Dwyer Instruments 629C User manual

Page 1
Series 629C Wet/Wet Differential Pressure Transmitter
L
®
Specications - Installation and Operating Instructions
5-15/16 [150.88]
1/4 NPT FEMALE FITTING
OPTIONAL 1/4 NPT MALE FITTING
7 [177.80]
Bulletin P-629C
43/64
[17.15]
1-11/32
[34.29]
3-7/64 [78.83]
1-31/32
1-27/64
[35.98]
[50.16]
OPTIONA
LCD
The SERIES 629C Wet/Wet Differential Pressure Transmitter monitors differential pressure of compatible gases and liquids with 0.5% accuracy. The design employs dual pressure sensors converting pressure changes into a 4 to 20 mA or voltage output signal. Small internal volume and minimal moving parts result in exceptional response and reliability. The wiring terminals and zero adjustment button are easily accessed under the removable cover. The Series 629C is designed to meet NEMA 4X (IP66) weatherproof construction.
RANGE Range Number Range Working Pressure* Over Pressure
01 02 03 04 05 06 07 08 09 11 12 13 14 15 16 17 18 19
*Pressures exceeding the working pressure limit may cause a calibration shift
of up to ±3% of full scale. Note: Over pressure of all models with 3-way valve is 100 psi.
0 to 5 psid 0 to 10 psid 0 to 25 psid 0 to 50 psid 0 to 100 psid 0 to 150 psid 0 to 200 psid 0 to 300 psid 0 to 500 psid 0 to 0.5 bar differential 0 to 1 bar differential 0 to 2 bar differential 0 to 4 bar differential 0 to 6 bar differential 0 to 10 bar differential 0 to 15 bar differential 0 to 20 bar differential 0 to 30 bar differential
Table 1: Pressure Limits
10 psi 20 psi 50 psi 100 psi 200 psi 300 psi 400 psi 600 psi 1000 psi 1 bar 2 bar 4 bar 8 bar 12 bar 20 bar 30 bar 40 bar 60 bar
50 psi 50 psi 120 psi 250 psi 500 psi 750 psi 1000 psi 1200 psi 2000 psi 3 bar 8 bar 8 bar 18 bar 18 bar 50 bar 60 bar 80 bar 120 bar
SPECIFICATIONS
Service: Compatible gases and liquids.
Wetted Materials: Without valve: 316, 316L SS. Additional wetted parts with valve option: Buna-N, silicone grease, PTFE, brass 360, copper, and reinforced copolymer. Accuracy: ±0.5% FS (includes linearity, hysteresis & repeatability). Stability: ±1% FS/year. Temperature Limits: 0 to 200°F (-18 to 93°C). Compensated Temperature Limits: 0 to 175°F (-18 to 79°C).
Pressure Limits: See Table 1. Thermal Effects: Avg 0.04%/°F
(0.072%/°C) (includes zero and span). Power Requirements: 2-wire: 10 to 35 VDC; 3-wire: 13 to 35 VDC or isolated 16 to 33 VAC (reverse polarity protected). Output Signal: 2-wire: 4 to 20 mA; 3-wire: Field selectable 0 to 5, 1 to 5, 0 to 10, or 2 to 10 VDC.
Zero and Units: Push buttons inside conduit enclosure.
Response Time: 400 msec. Loop Resistance: Current output: 0
to 1250 Ω (max), Rmax = 50(Vps-10);
Voltage output: Minimum load resistance
= 5 kΩ.
Current Consumption: 28 mA (max). Electrical Connections: Removable
terminal block; 1/2˝ female NPT conduit. Process Connections: 1/4˝ female or
male NPT.
Display: Optional 4-1/2 digit LCD eld
attachable display. Enclosure Rating: Designed to meet NEMA 4X (IP66) for non-LCD models. Mounting Orientation: Not position sensitive.
Weight: 10.1 oz (286 g). Agency Approvals: CE.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
Page 2
MODEL CHART Example 629C -01 -CH -P1 -E1 -S1 -3V 629C-01-CH-P1-E1-S1-3V
Series 629C Wet/wet differential pressure transmitter
Range 01
Housing CH Conduit housing, NEMA 4X (IP66) Process Connection
Electrical
Connection
Signal Output S1
Options 3V
*Pressures exceeding the working pressure limit may cause a calibration shift of up to ±3% of full scale.
