Dwyer Instruments Series APM, APM-100, APM-200, APM-101, APM-201 Instruction Manual

...
DWYER INSTRUMENTS, INC.
PO Box 373 • Michigan City IN 46360 USA Tel (800) 872-9141 • Fax (219) 872-9057
www.dwyer-inst.com
Analog Panel Meter
Series APM
Instruction Manual
0-20 mA, 4-20 mA, 0-5 V, 1-5 V, 10 V Inputs  NEMA 4X, IP65 Front  Universal 85-265 VAC, or 12/24 VDC Input Power Models  Large Dual-Line 6-Digit Display, 0.60" & 0.46"  Dual-Scale for Level Applications – Single Input  Isolated 24 VDC @ 200 mA Transmitter Power Supply  Signal Input Conditioning for Flow & Round Horizontal Tanks  Programmable Displays & Function Keys  Rate Displayed as Units per Second, Minute, Hour, or Day  Total, Grand Total or Non-Resettable Grand Total  9-Digit Totalizer with Total Overflow Feature  32-Point Linearization, Square Root, or Programmable Exponent  Multi-Pump Alternation Control  2 or 4 Relays + Isolated 4-20 mA Output for Rate or Total  External 4-Relays & Digital I/O Expansion Modules  RS-232 & RS-422/485 Serial Communication Options  Modbus
®
RTU Communication Protocol Standard
Tare Function
Bulletin: L-APM
Analog Panel Meter Instruction Manual
2
Disclaimer
The information contained in this document is subject to change without notice. Dwyer Instruments, Inc. makes no representations or warranties with respect to the contents hereof; and specifically dis­claims any implied warranties of merchantability or fitness for a par­ticular purpose.
!
CAUTION: Read complete
instructions prior to instal­lation and operation of the meter.
WARNING: Risk of electric shock or personal injury.
Warning
This product is not recommended for life support applications or ap­plications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. Dwyer Instruments, Inc. shall not be held liable for damages resulting from such improper use.
Limited Warranty
Dwyer Instruments, Inc. warrants this product against defects in ma­terial or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Dwyer Instruments, Inc.’s liability under this limited warranty shall not exceed the purchase val­ue, repair, or replacement of the defective unit.
Registered Trademarks
All trademarks mentioned in this document are the property of their re­spective owners.
© 2008-2011 Dwyer Instruments, Inc. All rights reserved.
www.dwyer-inst.com
Analog Panel Meter Instruction Manual
3
Table of Contents
INTRODUCTION ------------------------------------------------------------- 7
ORDERING INFORMATION ---------------------------------------------- 7 SPECIFICATIONS ----------------------------------------------------------- 8
General ------------------------------------------------------------------------------- 8 Process Input ---------------------------------------------------------------------- 9 Rate/Totalizer -------------------------------------------------------------------- 10 Relays ------------------------------------------------------------------------------ 11 Isolated 4-20 mA Transmitter Output ------------------------------------ 12 Modbus® RTU Serial Communications ---------------------------------- 13 PMA-12 Digital Input & Output Expansion Module ------------------ 13
COMPLIANCE INFORMATION ---------------------------------------- 14
Safety ------------------------------------------------------------------------------- 14 Electromagnetic Compatibility --------------------------------------------- 14
SAFETY INFORMATION ------------------------------------------------ 15 INSTALLATION ------------------------------------------------------------ 16
Unpacking ------------------------------------------------------------------------- 16 Panel Mounting Instructions ------------------------------------------------ 16 Configuration for 12 or 24 VDC Power Option ------------------------ 18 Transmitter Supply Voltage Selection (P+, P-) ----------------------- 19 Connections ---------------------------------------------------------------------- 19
Connectors Labeling --------------------------------------------------------- 20 Power Connections ---------------------------------------------------------- 20 Signal Connections ---------------------------------------------------------- 21 Modbus® RTU Serial Communications --------------------------------- 22 Relay Connections ----------------------------------------------------------- 22 Switching Inductive Loads -------------------------------------------------- 23 4-20 mA Output Connections ---------------------------------------------- 24 Analog Output Transmitter Power Supply ------------------------------ 24 External Relay & Digital I/O Connections ------------------------------ 25 Interlock Relay Feature ----------------------------------------------------- 26
SETUP AND PROGRAMMING ----------------------------------------- 27
Front Panel Buttons and Status LED Indicators --------------------- 28 Display Functions and Messages ----------------------------------------- 29 Main Menu ------------------------------------------------------------------------ 33 Setting Numeric Values ------------------------------------------------------ 34
