Specifications - Installation and Operating Instructions
641 AVT WITH DISPLAY OPTION
A DIMENSION
7-63/64
[202.80]
13-63/64
[355.20]
19-63/64
[507.60]
26-63/64
[685.40]
32-63/64
[837.80]
37-63/64
[964.80]
641 AVT WITHOUT
A DIMENSION
7-7/16
[188.91]
13-7/16
[341.31]
19-7/16
[493.71]
26-7/16
[671.51]
29-7/16
[747.71]
37-7/16
[950.91]
The Series 641 Air Velocity Transmitter (AVT) uses a
heated mass flow sensor technology. It has 8 user selectable ranges from 250 FPM to 15000 FPM with corresponding metric ranges of 1.25 MPS to 75 MPS. The
Series 641 AVT provides an isolated 4-20 mA output proportional to the velocity. With the optional 1/2˝ 4-1/2 digit
LED display, the Series 641 AVT will provide a highly visible
local readout of the velocity.
SPECIFICATIONS
Service: Air and compatible, non-combustible gases.
Accuracy:
3% FS Process gas: 32 to 122° F (0 to 50°C).
4% FS Process gas: -40 to 32°F & 122 to 212°F
(-40 to 0°C & 50 to 100°C).
Response Time: Flow: 1.5 seconds to 95% of final value
(Output filter set to minimum).
Temperature Limits: Process: -40 to 212°F (-40 to
INSTALLATION
Location: Select a location where the temperature will be
within 32 to 140°F (0 to 60°C) to mount the enclosure. The
transmitter may be located any distance from the receiver
provided that the total loop resistance does not exceed 600
ohms. The probe should be located where conditions are
representative of the overall environment being monitored.
Avoid locations where turbulence, stagnation, or rapidly
fluctuating velocities or temperatures are present as these
conditions may affect the readings. The filter setting may be
used to average velocity readings in turbulent conditions.
Position: The transmitter is not position sensitive and may
be mounted in any orientation.
Mounting: An integral 1/2˝ NPT allows direct mounting to
pipe fittings or a pipe flange. The Series 641 AVT may also
be mounted using a 5/16˝ compression fitting. Arrows on
the hex flats at the base of the probe indicate the direction
of the calibrated airflow. Align these arrows in the direction
of the process air. The case may be rotated independently
of the probe for ease of connection.
Airflow: The Series 641 AVT is intended for use with clean
dry air. Particulates in the air may cause sensor damage.
Dust accumulation may impair the velocity measurement
and will require probe cleaning.
Output Filter: Selectable 0.5 –15 (seconds).
Loop Resistance: 600 ohms max.
Current Consumption: 300 mA max.
Electrical Connections: Screw Terminal.
Process Connections: 1/2˝ male NPT.
Mounting Orientation: Unit not position sensitive.
Probe must be aligned with airflow.
Weight: 12.6 oz. (357.2 g).
Agency Approvals: CE (See text for test standards).
NOTE: Where conduit connections are not made, a 1/2˝
NPT cable seal should be used to prevent contaminants
from entering the case. Where conduit connections are
made, make sure that any possible condensation within the
conduit will not flow into the transmitter housing.
ELECTRICAL CONNECTION
The Series 641 AVT has been designed for easy and flexible connection to power and loop receivers. Electrical connection is made inside the body of the device with a “Euro”
style terminal block. The device features a current loop that
is fully isolated from the power source. The current loop has
an internal 24V isolated supply so no external loop power is
required. With full isolation, loop grounding is not a concern.
The input power requirements are also very flexible. The
device may be powered from either an AC or DC power
source.
3 or 4-Wire Connection
POWER SUPPLY
AC OR DC
RECEIVER
4-WIRE
DC SUPPL
ONLY
(EITHER
POLARITY)
RECEIVER
3-WIRE
RECEIVER NEGATIVE
COMMON
DC SUPPLY
ONLY
(EITHER
POLARITY)
RECEIVER
3-WIRE
RECEIVER POSITIVE
COMMON
CAUTION: Do not exceed the specified supply voltage rating. Permanent damage not covered by the warranty may
result. Do not use an external power source on the current
loop connection.
Receiver-Transmitter Connection — The Series 641
AVT is designed as a three or four wire 4-20 ma device. The
current loop output is isolated from the power supply input
and provides an internal 24-volt loop supply. With a DC
power supply, a three or four-wire connection may be used.
Do not use a three-wire connection with an AC power
source. In a three-wire connection either power supply wire
may be used as the common. The total loop resistance
should not exceed 600 Ohms.
