Dwyer Instruments AFG-2, AFG-1 User manual

Series AFG Averaging Flow Grid
Specifications - Installation and Operating Instructions
SECTION A-A
1/64
[.396]
SCALE 2:1
A
Bulletin F-AFG
The Series AFG Flow Grid is an outstandingly simple yet accu-
rate and cost effective alternative to other duct mounted pressure sensors. Once installed and connected to a suitable measuring instrument, the device will provide years of trouble free monitoring of both air and gas flow. Fitting the AFG Flow Grid is simple, with the unit supplied in kit form to allow both workshop and on-site installation into a wide range of square and circular ducts.
HOW THE AFG FLOW GRID WORKS
The AFG Flow Gird consists of two tubes mounted diagonally across a square or rectangular duct, or diametrically across a round duct. The tubes are drilled with a series of equi-spaced holes.
The holes in one tube face directly upstream and sense total pres­sure, while the pairs of holes in the second tube also face forward but at an included angle of 79 degrees, sensing static pressure.
The total and (sub) static pressures are averaged along the length of each tube and provide pressure signals at connectors outside the duct wall. The pressure differentials across these connectors constitute the output signal.
CONSTRUCTION
ØA
2
A
B
[27]
[51]
1-3/16
[30.16]
1-11/16
[42.86]
[2.38]
1-1/16
SPECIFICATIONS Service: Monitor air or compatible gas flow . Wetted Materials:304 SS, PVC, Polyurethane, acetyl plas-
tics, and neoprene rubber.
Accuracy: ±5%. Maximum Temperature: 176ºF (80ºC). Velocity Range:295.2 ft/min to 5904 ft/min (1.5 to 30 m/sec). Diameter of T ubes:5/16˝ (8 mm) or 5/8˝ (16 mm). Max Duct Diagonal: 60.4˝ (153.4 cm). Max Duct Diameter: 59.4˝ (150.9 cm). Process Connections: 5/16˝ barbed. Weight: AFG-1: 1 lb (454 g); AFG-2: 3 lb (1361 g).
APPLICATIONS
The AFG Flow Grids will give useful and reliable readings in a wide variety of ‘in duct’ locations often where other flow rate measuring devices are found to be unsatisfactory.
However , AFG Flow Grids should not be used in conditions of high humidity or where material of a sticky nature is present in the air stream, as a build-up of deposits on the pressure tubes or in the pressure holes will affect calibration. Where a high dust burden is likely to be encountered, it is advisable to provide access for cleaning when installing an AFG Flow Grid.
Positioning in Ducts: The AFG Flow Grids should be positioned in straight lengths of duct and at right angles to the axis of the duct. The following cri­teria should be complied with when positioning an AFG Flow Grid:
5/32
The output connectors are 1/4" diameter and are intended for use with plastic tube.
The AFG Flow Grids must not be used in air temperatures above 176ºF (80ºC).
1. Allow at least 3.5 diameters (3.5D) of duct upstream from 1D bends and minor obstructions.
2. Major obstructions such as right angled bends and opposed blade dampers require greater lengths of upstream duct (See the last page).
3. Allow at least 1D of duct downstream of the AFG Flow Grid before any change to the duct cross section or obstruction to the flow. Shorter lengths are likely to increase pressure loss.
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
4. Avoid a sudden expansion immediately before an AFG Flow Grid (See Fig. 2a).
5. A local contraction at the plane of the AFG Flow Grid is a use­ful technique to increase pressure differential when velocities are low (See Fig. 2b).
6. Where persistent swirl is expected it is advisable to install an anti-swirl device at least 1D upstream from the AFG Flow Grid.
Note: For rectangular duct D = Width + Height of Duct/ 2
a) Unacceptable
b) Acceptable
Fig. 2
INSTALLATION
The AFG Flow Grids are supplied in kit form, and tube lengths are cut to suit the required duct size by the customer.
page 2
Table 2: Included Parts
Description
Adapter & Pressure Tube Adapter Plate Duct Cap Cap Plate Adapter Drilling Template Duct Cap Drilling Template Diaphragm Elbow Tube Cap Grommet Cap Seal Adapter Seal Screws, Self Tapping No. 6 x 5/8˝
Decide on the best location for your AFG Flow Grid. The AFG Flow Grid is designed to fit into the shortest duct sides
of a rectangular duct or across a duct diameter. Mark out the duct to the dimensions shown in Fig. 4 and 5. Attach the self-adhesive templates supplied, and produce the holes to the sizes indicated on the templates. DEBURR the 1.26˝ (32 mm) diameter holes.
Quantity
2 2 2 2 2 2 2 2 2 2 2 2
16
The AFG Flow Grid is available in two tube diameters and lengths (See Table 1).
Table 1: Dimensions
Tube & Adapters
Tube Diameter “A”
5/16˝ (8 mm) 5/8˝ (16 mm)
Fig. 3
Supplied Length Size “B”
27˝ (688 mm)
59-4/5˝ (1518 mm)
Fig. 4
Fig. 5
Introduce tubes into the duct and secure at the adapter end using the clamping plate and No. 6 self-tapping screws supplied (See Fig. 6 and 7). Note position of tubes relative to the direction of flow (See Fig. 7).