Analog Panel Meter Instruction Manual
4
Reset Menu (reset) ------------------------------------------------------------ 34
Control Menu (Contrl) -------------------------------------------------------- 34 Setting Up the Rate/Totalizer Meter (setup) --------------------------- 35
Setting the Input Signal (input) ------------------------------------------ 36 Setting the Totalizer Features (total) ---------------------------------- 36 Dual-Scale for Level Application ------------------------------------------ 37 Setting the Decimal Point (dEc pt) -------------------------------------- 38 Programming the Rate/Totalizer (prog) -------------------------------- 39
Multi-Point Calibration & Scaling -------------------------------------- 40 Panel Meter Pro Software ---------------------------------------------- 40 Scaling the Meter (SCALE) ---------------------------------------------- 41 Time Base, Total Conversion Factor & Total Reset -------------- 43
Calibrating the Meter with External Source (Cal) ----------------- 44 Setting the Display Parameter & Intensity (dsplay) ----------------- 45 Display Setup Menu --------------------------------------------------------- 46 Character Set for Engineering Units Display (d unit) -------------- 47
Setting the Relay Operation (relay) ------------------------------------- 48
Relay Assignment (Assign) ----------------------------------------------- 49 Setting the Relay Action ---------------------------------------------------- 50 Programming Set and Reset Points ------------------------------------- 51 Setting Fail-Safe Operation ------------------------------------------------ 51 Programming Time Delay -------------------------------------------------- 51 Relay Action for Loss of 4-20 mA Input (Loop Break) --------------- 51
Relay and Alarm Operation Diagrams ----------------------------------- 52
High Alarm Operation (Set > Reset) ------------------------------------- 52 Low Alarm Operation (Set < Reset) -------------------------------------- 53 High Alarm with Fail-Safe Operation (Set > Reset) ------------------ 54 Low Alarm with Fail-Safe Operation (Set < Reset) ------------------- 55 Pump Alternation Control Operation ------------------------------------- 56 Rate Relay Sampling Operation ------------------------------------------ 57 Total Relay Sampling Operation ------------------------------------------ 57 Signal Loss or Loop Break Relay Operation --------------------------- 58 Time Delay Operation ------------------------------------------------------- 59
Relay Operation Details ------------------------------------------------------ 60
Overview ------------------------------------------------------------------------ 60 Relays Auto Initialization ---------------------------------------------------- 60 Fail-Safe Operation ---------------------------------------------------------- 60 Front Panel LEDs ------------------------------------------------------------- 61 Latching and Non-Latching Relay Operation -------------------------- 61 Non-Latching Relay (Auto) ------------------------------------------------- 62 Non-Latching Relay (A-nman) --------------------------------------------- 62 Latching Relay (LatcH) ----------------------------------------------------- 62 Latching Relay (Lt-Clr) ---------------------------------------------------- 63
Analog Panel Meter Instruction Manual
5
Acknowledging Relays ------------------------------------------------------ 63
Pump Alternation Control Applications (Altern) --------------------- 64 Setting Up the Interlock Relay (Force On) Feature ------------------ 67
Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 68 Setting Up the Password (pass) ------------------------------------------- 69
Protecting or Locking the Meter ------------------------------------------- 69 Total Reset Password & Non-Resettable Total ----------------------- 70 Making Changes to a Password Protected Meter -------------------- 71 Disabling Password Protection -------------------------------------------- 71
Advanced Features Menu ---------------------------------------------------- 72
Advanced Features Menu & Display Messages ---------------------- 73 Noise Filter (filter) -------------------------------------------------------- 76 Noise Filter Bypass (bypass) ---------------------------------------------- 76 Modbus® RTU Serial Communications (serial) --------------------- 77 Select Menu (SElEct) ------------------------------------------------------- 78 Signal Input Conditioning (Functn) -------------------------------------- 78 Low-Flow Cutoff (CutofF) -------------------------------------------------- 81 Analog Output Programming (AoutPr) ---------------------------------- 81 Programmable Function Keys User Menu (user) -------------------- 82 Tare (tare) --------------------------------------------------------------------- 83 Internal Source Calibration (ICAL) --------------------------------------- 83 Meter Copy Function (Copy) ----------------------------------------------- 86