Wire Type and Length — The wire selection for an installation is often overlooked or neglected and may contribute
to improper or even intermittent operation. In all cases
ensure that the connection meets all applicable national
and local electrical codes. Although the 4-20 mA current
loop systems are relatively immune to wire or wiring related
problems, selection of the wire for some installations will be
an important factor in ensuring satisfactory system operation. Twisted conductors will usually be immune to most
stray electric and magnetic fields and to some extent electromagnetic fields, such as interference from RF transmitters. With twisted pair wiring the current loop and the
power connections should be separate pairs. Avoid using
flat or ribbon cable that has no regular conductor twist.
Where interference is possible, it is recommended that
shielded wire be used. The shield must not be used as one
of the conductors and should be connected to ground at
only one end, generally at the power supply. Similarly, if the
installation uses conduit, the conduit should be connected
to protective ground as specified by the applicable code
and the signal wiring must not be connected to the conduit
at more than one point or as specified by the code.
The maximum length of wire connecting the transmitter
and receiver is a function of the wire resistance and receiver resistance. The total loop resistance must not exceed
600 Ohms, including the receiver resistance and wire resistance. The power supply connection must be designed so
that the worst case voltage drop due to wire resistance will
not cause the power supply voltage at the transmitter to
drop below the specified value. Provided the power supply
voltage is maintained within the specified voltage range, the
Series 641 AVT is not affected by variations in power supply voltage.
TRANSMITTER SETUP
The Series 641 AVT has been designed for easy setup. It
has five configuration parameters that may be adjusted by
the user. These parameters are Output Filter, Range (In
English or Metric), span, 4 mA set-point and 20 mA setpoint. All of these may be adjusted at any time in the field.
These adjustments may also be easily returned to factory
default.
Interior Label Diagram
CAUTION: Do not use a receiver with an internal power
supply or use an external supply in the current loop. The
current loop is powered from within the Series 641 AVT.
Connecting an external supply to the current loop may
destroy the transmitter. Using an external supply voids the
warranty.
Power Supply Connection — The power supply may be
either AC or DC. The DC power may be from 12 to 35 Volts.
The power connection is not polarity sensitive so the positive and negative connections may be made to either power
terminal. The AC connection may be from 10 to 16 VAC
RMS. Do not exceed 20 VAC. When selecting a transformer
please note that the specified output for transformers is at
some specified current. With a load current less than the
specified current transformer output may be significantly
A set of controls and indicators are provided within the unit
consisting of the select button, enter button, adjustment
control, and six LED indicators. When operating normally,
only the RUN LED indicator will be illuminated. During the
setup operation the LED indicators will indicate the parameter selected, when it is being adjusted, and status of the
adjustment process. If the unit is left in the setup mode for
several minutes without any activity it will return to the
normal operating mode.
higher than the specified voltage. Transformers with secondary voltages of 10 to 16 VAC are recommended.
CAUTION: Do not use transformers with a secondary voltage rating greater than 16 VAC RMS.
Two buttons and a potentiometer control the setup process.
The SELECT button is used to scroll between the setup
parameters.
The ENTER button allows access to each parameter for
adjustment.
The ADJUST potentiometer is used to change the value of
the parameters.
Holding the ENTER button for 2.5 seconds saves the new
parameter value.
Making Adjustments
The adjustment process has three steps: select the parameter, adjust the parameter, save the new value. These are
described in the following steps.
1. Select the parameter: Each time the SELECT button is pressed the LED indicator will advance to the next
parameter. When the last parameter, SPAN, is selected,
the next time the SELECT is pressed the unit will return
to RUN mode. Press the SELECT button until the LED
indicator illuminates the desired parameter. Press
ENTER. The selected indicator will begin to blink, showing the parameter may now be adjusted. If the unit is left
in the setup mode, after several minutes it will reset to
the operate mode.
2. Adjust the parameter: Turn the ADJUST potentiometer until the desired setting is made. This may be
adjusted using a small screwdriver or similar tool. Be
careful not to force the control past its stops or damage
will result.
3. Save the Parameter: To save the new parameter
press and hold the ENTER button. The LED indicator will
begin to flash at a faster rate. After about 2.5 seconds
all of the LED indicators will flash when the parameter is
saved. If you do not want to save the parameter press
the SELECT button without entering the parameter. The
adjusted value will be discarded and next LED indicator
will be illuminated.
Range Selection
The range selection allows you to select one of eight ranges
in either feet per minute (FPM) or meters per second (MPS).
Select the RANGE indicator by pressing ENTER when the
RANGE LED indicator is illuminated. The A,B,C LED indicators will display which range setting is currently active.
Press ENTER to enable adjustment. Turn the ADJUST until
the desired range indication is achieved. If you want to discard the adjustment press SELECT. If you want to save the
range press and hold ENTER. The RANGE LED will blink at
a faster rate for about 2.5 seconds then all of the LEDs will
flash indicating the value was saved.
