Dwyer Instruments 628-07-GH-P1-E4-S1 User manual

Page 1
Series 626 & 628 Pressure Transmitters
®
Specications - Installation and Operating Instructions
Bulletin E-111-A
-GH General Purpose Housing
The Series 626 & 628 Pressure Transmitters converts a single positive pressure into a standard 4-20 mA output signal. The Series 626 and 628 can be used to accurately measure compatible gases and liquids; Series 626 full-scale accuracy is 0.25%;
Series 628 full-scale accuracy is 1.0% (see specications). Designed for industrial environments with a NEMA 4X (IP66) housing, this transmitter resists most effects of
shock and vibration.
CAUTION
designed for 120 or 240 VAC operation. Use only on 13-30 VDC.
PRESSURE LIMITS Range *Maximum Pressure Over Pressure
0 to 5 psi 0 to 15 psi 0 to 30 psi 0 to 50 psi 0 to 100 psi 0 to 150 psi 0 to 200 psi 0 to 300 psi 0 to 500 psi 0 to 600 psi 0 to 1000 psi 0 to 1500 psi 0 to 3000 psi *Pressures exceeding the maximum pressure limit may cause a calibration shift of up to ±3% of full scale.
Do not exceed specied supply voltage ratings. Permanent
damage not covered by warranty will result. This device is not
10 psi 30 psi 60 psi 100 psi 200 psi 300 psi 400 psi 600 psi 1000 psi 1200 psi 2000 psi 3000 psi 6000 psi
50 psi 150 psi 300 psi 300 psi 500 psi 750 psi 1000 psi 1500 psi 2500 psi 3000 psi 5000 psi 5000 psi 7500 psi
1/4 NPT
7/8 [22.23]
HEX
SPECIFICATIONS Service: Compatible gases and liquids. Wetted Materials: Type 316L SS. Accuracy: 626: 0.25% FS, 0.20% RSS;
628: 1.0% FS, 0.5% RSS; 626 absolute ranges: 0.5% FS, 0.35% RSS (includes linearity, hysteresis, and repeatability).
Temperature Limit: 0 to 200°F (-18 to
93°C).
Compensation Temperature Range: 0
to 175° (-18 to 79°C).
Thermal Effect: 626: ±0.02% FS/°F. 628: ±0.04% FS/°F (includes zero and
span).
Pressure Limits: See table. Power Requirements: 10-30 VDC (for
4-20 mA, 0-5, 1-5, 1-6 VDC outputs); 13-30 VDC (for 0-10, 2-10 VDC outputs); 5 VDC ±0.5 VDC (for 0.5-4.5 VDC ratio­metric output). Output Signal: 4-20 mA, 0-5 VDC,1-5 VDC, 0-10 VDC, or 0.5-4.5 VDC.
055/64 [21.83]
2-27/64 [61.52]
3-13/64 [81.36]
Loop Resistance: 0-1000 Ω max. R max = 50 (Vps-10) Ω (4-20 mA output), 5 KΩ min (0-5, 1-5, 0.5-4.5 VDC output), 15 KΩ min (1-6, 0-10, 2-10 VDC output).
Current Consumption: 38 mA
maximum (for 4-20 mA output); 10 mA maximum (for 0-5, 1-5, 1-6, 0-10, 2-10,
0.5-4.5 VDC output); 140 mA maxumum
(for all 626/628/629-CH with optional
LED).
Electrical Connections: Model
dependent options: Wire end, Hirschman DIN EN 175801-803-C, Packard, Deutsch, M12.
Process Connection: Model dependent
options: 1/8˝, 1/4˝, 1/2˝ male NPT; 1/4˝ female NPT; 1/4˝ male or female BSPT; 1/8˝ or 1/4˝ male BSPP ISO 1179; 1/4˝
female SAE valve depressor.
Enclosure Rating: NEMA 4X (IP66). Mounting Orientation: Mount in any
position.
Weight: 10 oz (283 g). Compliance: Standard: CE; Optional:
NSF/ANSI 61/372, ANSI/UL 218, ANSI/ UL 508, NEPA 20.
INSTALLATION
1. Location: Select a location where the temperature of the transmitter will be
between 0 and 175°F (-18 to 79°C). Distance from the receiver is limited only by
total loop resistance. The tubing or piping supplying pressure to the unit can be practically any length required but long lengths will increase response time slightly.
2. Position: The transmitter is not position sensitive. However all standard models are originally calibrated with the unit in a position with the pressure connection
downward. Although they can be used at other angles, for best accuracy it is
recommended that units be installed in the position calibrated at the factory. Position affects will be more noticeable on ranges below 30 psi.
3. Pressure Connection: Use a small amount of plumber’s tape or other suitable sealants to prevent leaks. Be sure the pressure passage inside the port is not blocked.