They may be used in square, rectangular or round ducts. Unpack your AFG Flow Grid. The kit should contain the following
parts:
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
page 3
Fig. 6
Position and secure diaphragms and duct caps over protruding tubes using clamping washers and No. 6 x 5/8” screws, etc. (See Fig. 10 & 11).
Fig. 10
Fig. 7
Bias protruding ends of tubes towards the edge of the 1.26” (32 mm) diameter hole while cutting to length, and cut tubes 0.20” to
0.28˝ (5 to 7 mm) from the outside of the duct wall. DEBURR and REMOVE SHARP EDGES from the tube ends and slide tube caps over tubes (see Fig. 8 & 9). Fit the grommets as shown.
Fig. 8
Fig. 11
Push the elbows into the adapters. These may point in any direc­tion to suit tubing runs to differential pressure measuring instru­ments (See Fig. 12 & 13).
Fig. 12
Fig. 13
Fig. 9
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
page 4
Instrumentation and Completing the System:
The AFG Flow Grid is not a complete measuring system. To com­plete the system it is necessary to convert the output signal into a more useful form.
For occasional checking of the AFG Flow Grid, differential pressure portable instruments may be used.
A pressure transmitter may be used to give an electrical output proportional to the pressure signal or include a square rooting function to indicate velocity directly.
If the AFG Flow Grid is to be used as part of an alarm system, to warn for example, if the volume flow rate drops below a certain limit, a manometer fitted with alarm trips may be used.
To complete the installation, fit flexible tubing from the elbows at the ends of the AFG Flow Grid to the chosen instrument. The elbow connector is 6 mm outside diameter.
Interpretation of Output:
Duct mean velocity: The differential pressure signal obtained across the output tap­pings of the AFG Flow Grid is proportional to the duct mean veloc­ity pressure and to the square of the duct mean velocity.
The relationship between the differential pressure and the velocity pressure is the magnification factor M.
M= (ΔP)/(Pû) AFG Flow Grid: M=1.0
Table 3: Calculating Velocity from Differential Pressure
Fig. 14: Typical Performance Graphs
DUCT MEAN VELOCITY v ft/min
5/16˝
(6 mm) Tube
4000
2.0
1.5
1.0
0.5 FLOWGRID DIFFERENTIAL PRESSURE ΔP IN Wg.
0
20
FlowGRID DIFFERENTIAL PRESSURE Δ p Pa
500
400
300
200
100
5/8˝
(16 mm)
3000
15
1000
0
0
5
2000
10
DUCT MEAN VELOCITY m/s
Fig. 14 (above) shows AFG Flow Grid differential pressure against duct mean velocity.
This graph is drawn for standard air conditions of 1.2 kgs/m (0.075 lbs/ft3) and may be used if lower levels of accuracy (See page 1 & 3) are acceptable. If higher levels of accuracy are required on site calibration is essential (See next page).
3
Volume Flow Rate: The most useful information obtainable from an AFG Flow Grid is the volume flow rate in the duct in which it is fitted.
Table 4: Calculating Volumetric Flow from Differ ential Pressur e
Losses: Introducing an AFG Flow Grid into a duct causes a very small pres­sure loss, which should be known when calculating the energy requirements in a ducted system. The loss is measured as the pressure drop between tapping points situated D/2 upstream and downstream of the grid.
Fig. 15 shows magnification factor M and pressure loss factor L plotted against mean velocity for a typical AFG Flow Grid installa­tion. It will be seen that these values remain sensibly constant over the useful range of the AFG Flow Grid.
Fig. 15: Magnification and Pressure Loss Factors
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
page 5
Calibration on Site:
To achieve the best possible accuracy, the AFG Flow Grids must be calibrated on site and the following method of site calibration and subsequent calculation is advised.
Any valid method of determining the volume flow rate may be used in establishing the flow rate to differential pressure characteristic.
The following method and theory applies to the use of Pitot static tubes, as the primary means of determining volume flow rate by the velocity traverse technique.
To calibrate an AFG Flow Grid:
1. Install the AFG Flow Grid as described (See installation pages 2 & 3) and connect to a suitable manometer.
2. Prepare holes in the duct wall upstream of the AFG Flow Grid for the Pitot static tube traverse to give an adequate survey of the duct velocity pattern and mean duct velocity.
Table 6: Example: K Factor Calculation (Metric)
PITOT STATIC TUBE TRAVERSE DATA
Average
Average
Pitot Tube Traverse
Readings Pv Pa
& Pv
Reading
No.