The range setting is displayed with the LED indicators. The
function of these indicators is summarized on the control
label inside the unit. The following table summarizes the
indicator status for each range setting
Range/Units
250 FPM
500 FPM
1000 FPM
2000 FPM
3000 FPM
5000 FPM
10000 FPM
15000 FPM
1.25 MPS
2.5 MPS
5 MPS
10 MPS
15 MPS
25 MPS
50 MPS
75 MPS
Run
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
Filter
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
Span
Range
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4 mA
A
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
B
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
20 mA
C
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Adjusting the Output Filter
The output filter may be adjusted to smooth the readings
1: Indicator on
0: Indicator off
when measuring turbulent flow. The time constant may be
adjusted from 0.5 seconds to 15 seconds. To adjust the filter time constant, select the FILTER indicator. Press ENTER
to enable adjustment. Turn the ADJUST until the desired
amount of damping is achieved. To save the value press and
hold the ENTER button until the LED indicators all flash, indicating the value was saved. To discard the adjustment press
SELECT before pressing the ENTER button.
The Series 641 AVT has been calibrated for standard sea
level conditions. As a mass flow device it will always read
the air velocity for standard conditions. Density changes due
to barometric or absolute pressure are not corrected automatically. The span setting allows correction for altitude or
other static pressure conditions that affect the density of the
process air. This parameter allows for a ±50% adjustment in
the span value.
To make the span adjustment you will need to know either
the absolute static pressure or the corrected velocity of the
process air. Set the air velocity to a known value, ideally
about 3/4 of the full-scale range value. Press SELECT until
the SPAN LED indicator is illuminated then press ENTER.
The SPAN LED will begin to blink. Adjust the control for the
desired velocity then press and hold the ENTER button until
all of the LED’s flash, indicating the new value was saved. If
you know the absolute static pressure you can compute the
corrected velocity using the following equation:
Po
Vcor =
Vrdg
PA
Where:
P0 is the standard pressure of 29.9 in. Hg. or 760 mm Hg.
PA is the absolute pressure reading
Vrdg is the indicated velocity
Vcor is the corrected velocity
Restoring Factory Default Settings
The 4 mA, 20 mA, and Range settings override factory
default values. To restore these to the factory default settings, start with the unit in the RUN mode. Press and hold
the ENTER button. The RUN LED indicator will begin to
blink. After about 2.5 seconds all LED indicators will flash
indicating the factory settings have been restored. Range
and Filter settings are not affected by this operation. If you
are unsure whether any have been altered, press the
SELECT button six times to sequence through all settings.
When you return to the RUN mode, the RUN LED indicator
will blink several times if either the 4 mA, 20 mA, or span
settings have been changed. The RUN LED will otherwise
remain on.
MAINTENANCE
In general the Series 641 AVT should require very little maintenance. In some installations dust may accumulate on the
sensor over time. This can be removed by carefully brushing the probe with a small camel hairbrush. If too much force
is applied during cleaning, the sensor of the Series 641 AVT
may be damaged. Therefore, a trained technician should
perform the cleaning operation. A jet of air may also dislodge the accumulated buildup however, again, the sensor
is delicate and this operation should be done carefully with
clean regulated air. Using a shop air supply may exert
enough force to damage the sensor. Most air supplies of
this sort will also contain water or oil that could damage the
sensor. Technical grade denatured or isopropyl alcohol may
be used where the dust accumulation does not respond to
brushing. Do not use water. Always disconnect the power
when performing a cleaning operation.
4 mA Setting
To make this setting you will need a milliammeter connected in the current loop. It is not required to use a known air
flow velocity to make this calibration setting. The calibration
settings of the velocity and the mA outputs are independent
of each other. Press SELECT until the 4 mA LED indicator is
illuminated then press ENTER. The milliammeter will now
read approximately 4.0 mA. Adjust the control for a 4.0 mA
reading on the milliammeter. Press and hold ENTER to save
the new setting. Pressing SELECT before pressing ENTER
will restore the previous calibration value.
20 mA Setting
It is not required to use a known air flow velocity to make
this calibration setting. The calibration settings of the velocity and the mA outputs are independent of each other. Press
SELECT until the 20-mA LED indicator is illuminated. Press
ENTER to begin adjustment of the 20-mA set point. The 20
mA LED will now be blinking. Adjust the control until the milliammeter reads 20.0 mA. Press and hold ENTER to save
the new setting. Pressing SELECT before pressing ENTER
will restore the previous calibration value.
Aside from field calibrations for span, 4 mA and 20 mA setting as described above, the Series 641 cannot be fully factory calibrated in the field. Because of specialized computer instrumentation required, these units must be returned to
Dwyer Instruments for factory calibration. Contact customer
service to receive a return goods authorization number
before shipping.
CE
The following standards were used for CE approval:
IEC 61000-4-2: 2001
IEC 61000-4-3: 2002
IEC 61000-4-4: 1995
IEC 61000-4-5: 2001
IEC 61000-4-6: 2003
IEC 55011: 1998
IEC 61326: 2002
89/336/EEC EMC Directive