Dwyer Instruments A-IEF-DSP User manual

Series A-IEF Remote Display
(A-IEF-FDSP-RM) SHOWN
6.365
6X .193
®
Specications - Installation and Operating Instructions
Full functional display
A-IEF-FDSP-RM
3.976
Bulletin F-IEF-DSP-CE
6.365
4.790
Indicator display
A-IEF-IDSP-RM
The Series A-IEF Remote Display can be installed almost anywhere near a Series
IEF ow transmitter or IEFB thermal energy meter. Both the indicator display (A-IEF­IDSP-RM) and the full functional display (A-IEF-FDSP-RM) have a maximum display cable length of 100 ft (30 m) to permit easy viewing of ow readings. The full functional display allows for convenient adjustment of conguration settings and allows the user to save the IEF or IEFB conguration settings to a computer for printing.
• Full functional display can be used to set up the IEF/IEFB and adjust the settings if it is installed in a hard-to-reach location.
• Indicator display makes it convenient to read process values if the meter is inaccessible.
• Varying cable lengths of up to 100 ft (30 m) allows for exible installation on a wall or pipe mount.
• Easy to install and wire in the eld.
APPLICATIONS
• Mechanical rooms with a small footprint
• Hard-to-reach piping
• Boilers and chillers
• Chilled water
• Condenser water
MODEL CHART Model Description A-IEF-FDSP-RM
A-IEF-IDSP-RM
ACCESSORIES Model Description A-IEF-CBL-50 Plenum rated cable 50 ft (15.2 m)
SELLABLE PARTS Model Description A-IEF-LID IEF blank replacement lid assembly
INCLUDED WITH THE REMOTE DISPLAY
Carefully unpack the shipping container of the remote display and remove the following items: (1) Remote display with mounting bracket (2) Pipe clamps (1) 3 mm allen wrench (not shown) (1) Adapter PCBA board, screw and
stand-off (not shown)
MOUNTING BRACKET
A-IEF-DSP-RM full functional remote display (CE) A-IEF-DSP-RM indicator remote display
Shown with IEF-HN-PG and
A-IEF-VLV-BR accessory valve
• Make-up water
• Heating water
• Boiler feed water
• Steam condensate
(1) 3 hole grommet (not shown) (1) 1/2˝ NPT conduit tting (not shown)
PIPE CLAMPS
6X .193
SPECIFICATIONS Temperature Limits: Ambient: -4 to 158°F (-20 to 70°C); Storage: -40 to 185°F
(-40 to 85°C).
Display: 3.3˝ diagonal graphic LCD. Backlight (full display only). Enclosure Material Housing: Powder coated die cast aluminum. Enclosure Rating: NEMA 4X (IP66). Electrical Connection: Removable terminal blocks, #22 AWG (100 ft (30 m) max). Mounting: Wall or pipe mount. Mounting Orientation: Any orientation. Weight: 2.46 lbs (1.12kg).
INSTALLATION
The Series IEF/IEFB can support one display. If the IEF/IEFB has the local LCD display option (-LCD), the display will need to be replaced by a blank cover (blank cover offered separately, part number A-IEF-LID). The remote display must be connected to the IEF/IEFB owmeter with an eight conductor shielded cable (maximum length of 100 ft (30 m)). The provided adapter PCBA board will need to be installed in the IEF/ IEFB owmeter to connect to the remote display cable. For installations where the remote display is attached to a pipe, the included pipe clamps should be used.
Note: The power to the IEF/IEFB must be turned off before installation of the remote display.
Mounting the Remote Display
Locate an appropriate location that allows for visibility of the remote display. The remote display is suitable for mounting on a at surface or mounted to a pipe in any orientation; clamps are supplied for pipe sizes 3˝ to 12˝ (76.2 to 304.8 mm).
Surface/Wall Mount
To mount the remote display to a at surface such as a wall, hold the remote display in the desired location, mark hole locations on the at surface using the attached bracket as a template, drill holes and mount the remote display with screws suitable for surface and bracket slot dimensions.
Figure 2: Surface mount template (reverse view, not to scale)
Full functional display
A-IEF-FDSP-RM
4X .216
3.976
4.790
FULL FUNCTIONAL DISPLAY
Figure 1: Included items
RECOMMENDED INSTALLATION TOOLS
• Philips #2 screwdirver
• 1/8˝ slotted screwdriver
• Appropriate fasteners for wall mounting (wall mount installations)
• 5/16˝ nut driver or 1/4˝ slotted screwdriver (pipe mount installations)
• 1/4˝ nut driver (for standoff installation)
Find Quality Products Online at: sales@GlobalTestSupply.com
ADAPTER PCBA BOARD
www.GlobalTestSupply.com
Pipe Mount
To mount the remote display to a pipe, thread the pipe clamp through the appropriate slots on the mounting bracket as shown below in Figure 3.