METER OPERATION ----------------------------------------------------- 88
Front Panel Buttons Operation -------------------------------------------- 88 Function Keys Operation ---------------------------------------------------- 88 Maximum/Minimum Readings ---------------------------------------------- 89
TROUBLESHOOTING ---------------------------------------------------- 90
Diagnostics Menu (diag) ----------------------------------------------------- 90
Determining Software Version -------------------------------------------- 90
Reset Meter to Factory Defaults ------------------------------------------- 91
Factory Defaults & User Settings ----------------------------------------- 92
Troubleshooting Tips --------------------------------------------------------- 96 Alphabetical List of Display Functions & Messages --------------- 97
Analog Panel Meter Instruction Manual
6
Table of Figures
Figure 1: 1/8 DIN Panel Cutout and Mounting ................................... 16
Figure 2: Meter Dimensions - Side View ............................................ 17
Figure 3: Meter Dimensions - Top View ............................................. 17
Figure 4: Jumper Configuration for 12/24 VDC Power ..................... 18
Figure 5: Transmitter Supply Voltage Selection ............................... 19
Figure 6: Connector Labeling for Fully Loaded APM ....................... 20
Figure 7: Power Connections ............................................................. 20
Figure 8: Transmitters Powered by Internal Supply ......................... 21
Figure 9: Transmitter Powered by Ext. Supply or Self-Powered ..... 21
Figure 10: Voltage Input Connections ............................................... 22
Figure 11: Relay Connections ............................................................ 22
Figure 12: AC and DC Loads Protection ........................................... 23
Figure 13: Low Voltage DC Loads Protection ................................... 23
Figure 14: 4-20 mA Output Connections ........................................... 24
Figure 15: Expansion Modules & DIN Rail Mounting Kit .................. 25
Figure 16: External Relays Module Connections ............................. 25
Figure 17: Digital I/O Module Connections ....................................... 26
Figure 18. Interlock Connection ......................................................... 26
Figure 19: Acknowledge Relays w/Function Key or Digital Input ... 63
Figure 20: Meter Copy Connection .................................................... 86
Figure 21:1/8 DIN Panel Cutout Template ....................................... 105
Analog Panel Meter Instruction Manual
7
INTRODUCTION
The APM is a multipurpose, easy to use rate/totalizer ideal for flow rate, total, and control applications. It accepts current and voltage signals (e.g. 4-20 mA, 0-10 V). Three of the front panel buttons can be custom-programmed for specific opera­tion.
The basic model includes an isolated 24 VDC transmitter power supply that can be used to power the input transmitter or other devices. An additional isolated 24 VDC power supply is included with the 4-20 mA output option.
A fully loaded APM rate/totalizer meter has the following: four SPDT relays, 4-20 mA output, and two 24 VDC power supplies. The APM capabilities may be enhanced by adding the following external expansion modules: four SPST relays (creating an eight-relay rate/totalizer), two digital I/O modules with four inputs and four outputs each, and RS-232 or RS-485 communication adapters.
The eight relays can be used for alarm indication or process control applications. The 4-20 mA isolated output, Modbus
®
RTU serial communications, and digital I/O
options make the APM an excellent addition to any system.
ORDERING INFORMATION
85-265 VAC Model
12/24 VDC Model
Options Installed
APM-100 APM-200 No options APM-101 APM-201 4-20 mA output APM-120 APM-220 2 relays APM-121 APM-221 2 relays & 4-20 mA output APM-140 APM-240 4 relays APM-141 APM-241 4 relays & 4-20 mA output
Accessories
Model Description
PMA-01 RS-232 serial adapter PMA-02 Meter copy cable PMA-03 RS-422/485 serial adapter PMA-04 RS-232 to RS-422/485 isolated converter PMA-05 RS-232 to RS-422/485 non-isolated converter PMA-06 USB to RS-232 non-isolated converter PMA-07 USB to RS-422/485 isolated converter PMA-08 USB to RS-422/485 non-isolated converter PMA-09
Suppressor (snubber): 0.01 µF/470 , 250 VAC PMA-10 DIN rail mounting kit for two expansion modules PMA-11 4 SPST (Form A) relays PMA-12 4 digital inputs & 4 digital outputs (2 may be connected)
Analog Panel Meter Instruction Manual
8
SPECIFICATIONS
Except where noted all specifications apply to operation at +77°F (+25°C).
General
DISPLAY
Main display: 0.6" (15 mm) high, red LEDs Second display: 0.46" (12 mm) high, red LEDs 6 digits: each (-99999 to 999999), with lead zero blanking.
DISPLAY INTENSITY
Eight user selectable intensity levels.
DISPLAY UPDATE RATE
5/second (200 ms).
OVERRANGE
Display flashes
999999.
UNDERRANGE
Display flashes
-99999.