4. Electrical Connections Wire Length - The maximum length of wire connecting the transmitter and receiver
is a function of wire size and receiver resistance. Wiring should not contribute more than 10% of the receiver resistance to total loop resistance. For extremely long
runs (over 1000 feet), choose receivers with higher resistance to minimize the size and cost of connecting leads. Where wiring length is under 100 feet, wire as small
as 22 AWG can be used.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
CURRENT (4-20 mA) OUTPUT OPERATION
An external power supply delivering 10-30 VDC with minimum current capability of 40 mA DC (per transmitter) is required to power the control loop. See Figure A for connection of the power supply, transmitter and receiver. The range of appropriate receiver load resistance (RL) for the DC power supply voltage available is expressed
by the formula:
1 RED
PRESSURE
TRANSMITTER
If ordering optional pre-wired cable, black wire is negative [-] and red wire is positive [+].
2 BLACK
3 [NC]
RL Max = Vps – 10
20 mA DC
RECEIVER
mA
4 SILVER
SHIELD WIRE [NOT CASE GROUNDED]
Figure A: Current output connection
POWER SUPPLY
13-30 VDC
Page 2
Hirschman DIN Connector with 4-20 mA When using cable version of -GH General
TERMINAL 4: [-]
+]
3-5/16 [84.14]
1/4 NPT
Ø55/64
[NOT CASE GROUNDED]
TERMINAL
TERMINAL 4: [-]
3:
[VOUT]
[NOT CASE GROUNDED]
TERMINAL
TERMINAL 4: [-]
3:
[VOUT]
V- [COMMON]
V+
Purpose Housing, black wire is negative [-] and red wire is positive [+]. When using optional Hirschman DIN Plug, remove top-center screw and lift off the terminal
block assembly. Wire to terminals shown below in Figure B. For optional 4-pin M-12
connector, wire to pins as shown in Figure C.
A
TERMINAL 3: [GROUND]
B; [+]
C; [VOUT
A
TERMINAL 1: [+]
SECTION A-A
TERMINAL 1: [+]
TERMINAL 2: [-]
Figure B Figure C
[21.83]
2-27/64 [61.52]
Figure D: Packard Connection
A; [-]
7/8
[22.23]
HEX
C; [GND]
A; [-]
B; [+]
RATIOMETRIC (0.5-4.5 VDC) OUTPUT OPERATION
(Other outputs contact the factory) See Figure K for connection of the power supply,
transmitter and receiver.
1 RED
POWER
PRESSURE
TRANSMITTER
General Purpose Housing with Ratiometric Output When using cable version of
-GH General Purpose Housing, black wire is negative [-], red wire is positive [+] and white wire is output. When using optional Hirschman DIN Plug, remove top-center
screw and lift off the terminal block assembly. Wire to terminals shown below in Figure
H. For optional 4-pin M-12 connector, wire to pins as shown in Figure I. If utilizing optional A-164 cable for M-12 connection, brown wire corresponds to pin #1, white #2, blue #3, and black #4.
2 BLACK [COMMON]
3 WHITE [+V OUT]
V IN
RECEIVER
Figure K: Voltage output connection
4 SILVER
SHIELD WIRE
SUPPLY
5 VDC ±10%
A
1: [+]
SECTION A-A
TERMINAL 1: [+]
A
TERMINAL 2: [-]
TERMINAL 3: [OUTPUT]
TERMINAL [GROUND]
TERMINAL 2:
VOLTAGE (0-5, 1-5, 0-10, 1-6 or 2-10 VDC) OUTPUT OPERATION
(Other outputs contact the factory) See Figure E for connection of the power supply,
transmitter and receiver.
1 RED
PRESSURE
TRANSMITTER
Hirschman DIN Connector with Voltage Output When using cable version of
-GH General Purpose Housing, black wire is negative [-], red wire is positive [+] and
white wire is output. When using optional Hirschman DIN Plug, remove top-center
screw and lift off the terminal block assembly. Wire to terminals shown below in Figure
F. For optional 4-pin M-12 connector, wire to pins as shown in Figure G. If utilizing optional A-164 cable for M-12 connection, brown wire corresponds to pin #1, white #2, blue #3, and black #4.
2 BLACK [COMMON] POWER
3 WHITE [+V OUT]
4 SILVER
RECEIVER
Figure E: Voltage output connection
V IN
SHIELD WIRE
SUPPLY
A
1: [+]
SECTION A-A
TERMINAL 1: [+]
A
TERMINAL 2: [-]
TERMINAL 3: [OUTPUT]
TERMINAL [GROUND]
TERMINAL 2:
Figure H Figure I
Deutsche Connector with Voltage Output, Ratiometric and 4-20 mA
When using this cable version see Figure J for voltage output and ratiometric terminal connections. See Figure P for 4-20 mA terminal connections.
V OUT
Figure J: Deutsche connection, voltage output
V- [COMMON]
3-7/32 [81.74]
Figure P: Deutsche connection, 4-20 mA output
MAINTENANCE
After nal installation of the pressure transmitter and its companion receiver, no routine
maintenance is required. A periodic check of system calibration is suggested. The
sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
CE APPROVAL Note: Accuracy is increased to ±3.6% when a 10 V/m between 80-1000 mhz RF
eld is applied.
Vent lter
V+
Figure F Figure G
Find Quality Products Online at: sales@GlobalTestSupply.com
Printed in U.S.A. 8/22 FR# 174757-05 Rev. 2©Copyright 2022 Dwyer Instruments, Inc.