Figure 3: Pipe clamps
Once the pipe clamps are in place, the remote display may be mounted in any orientation. See Figure 4 below for recommended orientations.
VERTICAL PIPE INSTALLATION HORIZONTAL INSTALLATION
Figure 4: Pipe installation
WIRING Remote Display Cable Installation and Wiring
The cable connecting the remote display to the Series IEF or IEFB will wire into two removable terminal blocks located on the back of the remote display lid.
The cable will need to have a sufcient service loop inside the remote display for easy access [9˝ (22 cm) is recommended]. Similar to the IEF/IEFB, the cable wires should be stripped approximately 0.22 in (5.59 mm). A 1/8˝ slotted screwdriver can be used to tighten the terminal block screws. For Dwyer Instruments plenum cable A-IEF-CBL-X, the recommended colors codes are:
Remote Display Terminal Wire Color Remote Display Terminal Wire Color
DAT
CLK GND VCC SHIELD*
*Connect the shield/drain wire on CE units.
Note: Refer to Figure 5 wiring diagram for proper wiring of remote display to IEF/IEFB. *Connect the shield/drain wire on CE units.
REMOTE DISPLAY LID
Note: Use the USB connector near the terminal blocks to connect the display to a computer in order to to print out the conguration values for the IEF/IEFB (supported on the full functional display only). See the IEF/IEFB manual F-IEF-F or F-IEFB-F for details.
Note: For full functioning display A-IEF-FDSP-RM if the display lock out feature is desired the switch is located on the back of the display as shown below:
Black Brown Red Orange Metal
Figure 5: Wiring diagram
DAT CLK
GND
VCC
*SHIELD
VCC
GND
VCC VCC GND GND
DAT CLK GND VCC IEF/IEFB ADAPTER BOARD VCC GND
Yellow
Green Blue
Violet
In order for the remote display to operate an adapter PCBA board, shown below, must be installed in the display port of the Series IEF or IEFB.
Figure 7: Adapter PCBA board
The terminal block wire entries face the center of the cover. After connecting the cable to the remote display, use a 3 mm Allen wrench to remove the tether-mounting screw from the IEF/IEFB and install the remote display cover to the housing (The cover has four screws).
Using the supplied 3mm Allen wrench, begin by unscrewing the (4) captured screws of the Series IEF or Series IEFB to remove the lid from the enclosure.
Note: The lid is tethered to the IEF/IEFB enclosure to allow for convenient wiring. The lid is only tethered in the base unit.
Mount the adapter board and afx to the Series IEF or IEFB by screwing in supplied screw to the stand off as pictured below.
Figure 8: Installed IEF/IEFB adapter PCBA board with tether
Feed the remote display wiring cable into the Series IEF/IEFB housing through the grommet, as shown below. Connect to the removable terminal blocks located on the adapter board.
Figure 9: IEF/ IEFB grommet two and three hole grommet
IEF/IEFB Cable Installation (cable gland option):
If the IEF/IEFB has a cable gland option with a 2 hole grommet, insert the included 3 hole insert. First, disconnect the A and B cables from the IEF/IEFB terminal blocks. Fully loosen the cable gland nut onto the A and B cables. Remove the cables from the IEF/IEFB. Remove the two hole cable gland insert and install the included 3 hole cable gland insert. This will allow each cable to be installed in the IEF/IEFB. For easier installation, insert the remote display cable, the A cable, and the B cable at the same time. Connect the A and B cables to the IEF/IEFB terminal blocks (See the IEF/IEFB manual F-IEF-F or F-IEFB-F for details.) After connecting the A and B cables, the IEF/IEFB PCBA adapter board can be installed.
Once the wiring of the remote display is complete, install a blank cover on the IEF unit (not a LCD cover). Use a 3 mm hex key to tighten the four cover screws.
MAINTENANCE/REPAIR
Upon nal installation of the Series IEF Remote Display, no routine maintenance is required. The display is not eld serviceable and it is not possible to repair the unit. Field repair should not be attempted and may void warranty.
Power must be supplied to the IEF/IEFB prior to this unit being operational. For further instruction on display use refer to bulletin F-IEF-F or F-IEFB-F
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.
Figure 6
Printed in U.S.A. 12/19 FR# 444519-01©Copyright 2019 Dwyer Instruments, Inc.