DISPLAY ASSIGNMENT
The main (Big) and small (Little) displays may be assigned to rate, total, grand total, alternate rate & total, max/min, units (small display only), set points, and Modbus
®
input.
PROGRAMMING METHODS
Four front panel buttons, digital inputs, PC with Panel Meter Pro software, or cloning using Copy function.
NOISE FILTER
Programmable from 2 to 199 (0 will disable filter).
FILTER BYPASS
Programmable from 0.1 to 99.9% of calibrated span.
RECALIBRATION
All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
MAX/MIN DISPLAY
Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
PASSWORD
Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals.
Pass 1: Allows use of function keys and digital inputs. Pass 2: Allows use of function keys, digital inputs and editing set/reset points. Pass 3: Restricts all programming, function keys, and digital inputs. Total: Prevents resetting the total manually.
Gtotal: Prevents resetting the grand total manually.
NON-VOLATILE MEMORY
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
POWER OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or jumper selectable 12/24 VDC 10%, 15 W max.
FUSE
Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
ISOLATED TRANSMITTER POWER SUPPLY
Terminals P+ & P-: 24 VDC 5% @ 200 mA max (standard), (12/24 VDC powered models rated @ 100 mA max). 5 or 10 VDC @ 50 mA max, selectable with internal jumper J4.
Analog Panel Meter Instruction Manual
9
NORMAL MODE REJECTION
Greater than 60 dB at 50/60 Hz.
ISOLATION
4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
OVERVOLTAGE CATEGORY
Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installa­tion Overvoltage Category III.
ENVIRONMENTAL
Operating temperature range: -40 to 149°F (-40 to 65°C). Storage temperature range: -40 to 185°F (-40 to 85°C). Relative humidity: 0 to 90% non-condensing.
CONNECTIONS
Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial com­munication adapters.
ENCLOSURE
1/8 DIN, high impact plastic, UL 94V-0, color: black.
MOUNTING
1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm) Two panel mounting bracket assemblies are provided.
TIGHTENING TORQUE
Screw terminal connectors: 5 lb-in (0.56 Nm).
OVERALL DIMENSIONS
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D).
WEIGHT
9.5 oz (269 g).
WARRANTY
1 year parts & labor.
Process Input
INPUTS
Field selectable: 0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus
®
PV (Slave)
ACCURACY
±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span.
TEMPERATURE DRIFT
0.003% of calibrated span/°F max from 32 to 149°F (0.005% from 0 to 65°C), 0.006% of calibrated span/°F max from -40 to 32°F (0.01% from -40 to 0°C)
SIGNAL INPUT CONDITIONING
Linear, square root, programmable exponent, or round horizontal tank volume calculation.
MULTI-POINT LINEARIZATION
2 to 32 points.
PROGRAMMA­BLE EXPONENT
1.0001 to 2.9999.
LOW-FLOW CUTOFF
0-999999 (0 disables cutoff function).
Analog Panel Meter Instruction Manual
10
DECIMAL POINT
Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd.
CALIBRATION RANGE
Input Range
Minimum Span
Input 1 & Input 2 4-20 mA 0.15 mA 10 V
0.10 V An Error message will appear if the input 1 and input 2 signals are too close together.
INPUT IMPEDANCE
Voltage ranges: greater than 1 M. Current ranges: 50 - 100
(depending on resettable fuse impedance).
INPUT OVERLOAD
Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
Rate/Totalizer
DISPLAY ASSIGNMENT
The main (Big) and small (Little) displays may be assigned to rate, total, grand total, alternate R & T, units, and set point.
RATE DISPLAY INDICATION
-99999 to 999999, lead zero blanking. “R” LED illuminates while displaying rate.
TOTAL DISPLAY & TOTAL OVERFLOW
0 to 999,999; automatic lead zero blanking. “T” LED is illumi­nated while displaying total or grand total. Up to 999,999,999 with total-overflow feature. “
oF” is dis-
played to the left of total overflow and LED is illuminated.
ALTERNATING DISPLAY
Either display may be programmed to alternate between rate and total or rate and grand total every 10 seconds.
TOTAL DECIMAL POINT
Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Total decimal point is independent of rate decimal point.
TOTALIZER
Calculates total based on rate and field programmable mul­tiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed.
TOTALIZER ROLLOVER
Totalizer rolls over when display exceeds 999,999,999. Relay status reflects display.
TOTAL OVERFLOW OVERRIDE
Program total reset for automatic with 0.1 second delay and set point 1 for 999,999.
TOTALIZER PRESETS
Up to eight, user selectable under setup menu. Any set point can be assigned to total and may be programmed anywhere in the range of the meter for total alarm indica­tion.