02 03 04 05 06 07 08 09 11 12 13 14 15 16 17 18 19
P1 P2
E1 E2 E3 E5 E6
S3
AT FC LCD NIST
PRESET
0 to 5 psid 0 to 10 psid 0 to 25 psid 0 to 50 psid 0 to 100 psid 0 to 150 psid 0 to 200 psid 0 to 300 psid 0 to 500 psid 0 to 0.5 bar differential 0 to 1 bar differential 0 to 2 bar differential 0 to 4 bar differential 0 to 6 bar differential 0 to 10 bar differential 0 to 15 bar differential 0 to 20 bar differential 0 to 30 bar differential
1/4˝ male NPT 1/4˝ female NPT
Cable gland with 3´ of prewired cable Cable gland with 6´ of prewired cable Cable gland with 9´ of prewired cable
1/2˝ female NPT conduit
M-12 4 pin connector 4-20 mA Field selectable 0-5, 1-5, 0-10, 2-10 VDC 3-way valve Aluminum tag
Factory calibration certicate
LCD indication
NIST traceable certicate
Preset transmitter
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 3
INSTALLATION
7-17/64 [184.66]
[142.11]
[108.33]
3 [76.19]
1
VIN
+
CONNECTION
UNIT BUTTON-PRESS TO TOGGLE THE
ZERO BUTTON- PRESS AND
TRANSMITTER CONNECTION INSTRUCTION:
- TURN OFF POWER SUPP
- CONNECT THE POWER SUPPL [TERM #2] OF THE GAGE AS SHOWN
- INST
- TURN ON POWER
CAUTION: BE SURE TO TURN OFF POWER WHEN CONNECTING OR REMOVING THE LCD CONNECTOR. FAILURE TO DO SO CAN RESULT IN GAGE DAMAGE.
BLEED FITTING
BLEED FITTING
1. Location: Select a location where the temperature of the unit will be between 0 and 200°F (-18 to 93°C). Distance from the receiver is limited only by total loop resistance (see electrical connections). The tubing feeding pressure to the instrument can be practically any length required, but long lengths will increase the response time slightly. Mount the instrument in a location that will not be subject to excessive
temperature, shock, or vibration.
2. Position: A vertical position is recommended (pressure connections pointing horizontally) since that is how all standard models are spanned and zeroed at the
factory. They can be used at other angles, but may require nal zeroing. Due to
potential condensation buildup that may travel down conduit or cable and into the housing, it is recommended to install with the electrical conduit or cable gland pointing downward.
3. Pressure Connection: Dual 1/4“ NPT pressure connections are provided. Use pipe thread sealant tape or other suitable pipe joint compound when making connection to the pressure source. Avoid excess sealant which could block the pressure passage.
When monitoring liquid pressures, air trapped in the lines can cause incorrect readings.
Bleed ttings or similar mechanisms should be used to bleed off any trapped air.
Optional 3-Way Valve
For applications where higher line pressures may be encountered at installation or when it is necessary to remove the transmitter for maintenance without interrupting the process, the optional three way valve is recommended. (See Figure 1)
ELECTRICAL CONNECTIONS
Shielded cable is recommended for control loop wiring. Electrical connections to the
Series 629C pressure transmitters are made to the terminal block located inside the housing. Remove the screws and lift off the cover. Wire as shown in Figure 3 or 4. Use Figure 3 for current output connection. Use Figure 4 for current output with optional LCD display. If ordering pre-wired cable, black wire is negative (-) and red wire is
positive (+).
PRESSURE
TRANSMITTER
LOW [-]
PRESSURE
CONNECTION
COM
2 3 4
SHIELD
Figure 3: Current Output Connection
UNIT [PSID/BARD] ON THE LCD
+-
RECEIVER
HOLD TO ZERO THE GAGE
-
HI [+] PRESSURE
POWER SUPPLY
10-35 VDC
2-13/32
[60.96]
1-37/64
[40.14]
5-19/32
LOW SIDE
3-63/64
[101.02]
4-17/64
2-25/64
[60.84]
Figure 1: 629C with Optional 3-Way Valve
Installation with 3-way valve option. Begin with valve V1 open and valves V2 and V3 closed. (See Figure 2) Slowly open valves V2 and V3. Once the pressure has stabilized and is equal on the high and low side of the transmitter, valve V1 can be closed and normal operation can proceed.
HIGH SIDE
POWER SUPPLY
10-35 VDC
+
-
ALL THE LCD'S CONNECTOR TO THE GAGE AS SHOWN.
