TEST EQUIPMENT
BARBED FOR 1/8 OR
3/16 I.D. TUBING
1-1/16
[26.98]
5/8 [15.88]
5-7/8
[149.23]
2-13/16
[71.44]
29/32
[23.02]
Series
477
Handheld Digital Manometer
Selectable Pressure Units, ±0.5% Accuracy, FM Approved Intrinsically
Safe for Hazardous Locations, Class 1, Div. 1, Group A, B, C, D, T4
Portable
Manometers,
Series 477 Handheld Digital Manometers are packed
pressure measurement and recording faster, easier and more accurate than ever. First, you
can instantly select from up to nine of the most widely used pressure units without having
to waste time and risk mistakes with tedious conversions. Next, a non-volatile memory
function enables storage of up to 40 readings — perfect for HVAC technicians making Pitot
tube traverses of airflow readings across a duct.
safe for hazardous locations, Class 1, Div. 1, Group A, B, C, D, T4.
When working in poorly lighted areas, just switch on the handy backlight feature . It
automatically shuts itself off after 20 minutes to minimize battery drain. Electronic zeroing
means you simply touch a single key to perfectly null out any minor pressure differences.
A display HOLD key freezes the current pressure for those all-too-comm on situations
where readings fluctuate. We even included an audible alarm to warn you of overpressure
plus a visual alarm warning in case ambient noise levels are too high to hear the alarm.
Audible alarm also conf irms a value has been stored, eliminating the need to observe
display during a duct traverse.
FEATURES
• New low pressure ranges
• USB option comes with cable and software for easy data downloading
• Instant selection from up to nine english/metric units
• Stores 40 readings in memory for later reference
• Measure positive, negative or differential pressures
• Large easy-to-read 0.4˝ LCD display includes switchable backlight for
great visibility — anywhere
• Both audible and visual overpressure alarms
• Includes + and - indicators plus low battery warning
• Operates up to 100 Hours on a single 9 V battery
See page 567 for process tubing options.
with features you need to make
The FM approved models are intrinsically
SPECIFICATIONS
Service: Air and compatible gases. FM
models air and compatible combustible
gases.
Wetted Materials: Consult factory.
Accuracy: ±0.5% FS, 60 to 78°F (15.6
to 25.6°C); ±1.5% FS from 32 to 60°F
and 78 to 104°F (0 to 15.6°C and 25.6
to 40°C).
Pressure Hysteresis: ±0.1% of fullscale.
Pressure Limits: See chart.
Temperature Limits: 0 to 140°F (-17.8
to 60°C).
Compensated Temperature Limits:
32 to 104°F (0 to 40°C).
ACCESSORIES
A-402A CARRYING CASE — Tough gray nylon pouch protects any
Series 477 Manometer. Double zippered for quick and easy access.
With belt loop that snaps closed.
7-1/2˝H x 3˝W x 2-1/4˝D (191 x 76 x 57 mm)
UHH-C1, Soft carrying case
OPTION
For NIST traceable calibration certificate, add suffix -NIST to model numbers.
Example: 477-1-FM-NIST.
Storage Temperature Limits: -4 to
176°F (-20 to 80°C).
Display: 0.42˝ (10.6 mm) 4 digit LCD.
Response Time: 1 s.
Resolution: See chart.
Power Requirements: 9 V alkaline
battery, installed non-functional, user
replaceable.
Weight: 10.2 oz (289 g).
Connections: Two barbed connections
for use with 1/8˝ (3.18 mm) or 3/16˝
(4.76 mm) ID tubing. Two compression
fittings for use with 1/8˝ (3.18 mm) ID x
1/4˝ (6.35 mm) OD tubing for 477-7-FM
& 477-8-FM only.
Agency Approvals: CE, FM.
Model*
477-000-FM
477-00-FM
477-0-FM
477-1-FM
477-2-FM
477-3-FM
477-4-FM
477-5-FM
477-6-FM
477-7-FM
477-8-FM
422
Range
0-1.000 in w.c.
0-4.000 in w.c.
0-10.00 in w.c.
0-20.00 in w.c.
0-40.00 in w.c.
0-200.0 in w.c.
0-10.00 psi
0-20.00 psi
0-30.00 psi
0-100.0 psi
0-150.0 psi
bar
.0498
.0996
.4982
.6895
1.379
2.069
6.895
10.34
psi
.1445
.3613
.7225
1.445
7.225
10.00
20.00
30.00
100.0
150.0
in Hg
.0736
.2942
.7355
1.471
2.942
14.71
20.36
40.72
61.08
203.6
305.4
Available Pressure Units
kPa
in w.c.
.2491
1.000
0.996
4.000
2.491
10.00
4.982
20.00
9.96
40.00
49.82
200.0
68.95
276.8
137.9
553.6
206.9
830.4
689.5
2768
1034
4152
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
mm Hg
1.868
7.473
18.68
37.36
74.73
373.6
517.1
1034
1551
5171
7757
mbar
2.491
9.96
24.91
49.82
99.6
498.2
689.5
1379
2069
6895
mm w.c.
25.40
101.6
254.0
508.0
1016
5080
7031
Pa
249.1
996
2491
4982
9964
Maximum
Pressure
5 psig
5 psig
5 psig
10 psig
10 psig
30 psig
30 psig
60 psig
60 psig
150 psig
200 psig