Analog Panel Meter Instruction Manual
11
PROGRAMMA­BLE DELAY ON RELEASE
0.1 and 999.9 seconds; applied to the first relay assigned to total or grand total.
If the meter is programmed to reset total to zero automati­cally when the preset is reached, then a delay will occur before the total is reset.
TOTAL RESET
Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications.
TOTAL RESET PASSWORD
Total and grand total passwords may be entered to prevent resetting the total or grand total from the front panel.
NON­RESETTABLE TOTAL
The grand total can be programmed as a non-resettable total by entering the password “050873”.
!
Caution!
Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled.
Relays
RATING
2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP ( 50 W) @ 125/250 VAC for inductive loads.
NOISE SUPPRESSION
Noise suppression is recommended for each relay contact switching inductive loads; see page 23 for details.
RELAY ASSIGNMENT
Relays may be assigned to rate, total, or grand total.
DEADBAND
0-100% of span, user programmable.
HIGH OR LOW ALARM
User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
RELAY OPERATION
Automatic (non-latching). Latching (requires manual acknowledge). Sampling (based on time). Pump alternation control (2 to 8 relays). Off (disable unused relays and enable Interlock feature). Manual on/off control mode.
RELAY RESET
User selectable via front panel buttons, digital inputs, or PC
1. Automatic reset only (non-latching), when the in­put passes the reset point or total is reset to zero.
2. Automatic + manual reset at any time (non-latching).
3. Manual reset only, at any time (latching).
4. Manual reset only after alarm condition has cleared (L).
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
Analog Panel Meter Instruction Manual
12
TIME DELAY
0 to 999.9 seconds, on & off relay time delays Programmable and independent for each relay.
FAIL-SAFE OPERATION
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
AUTO INITIALIZATION
When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
OUTPUT SOURCE
Rate/process, total, grand total, max, min, set points 1-8, or manual control mode.
SCALING RANGE
1.000 to 23.000 mA for any display range.
CALIBRATION
Factory calibrated: 4.000 to 20.000 = 4-20 mA output.
ANALOG OUT PROGRAMMING
23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break.
ACCURACY
± 0.1% FS ± 0.004 mA.
TEMPERATURE DRIFT
0.22 µA/°F max from 32 to 149°F (0.4 µA/°C from 0 to 65°C),
0.44 µA/°F max from -40 to 32°F (0.8 µA/°C from -40 to 0°C).
Note: Analog output drift is separate from input drift.
ISOLATED TRANSMITTER POWER SUPPLY
Terminals I+ & R: 24 VDC 5% @ 40 mA maximum; may be used to power the 4-20 mA output or other devices. Refer to Figure 6 on page 20 and Figure 14 on page 24.
EXTERNAL LOOP POWER SUPPLY
35 VDC maximum.
OUTPUT LOOP RESISTANCE
Power supply Minimum Maximum
24 VDC
10 700
35 VDC (external)
100 1200
Analog Panel Meter Instruction Manual
13
Modbus® RTU Serial Communications
SLAVE ID
1 – 247 (Meter address).
BAUD RATE
300 - 19,200 bps.
TRANSMIT TIME DELAY
Programmable between 0 and 199 ms or transmitter always on for RS-422 communication.
DATA
8 bit (1 start bit, 1 or 2 stop bits).
PARITY
Even, Odd, or None with 1 or 2 stop bits.
BYTE-TO-BYTE TIMEOUT
0.01 – 2.54 second.
TURN AROUND DELAY
Less than 2 ms (fixed).
Note: Refer to the Modbus® Register Tables located at www.dwyer-inst.com for details.
PMA-12 Digital Input & Output Expansion Module
CHANNELS
4 digital inputs & 4 digital outputs per module.
SYSTEM
Up to 2 modules for a total of 8 inputs & 8 outputs.
DIGITAL INPUT LOGIC HIGH
3 to 5 VDC.
DIGITAL INPUT LOGIC LOW
0 to 1.25 VDC.
DIGITAL OUTPUT LOGIC HIGH
3.1 to 3.3 VDC.
DIGITAL OUTPUT LOGIC LOW
0 to 0.4 VDC.
SOURCE CURRENT
10 mA maximum output current.
SINK CURRENT
1.5 mA minimum input current.
+5 V TERMINAL
To be used as pull-up for digital inputs only Connect normally open pushbuttons across +5 V & DI 1-4.