1
250
Pv Pv
15.81 96
Pv
9.80
Pv Pv
48
Pv
6.93
DUCT AREA A = 250 X 500 mm = 0.125 m
2
230
15.17 92
9.59 46
6.78
3
260
16.12 99
9.95 47
6.86
4
240
15.49 96
9.80 51
7.14
5
212
14.56 90
9.49 45
6.71
of
Pv
15.43
9.73
6.88
2
of
Pv
238.08
94.67
47.33
Flow-
grid Diff
Δp
514.2
199.8
98.1
AVERAGE k1 = 0.1107
Mag­Factor
p = M
Δ
Pv
2.160
2.110
2.072
Flow Constant K1 = Ax1.291
CF
M
0.1095
0.1108
0.1118
3. Operate the system to give a typical flow rate through the Flow Grid and take records of Pitot static tube traverse readings and the Flow Grid differential pressure readings.
4. If possible, arrange the system flow rate to be changed to give additional sets of readings covering the range over which the sys­tem is intended to be used.
5. The theory of the AFG Flow Grid for normal atmosphere condi­tions is shown on page 4.
(Δp)/(Pv)= M (See page 4). Measure the ambient temperature ‘t’, the ambient barometric
pressure ‘B’ and the duct static pressure Ps. Calculate the cor­rection factor CF in the appropriate units.
Hence calculate the flow constant ‘K’ for each set of readings taken.
Table 5: Calculating Flow Constant K
SI Units
K1= A x 1.291 CF
M
Where =
Δp = X Flowgrid differential pressure M = X Flow grid magnification factor Pv = duct mean velocity pressure Pa A = cross section area of duct m
2
CF = correction factor Take the average K1and plot the curve of Q v Δp
Where
1
Δp
Q = K Q = volume flowrate m3/s
K1= A x 4005 CF
Δp = X Flowgrid differential pressure in. wg. M = X Flowgrid magnification factor Pv = duct mean velocity pressure wg A = cross section area of duct ft CF = correction factor
1
Q = K Q = volume flowrate ft
Δp
Imperial Units
M
3
/min
2
6. Suggested format for results using worked examples: Metric Units (example- using AFG Flow Grid in duct size 250 mm
x 500 mm)
Table 7: Graph Plotting Information Derived from Traverse Data (metric)
MX Flow Grid
Diff Δp Pa
Δp
Vol Flow
Rate
Q = K
ΔpM3/s
1
25
5
0.553
50
7.07
0.783
100
10
1.107
200
14.14
1.565
300
17.32
1.917
400
20.0
2.214
500
22.36
2.475
600
24.43
2.704
Imperial Units (example- using AFG Flow Grid in duct size 10” x 20”)
Table 8: Example: K Factor Calculation (Imperial)
PITOT STATIC TUBE TRAVERSE DATA
Average
Average
Flow-
Mag-
Pitot Tube Traverse
Readings Pv Pa
& Pv
Reading
No.
1
0.95
Pv
Pv
0.975
0.48
Pv
0.693
Pv Pv
0.23
Pv
0.480
DUCT AREA A = 10˝ X 20˝ = 1.388 ft
2
0.99
0.995
0.50
0.707
0.25
0.50
3
1.03
1.015
0.52
0.721
0.25
0.50
4
1.06
1.030
0.53
0.728
0.24
0.49
5
0.99
0.996
0.49
0.70
0.22
0.469
of
of
Pv
1.004
1.002
0.504
0.710
0.238
0.488
2
grid
Pv
Diff
Δp
2.169
1.063
0.493
AVERAGE k1 = 3824
Factor
p = M
Δ
Pv
2.160
2.110
2.072
Flow Constant K1 = Ax4005
CF
M
3781
3828
3863
Table 9: Graph Plotting Information Derived from Traverse Data (Imperial)
MX Flow Grid
Diff Δp Pa
Δp
Vol Flow
Rate
Q = K
Δpft3/min
1
0.5
0.707
2703
1.0
1.0
3824
1.5
1.225
4684
2.0
1.414
5408
2.5
1.581
6046
(see Fig. 17 for Graph)
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
page 6
Table 10: Uncertainty and Repeatability of Measurement
Expected uncertainty of measurement with typical system obstruc­tions:
Straight Upstream Length
Required to Maintain
Obstruction
Right Angle Bend Radius Angle Bend r=1D or less Opposed Blade Damper 30° Bend Tapered Contraction Sudden Contraction
Note: For rectangular ducts D= Width + Height of Duct/2 On any particular installation repeatability of signal output is likely
to be better than ±5%. When calibrated on site (See Previous Page) uncertainty of mea-
surement is likely to be better than ±5%.
±10%
10.0D
10.0D
10.0D
3.5D
3.5D
3.5D
±15%
3.5D
3.5D
3.5D
2.0D
2.0D
2.0D
Fig. 16
MAINTENANCE
No maintenance is normally required except where a high dust burden is likely to be encountered in the air stream. Deposits in the pressure holes will affect calibration and it is advisable to provide some means of access for cleaning when installing the AFG Flow Grid. The Series AFG Flow Grid is not field serviceable and should be returned if repair is needed (field repair should not be attempt­ed and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact cus­tomer service to receive a return goods authorization number before shipping.
Fig. 17
©Copyright 2005 Dwyer Instruments, Inc. Printed in U.S.A. 12/05 FR# R1-443394-00