Wire Length – The maximum length of wire connecting transmitter and receiver is a function of wire size and receiver resistance. Wiring should not contribute to more than 10% of receiver resistance to total loop resistance. For extremely long runs (over 1000 ft or 305 m), choose receivers with higher resistance to minimize size and cost of connecting leads. When wiring length is under 100 ft (30.5 m), lead wire as small as 22 AWG can be used.
Current (4 to 20 mA) Output Operation – An external power supply delivering 10 to 35 VDC with minimum current capability of 40 mA DC (per transmitter) is required to power the control loop. See Figure 3 for connection of the power supply, transmitter,
and receiver. The range of the appropriate receiver load resistance (RL) for the DC
power supply voltage available is expressed by the formula
Vin [TERM #1]
Com [TERM #2]
+
-
RECEIVER
SHIELD [TERM #4]
RED
BLACK
BLUE
.
Figure 4: Current Output with Optional LCD
ORANGE
YELLOW
WHITE
LY.
Y AND RECEIEVER TO Vin [TERM #1] AND Com
.
LCD CONNECTOR
Figure 2: Bleed Fitting Connections
To ensure proper pressures will be detected by the 629C, use the bleed ttings provided with this package to free media of bubbles. Before applying pressure to the process connections, turn V1 to the open position and back off either the low or high side bleed hex nut. Next, apply pressure. After the owing liquid is free of bubbles,
retighten the bleed hex nut.
Before removing the transmitter from operation, open valve V1, then close valves V2 and V3.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
RL max =
vps - 10
20 mA DC
Page 4
VOLTAGE (0 TO 5, 1 TO 5, 0 TO 10, OR 2 TO 10 V) OUTPUT OPERATION
1
VIN
+
TRANSMITTER CONNECTION INSTRUCTION:
- TURN OFF POWER SUPPL
- CONNECT THE POWER SUPPL THE GAGE AS SHOWN.
- CONNECT THE RECEIVER [+] TO POWER SUPPL
- INST
- SET VOL
- TURN ON POWER.
CAUTION: BE SURE TO TURN OFF POWER WHEN CONNECTING OR REMOVING THE LCD CONNECTOR. FAILURE TO DO SO CAN RESULT IN GAGE DAMAGE.
CONNECTION
UNIT BUTTON-PRESS TO TOGGLE THE
ZERO BUTTON-PRESS AND
OR ISOLA
To select the voltage output that is going to be used, congure the dip switches
according to the Figure 5 below.
0 to 5 VDC
1 2
1 to 5 VDC
1 2
LOW [-]
PRESSURE
CONNECTION
UNIT [PSID/BARD] ON THE LCD
HOLD TO ZERO THE GAG
HI [+] PRESSURE
ON
OFF
0 to 10 VDC 2 to 10 VDC
1 2
ON
OFF
Figure 5: Voltage Output Dip Switch Selection
For voltage outputs, wire as shown in Figure 6 for voltage output connection. Use
Figure 7 for voltage output with optional LCD display. Terminal 1 is positive (+), terminal 2 is negative (-), and terminal 3 is +Vout. If ordering optional prewired cable,
black wire is negative (-), red wire is positive (+), and white wire is +Vout. For optimal
accuracy, use a separate common wire for the receiver.
COM
PRESSURE
TRANSMITTER
2
VO
3 4
SHIELD
Figure 6: Voltage Output Connection
+-
RECEIVER
ON
OFF
ON
OFF
1 2
-
OR 16-33 VAC
POWER SUPPLY
13-35 VDC
+
-
POWER SUPPLY
13-35 VDC
TED
16-33 VAC
ALL THE LCD'S CONNECTOR TO THE GAGE AS SHOWN.
TAGE SELECTION DIP SWITCH TO DESIRED VOLTAGE OUTPUT.
MAINTENANCE/REPAIR
Upon nal installation of the Series 629C Wet/Wet Differential Pressure Transmitter, no routine maintenance is required. The Series 629C is not eld serviceable and is not
possible to repair the unit. Field repair should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Material Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus
any additional application notes.
Vin [TERM #1]
Com [TERM #2]
Vo [TERM #3]
+
­RECEIVER
SHILED [TERM #4]
RED
BLACK
BLUE
Y [-].
Figure 7: Voltage Output with Optional LCD Display
ORANGE
YELLOW WHITE
Y.
Y [+] TO Vin [TERM #1] AND [-] TO Com [TERM #2] OF
Vo [TERM #3] OF THE GAGE AND RECEIVER [-] TO
LCD CONNECTOR
VOLTAGE SELECTION DIP SWITCH
©Copyright 2016 Dwyer Instruments, Inc. Printed in U.S.A. 3/16 FR# 443277-10