Analog Panel Meter Instruction Manual
14
COMPLIANCE INFORMATION
Safety
UL & c-UL LISTED
USA & Canada UL 508 Industrial Control Equipment
UL FILE NUMBER
E212517
FRONT PANEL
UL Type 4X, NEMA 4X, IP65; panel gasket provided
LOW VOLTAGE DIRECTIVE
EN 61010-1:2001 Safety requirements for measurement, control, and laboratory use
Electromagnetic Compatibility
EMISSIONS
EN 55022:2006/A1:2007 Class A ITE emissions requirements.
Radiated Emissions
Class A.
AC Mains Conducted Emissions
Class A.
IMMUNITY
EN 61326-1:2006 Measurement, control, and laboratory equipment.
EN 61000-6-2:2005 EMC heavy industrial generic immunity standard.
RFI - Amplitude Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz).
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz).
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz).
Electrical Fast Transients
±2kV AC mains, ±1kV other.
Electrostatic Discharge
±4kV contact, ±8kV air.
RFI - Conducted
10V, 0.15-80 MHz, 1kHz 80% AM.
AC Surge
±2kV Common, ±1kV Differential.
Surge
1KV (CM).
Power-Frequency Magnetic Field
3 A/m 70%V for 0.5 period.
Voltage Dips
40%V for 5 & 50 periods. 70%V for 25 periods.
Voltage Interruptions
<5%V for 250 periods.
Analog Panel Meter Instruction Manual
15
Note:
Testing was conducted on APM meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.
Declaration of Conformity available at www.dwyer-inst.com.
SAFETY INFORMATION
!
CAUTION: Read complete
instructions prior to instal­lation and operation of the meter.
WARNING: Risk of electric shock or personal injury.
Warning!
Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.
Analog Panel Meter Instruction Manual
16
INSTALLATION
There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applica­tions. Instructions are provided for setting up a 12/24 VDC po­wered meter to operate from 12 VDC and for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 18.
Unpacking
Remove the meter from box. Inspect the packaging and con­tents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x
45 mm). Refer to Figure 1 for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until me­ter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
Note: See Figure 21 on page 105 for 1/8 DIN Panel Cutout Template
3.622" (92mm)
1.772"
(45mm)
Panel Cutout to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances: A: +0.032 (+0.8mm)
-0.000 (-0.0mm) B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Panel
Gasket
Mounting
Bracket
Mounting
Screw
Removable Connectors
Figure 1: 1/8 DIN Panel Cutout and Mounting
Analog Panel Meter Instruction Manual
17
Mounting Dimensions
1.76"
(45 mm)
0.59"
(15 mm)
4.77"
(121 mm)
2.45"
(62 mm)
5.05"
(128 mm)
Figure 2: Meter Dimensions - Side View
3.61"
(92 mm)
4.17"
(106 mm)
4.68"
(119 mm)
Figure 3: Meter Dimensions - Top View
Analog Panel Meter Instruction Manual
18
Configuration for 12 or 24 VDC Power Option
Warning!
Do not exceed voltage rating of the selected configuration.
Meters equipped with the 12/24 VDC power option are shipped from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power connector, for 12 V as shown below.
MAIN BOARD
24 VDC 12 VDC POWER
J9
12 V
24 V
J9 CONFIGURATION
Factory Default
M-LINK
+ _
Figure 4: Jumper Configuration for 12/24 VDC Power
Analog Panel Meter Instruction Manual
19
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector, for the desired excitation voltage as shown.
MAIN BOARD
INPUT SIGNAL
J4
5 V
10 V
24 V
J4 CONFIGURATION
Factory Default
P+
P-
mA+
COM
V+
Figure 5: Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter.
!
Caution!
Use copper wire with 140°F (60°C) or 140/167°F (60/75°C) insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the meter and ensure personnel safety.
Analog Panel Meter Instruction Manual
20
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all con­nectors available with requested configuration.
Warning!
Do not connect any equipment other than Dwyer Instruments, Inc.’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
DW1815
RI- I+
MA OUT
132
POWER
+
-
SIGNAL
P- COMP+ V+ mA+
3412 5
M-LINK
CNONO NC NC C
RELAY4 RELAY3
4365 21
CNONO NC NC C
RELAY2 RELAY1
4365 21
123 45678
21
Figure 6: Connector Labeling for Fully Loaded APM
Power Connections
Power connections are made to a two-terminal connector labeled POWER on Figure 6. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+
-
Figure 7: Power Connections
Analog Panel Meter Instruction Manual
21
Signal Connections
Signal connections are made to a five-terminal connector labeled SIGNAL on Figure 6. The COM (common) terminal is the return for the
4-20 mA and the 10 V input signals.
