending on the position of DIP Switch 6 ON SW1.
Simultaneous Current and Voltage Output Wiring
Figure 3
ANALOG DIP SWITCH SETTINGS
The analog output DIP switches (SW1) are located above the terminal blocks on the left are as shown in Figure 4. A small screw driver or pen can be used to change the position of the switches as required.
WARNING
All power should be turned off to the transmitter before adjusting the DIP switch settings to avoid electrical shock.
UNITS
5V
REV
10V DIR
• When the switch is in the ON position, the output will be 0 to 10 VDC.
• When the switch is in the OFF position, the output will be 0 to 5 VDC.
Setting the Input / Output Action
The output will either follow the process directly (DIRECT) or inverted (REVERSED) based on the position of DIP Switch 7 on SW1.
• When the switch is in the ON position, the output directly follows the input (i.e. output increases as the input increases).
• When the switch is in the OFF position, the output acts in reverse of the input (i.e. output decreases as the input increases).
Figure 4
Analog Dip Switches
Factory Default Settings (DIP SW1 – All Switches ON)
Range = Highest Range Setting (4000 FPM) Units = Imperial (FPM) Voltage Output Range = 0 to 10 VDC Direct / Reverse Output Action = Direct
KEY
CALIBRATION
NOTICE
takes place. This delay is used to reduce vibration or disturbances of the user related to the button presses.
There is a 5 second delay from the time the zero or span calibration buttons are released until the time that the change in calibration
NOTICE
adjusted by the user.
Zero Calibration
The zero calibration can be set by covering the sensor to ensure no air ow and pressing the zero button for 3 seconds. If either the remote or local LCD is present, the display will read ZEro and then sequence back to the home display.
SPAN Calibration
The span calibration can be adjusted only after setting the zero adjustment. It must be completed within 5 minutes of the last zero calibration. The span calibration button will be ignored until the zero calibration is completed. Place the sensor in airow that matches the maximum selected range of the transmitter. Press and hold the span button for 3 seconds. If either the remote or local LCD is present, the display will read SPAn and then sequence back to the home display. If the span calibration is attempted before adjusting the zero calibration, the FAiL error message will be displayed briey before returning to the home display.
LCD Display
The Series AVUL can be ordered with an optional, integral LCD. It comes with a housing cover and overlay to protect the display. The display will plug into the pins as shown in Figure 5. If the display is not needed for normal operation, the transmitter can be ordered without the LCD.
The security level that is set in the Programming Menu section of the manual will determine which calibrations, if any, may be
Figure 6
Remote Display Diagram
Display Error Messages
ovEr = The air velocity is greater than the maximum span value causing an Over
Range Error
UndEr = The air velocity is less than the minimum span value causing an Under Range
Error
FAiL = When the span or zero buttons are pressed, the air velocity value is out of the range to allow a correct setting. This may be due to a sensor failure. Err1 = The sensor is damaged.
Pluggable Display Diagram
Figure 5
Another option for models that do not have a display would be to use a Model A-435-A remote display tool which can plug into the connector shown in Figure 6. The remote display tool has two buttons that function identically to the buttons on the PCB.
PROGRAMMING MENUS
Home Menu
During normal operation, the display will be in the Home Menu and will display the current measured pressure and the engineering units.
Menu Access Security
While in the Home Menu, press and hold the Zero and Span buttons simultaneously until SECUr appears on the display in order to access the other programming menus. Upon releasing the buttons, the display will indicate the current security level.
If the current security level is the security level desired (i.e. Security Level 0), press and hold the span button for 3 seconds to enter the Velocity or Air Flow Menu.
If the security level is not the desired level, the security level can be changed temporarily to a lower security level or permanently to a higher level of security by pressing the zero button. A security code will appear on the display, and it can be changed to one of the codes listed in Table 3. The span button chooses which digit and the zero button increments the value of that digit. Pressing and holding the span button will store the value.
The level of access to the programming menus and the calibration is limited based on the security level. Table 3 details the level of access for each security level.
Loading...
+ 8 hidden pages