Series Series WD3 Water Leak Detector
Specications - Installation and Operating Instructions
1-3/16
[30.12]
1-5/16
[33.15]
5/8
4-1/8
[105.23]
[16.58]
Bulletin L-WD3
[91.70]
3
[76.68]
5/16
[7.52]
WD3-BP WD3-LP Bracket
The Series WD3 Water Leak Detector protects equipment from water damage by
detecting the presence of water in drip pans in air handler units, under raised oors
in data centers, or on oors around sump pumps and drains. Water is detected once
it reaches a level that bridges the two conductive strips on the bottom of the housing.
Depending on the model ordered, audible and visual alerts provide local indication
of the alarm condition and an internal switch will give remote indication or control to
prevent further build up of water.
For applications where power is not available, the Model WD3-BP-D1-A is battery
powered. Otherwise, either AC or DC supply voltages can be used to power the water
detector. The sensing height can be adjusted to as low as 1/32˝ using the included
adjustable mounting bracket. The mounting bracket can attach to any at surface by
either using the attached adhesive strips or mounting screws.
INSTALLATION
Mounting
The Series WD3 mounts horizontally using an adjustable mounting bracket that allows
detection from 1/32˝ up to 17/32˝. The tabs on the side of the water detector t into the
slots on the bracket as shown in Figure 1. The mounting bracket mounts to the drip
pan or at surface by either the attached adhesive strips or using two #6 or #8 screws.
2
SPECIFICATIONS
Service: Water or conductive uids.
Minimum Sensing Gap: 1/32˝.
Switch Type: Battery powered models: SPST NO SSR; External powered models:
DPDT relay.
Electrical Ratings: Battery powered model: Pilot duty rating 250 mA @ 24 VDC;
External powered models: 1A @ 24 VAC/DC.
Audible Alarm: At least 85 dB @ 1 foot distance (depends on model).
Visual Alarm: Red LED for water level; Yellow LED for low battery (battery powered
models only); Green LED for power condition (external powered models only).
Temperature Limits: 32 to 122°F (0 to 50°C).
Power Requirements: Battery Powered Model: 3V CR2450 lithium metal battery,
installed functional, user replaceable; External Powered Models: 24 VAC ±10%,
11-27 VDC.
Power Consumption: Battery powered model: 0.9 mA steady state / 3.0 mA during
alarm condition; External powered models: 30 mA steady state / 85 mA during
alarm condition.
Battery Life: 5 years steady state / 48 hours during alarm condition.
Electrical Connections: 4.9 ft (1.5 m), 22 AWG, PVC, UL plenum rated cable (10 ft
(3 m) cable on WD3-LP-D2-10 model).
Enclosure Material: ABS and polycarbonate with ammability classication UL 94
V-0.
Enclosure Rating: Audible alarm models: Water-tight up to 3/4 of the body height;
Non-audible alarm models: NEMA 6P (IP 68) submersible.
Weight: 4.85 oz (137.5 g).
Agency Approvals: CE.
1/8
[2.50]
5/8
[16.18]
BracketWD3
Figure 1: Mounting WD3 to Mounting Bracket
NOTICE
adhesive is very strong and is not easily removed once attached.
Before attaching the mounting bracket to the desired surface, the
Series WD3 will need to be attached to the mounting bracket. The
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com

Replacing Batteries (Battery Powered Model Only)
When the battery is low, a yellow warning LED will begin to ash and an audible alarm
will sound every 300 seconds to alert that it is time to change the battery. Using a large
at head screw driver, turn the battery cover 1/4 turn in the direction of the arrows on
the cover. Remove the battery cover by lifting it up. Remove the coin cell battery from
its compartment. Insert a new 3V CR2450 coin cell battery in the compartment with
the positive (+) side of the battery facing up. Replace the battery cover and twist the
cover using the large at head screw driver in the opposite direction of the arrows on
the cover.
MODEL CHART
Model Output Power
WD3-BP-D1-A
WD3-LP-D2
WD3-LP-D2-A
WD3-LP-D2-10
Wiring
The wires in the 4.9 ft (1.5 m) or 10 ft (3 m) model dependent cable for the Series WD3
are color coded to reduce wiring errors. For battery powered models, Figure 2 has the
wiring diagram. For external powered models, Figure 3 has the wiring diagram.
SPST NO SSR
DPDT Relay
DPDT Relay
DPDT Relay
Battery
24 VAC ±10%, 11-27 VDC
24 VAC ±10%, 11-27 VDC
24 VAC ±10%, 11-27 VDC
Audible
Alarm
Yes
No
Yes
No
Cable
Length
4.9 ft (1.5 m)
4.9 ft (1.5 m)
4.9 ft (1.5 m)
10 ft (3 m)
YELLOW
GREEN
Operation
After mounting and wiring the Series WD3, it is ready for operation. The water is
detected when it bridges the two conducting strips on the bottom of the unit. Upon
detecting water, the relay contact will close and a red LED will begin to ash. On
models with the built in annunciator, the annunciator will begin to chirp until the water
bridge between the conducting strips evaporates. After water evaporates, the relay
contacts will return to their normal state.
LED Indicators
For Models WD3-LP-D2, WD3-LP-D2-A and WD3-LP-D2-10
Green – On when power is supplied to the unit
Red – On when water is detected
For Model WD3-BP-D1-A
Yellow – On when low battery condition is detected
Red – On when water is detected
MAINTENANCE/REPAIR
Upon nal installation of the Series WD3 no routine maintenance is required. The
Series WD3 is not eld serviceable with the exception of replacing the batteries on
battery powered model and should be returned if repair is needed. Field repair should
not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping the
product back for repair. Be sure to include a brief description of the problem plus any
additional application notes.
YELLOW
WHITE
GREEN
BLUE
BROWN
PWR IN
Figure 3: Wiring for WD3-LP-D2, WD3-LP-D2-A and WD3-LP-D2-10
ORANGE
RED
BLACK
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Printed in U.S.A. 2/20 FR# 444159-00 Rev.3©Copyright 2020 Dwyer Instruments, Inc.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com