Current and Voltage Connections
The following figures show examples of current and voltage connections. There are no switches or jumpers to set up for current and voltage inputs.
Setup and programming is performed through the front panel buttons.
-+
mA+P-
21354
P+ V+
COM
INPUT SIGNAL
3-Wire 4-20 mA
Transmitter
Signal
+-
2-Wire
4-20 mA
Transmitter
mA+P-
21354
P+ V+
COM
INPUT SIGNAL
Figure 8: Transmitters Powered by Internal Supply
+--+
External
Power
Supply
2-Wire
4-20 mA
Transmitter
mA+P-
21354
P+ V+
COM
INPUT SIGNAL
-+
mA+P-
21354
P+ V+
COM
INPUT SIGNAL
2-Wire 4-20 mA
Self-Powered
Transmitter
Figure 9: Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable fuse. The display may or may not show a fault condition depending on the nature of the overload.
The fuse limits the current to a safe level when it detects a fault condi­tion, and automatically resets itself when the fault condition is removed.
Analog Panel Meter Instruction Manual
22
-+
+
Voltage
Signal
mA+P-
21354
P+ V+
COM
INPUT SIGNAL
mA+P-
21354
P+ V+
COM
INPUT SIGNAL
3-Wire Voltage
Transducer
Signal
-
Figure 10: Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.
Modbus® RTU Serial Communications
Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 6. Use the PMA-01 for RS-232 interfacing or the PMA­03 for RS-422/485 interfacing. The same port is used for interfacing with all expansion modules (e.g. external relays, digital I/O).
Use the PMA-02 meter copy cable for meter-to-meter interfacing for cloning purposes (i.e. copying settings from one meter to other meters).
Relay Connections
Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 on Figure 6. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of the cor­responding relay. The relays’ C terminals should not be confused with the COM (common) terminal of the INPUT SIGNAL connector.
CNONO NC NC C
RELAY4 RELAY3
4365 21
CNONO NC NC C
RELAY2 RELAY1
4365 21
Figure 11: Relay Connections
Analog Panel Meter Instruction Manual
23
Switching Inductive Loads
The use of suppressors (snubbers) PMA-09 is strongly recommended when switching inductive loads to prevent disrupting the microproces­sor’s operation. The suppressors also prolong the life of the relay con­tacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies. Refer to the following circuits for RC network assembly and installation.
C
R
C
R
Figure 12: AC and DC Loads Protection
Choose R and C as follows: R: 0.5 to 1 for each volt across the contacts.
C: 0.5 to 1 µF for each amp through closed contacts.
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC
network may also be installed across the load. Experiment for best results.
Figure 13: Low Voltage DC Loads Protection
RC Networks Available from Dwyer Instruments, Inc.
RC networks are available from Dwyer Instruments, Inc. and should be applied to each relay contact switching an inductive load. Part number: PMA-09.
Note:
Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Use a diode with a reverse breakdown voltage two to three times the circuit vol­tage and forward current at least as large as the load current.
Analog Panel Meter Instruction Manual
24
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connec­tor terminals labeled MA OUT. The 4-20 mA output may be powered internally or from an external power supply.
12-35 VDC
Power
Supply
+
4-20 mA
Input Meter
-
+
RI- I+
132
RELAY1
321
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
RI- I+
MA OUT
132
RELAY1
321
24 V
MA OUT
Figure 14: 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the return. This power supply is capable of sourcing up to 40 mA.
Analog Panel Meter Instruction Manual
25
External Relay & Digital I/O Connections
The relay and the digital I/O expansion modules PMA-11 & PMA-12 are connected to the meter using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are identical and interchangeable; they are used to connect additional modules to the sys­tem.
Note: The jumper located between the RJ45 connectors of the PMA-12
must be removed on the second digital I/O module in order for the system to recognize it as module #2.
Warning!
Do not connect or disconnect the expansion modules with the power on! More detailed instructions are provided with each op­tional expansion module.
Figure 15: Expansion Modules & DIN Rail Mounting Kit
12
RLY5 RLY6 RLY7 RLY8
345678
NO C NO C NO C NO C
Figure 16: External Relays Module Connections
Analog Panel Meter Instruction Manual
26
123456
+5 I1 I2 I3 I4 O1
78
O2 O3
910
O4 G
DI 1-4 DO 1-4
5 VDC GND
Figure 17: Digital I/O Module Connections
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay. This feature is enabled by configuring the relay, and relative digital input(s) (see page
67). In one example, dry interlock contacts are connected in series to
one digital input which will be used to force on (energize) the assigned interlock power relay when all interlock contacts are closed (safe). The interlock relay front panel LED flashes when locked out. The interlock relay would be wired in-series with the load (N/O contact). See below.
Figure 18. Interlock Connection
Analog Panel Meter Instruction Manual
27
SETUP AND PROGRAMMING
The meter is factory calibrated prior to shipment to read in milliamps and volts depending on the input selection. The calibration equipment is certified to NIST standards.
Overview
There are no jumpers to set for the meter input selection. Setup and programming is done through the front panel buttons. After power and input signal connections have been completed and veri-
fied, apply power to the meter.
Analog Panel Meter Instruction Manual
28
Front Panel Buttons and Status LED Indicators
Button Symbol
Description LED Status
Menu 1-8 Alarm 1 – 8 indicator
Right arrow/F1 R Rate indicator
Up arrow/F2 T
Total indicator or Flashing: Tare
Enter/F3 G T Grand Total indicator
Note: Alarms 5-8 are enabled when
relay expansion module is installed.
Total overflow indicator
M
Manual control relays &/or analog output
Press the Menu button to enter or exit the Programming Mode at
any time.
Press the Right arrow button to move to the next digit during digit
or decimal point programming.
Press or hold the Up arrow button to scroll through the menus,
decimal point, or to increment the value of a digit.
Press the Enter button to access a menu or to accept a setting.  Press and hold the Menu button for three seconds to access the
advanced features of the meter.
Analog Panel Meter Instruction Manual
29
Display Functions and Messages
The meter displays various functions and messages during setup, pro­gramming, and operation. The following table shows the main menu functions and messages in the order they appear in the menu.
Display Parameter Action/Setting Description
reset
Reset
Press Enter to access the Reset menu.
Rst t
Reset total
Press Enter to reset total.
Rst Gt
Reset grand total
Press Enter to reset grand total.
Rst Hi
Reset high
Press Enter to reset max display.
Rst Lo
Reset low
Press Enter to reset min display.
Rst HL
Reset high & low
Press Enter to reset max & min displays.
Contrl
Control
Enter Control menu.
Auto
Automatic
Press Enter to set meter for automatic operation.
mAn
Manual
Press Enter to manually control relays or analog output operation.
setup
Setup
Enter Setup menu.
Input
Input
Enter Input selection menu
mA
4-20 mA
Set meter for 4-20 mA input
volt
0-10 VDC
Set meter for 10 VDC input
Total
Total
Enable or disable totalizer features
level
Level
Enter Level menu and select Yes for dual­scale display or
No for single scale display
Dec pt
Decimal point
Set decimal point for rate, total, grand total.
prog
Program
Enter the Program menu.
sCalE
Scale
Enter the Scale menu.
Cal
Calibrate
Enter the Calibrate menu.
Inp 1
Input 1
Calibrate input 1 signal or program input 1 value.
Dis 1
Display 1
Program display 1 value.
Analog Panel Meter Instruction Manual
30
Display Parameter Action/Setting Description
Inp 2
Input 2
Calibrate input 2 signal or program input 2 value (up to 32 points).
Dis 2
Display 2
Program display 2 value (up to 32 points).
Error
Error
Error, calibration not successful, check signal or programmed value.
dsplay
Display
Enter the Display menu.
big
Big display
Press Enter to assign the Main display parameter (default: PV or rate).
Little
Little display
Press Enter to assign the small display parameter (default: total).
d-Inty
Display intensity
Set display intensity level from 1 to 8.
RELaY
Relay
Enter the Relay menu.
Assign
Assignment
Assign relays to rate, total, or grand total.
Asign1
Assign 1
Relay 1 assignment.
rATE
Rate
Assign relay to rate.
totAL
Total
Assign relay to total.
G total
Grand total
Assign relay to grand total.
RLY 1
Relay 1
Relay 1 setup.
Act 1
Action 1
Set relay 1 action.
Auto
Automatic
Set relay for automatic reset.
A-nman
Auto-manual
Set relay for automatic & manual reset any time.
LatCH
Latching
Set relay for latching operation (relays assigned to rate).
Lt-CLr
Latching­cleared
Set relay for latching operation with ma­nual reset only after alarm condition has cleared (relays assigned to rate).
Altern
Alternate
Set relay for pump alternation control (relays assigned to rate).
Sanmpl
Sampling
Set relay for sampling operation
OFF
Off
Disable relay and front panel status LED (select off to enable interlock feature).
Set 1
Set 1
Program set point 1.
Loading...
+ 78 hidden pages