Series VPS Valve Position Sensor
ø2.375
[60.33]
1.125
[28.58]
.812
[20.62]
1.687
[42.85]
.313
[7.95]
1.032
[26.21]
.250
[6.35]
1.562
[39.67]
.781 [19.84]
.500 [12.70]
1.879 [47.73]
M12 x 1 THD. 4-PIN
QUICK
DISCONNECT
ø.218
[ø5.54]
(2) PL
1.180 [29.97]
Specifications – Installation and Operating Instructions
VPS2411 P1
Bulletin F-65
The dual inductive, 2-wire AC/DC Series VPS Valve
Position Sensor maintains VDI/VDE 3845 dimensions so
positioners can be easily mounted on top of the sensor and
target. The Model VPS2411 Sensor and Model P1 Target
mount easily and directly to actuators with ISO-NAMUR topworks (see picture below). Fully adjustable target in 2° increments, the sensor has two independent LED’s and bright
Flow Line indicator that provide local visual indication. All
electrical connections are made with the Model VIP82 4-pin
quick disconnect cable (6 ft. in length) for ease in installation.
Solid state components are fully embedded in an epoxy resin
to prevent condensation build-up and to protect against
vibration and shock. The rugged PBTP housing provides
excellent corrosion resistance and moisture protection.
Two VPS2411 and one P1 shown mounted with W.E.
Anderson pneumatic actuator and positioner.
Specifications
Power Requirements: 20-140 VAC (50/60 Hz)
10-200 VDC.
Output Operation: Dual normally open.
Load Current: ≤200 mA.
Minimum Load Current: 5 mA.
Leakage Current: ≤0.8 mA.
Voltage Drop: ≤5.0 V.
Repeatability: ≤0.01 mm.
Hysteresis: 3-15% of sensing range.
Switching Frequency: 25 Hz.
Temperature Limits: -13°F to 176°F (-25°C to 80°C).
Housing Material: Polybutylene Terephthalate (PBTP).
Electrical Connection: M12 4-Pin Quick Disconnect (Order
Model VIP82 for 6’ Long Mating Cable).
Mounting Holes: NAMUR Mounting 3.15˝ x 1.18˝ (80 x
30mm) or 5.12 x 1.18 (130 x 30mm).
Models:
Model VPS2411 - Valve Position Sensor
Model P1 - Valve Position Target
VIP82 - Quick Disconnect Cable, 6 ft. long.
Maintenance:
The unit requires no routine maintenance or lubrication.
The unit is not repairable.
PROXIMITY CONTROLS
A DIVISION OF DWYER INSTRUMENTS, INC.
1431 STATE HIGHWAY 210 E • FERGUS FALLS, MN 56537 U.S.A.
Phone: 218/739-3364 www.proximitycontrols.com
Fax: 218/739-2734 e-mail: proxsls@prtel.com
INSTALLATION DRAWING
NAMUR C BRACKET
MODEL No. VPS
COUPLING
COLLAR
TARGET RINGS
NAMUR ACTUATOR DIMENSIONS
NAMUR A HOLE PATTERN 30mm X 80mm, SHAFT HEIGHT 20mm
NAMUR B HOLE PATTERN 30mm X 80mm, SHAFT HEIGHT 30mm
NAMUR C HOLE PATTERN 30mm X 130mm, SHAFT HEIGHT 30mm
COVER
INSTALLATION PROCEDURE:
1. Fasten the Series VPS to the actuator with the appropriate fasteners (M5, 10-24, 10-32). For Namur C actuators
you must first attach the Namur C bracket to the actuator.
2. Attach the coupling to the actuator shaft for Namur A &
C actuators only.
3. Attach the collar to the actuator shaft or coupling.
4. Install one stainless steel flat head screw (two if it is a
dual sensor installation) into each of the target rings and
plug the other holes with the plastic screws or plugs. Slide
the target rings over the collar and adjust as appropriate for
open and closed position. NOTE: Bottom target energizes
the red LED and the top target energizes the green LED.
5. Place the cover onto the top target being careful to align
for proper flow indication and secure with M6 x 16 fastener
for Namur B actuators or M6 x 25 fastener for Namur A & C
actuators.
FLOW INDICATOR
WIRING DIAGRAM
MODEL VPS2411
PIN 4 BLACK
PIN 1 BROWN
NOTE:
1. WIRE COLORS ARE FOR VIP82 QUICK DISCONNECT CABLE
1 BROWN
SW1
GRN LED
SW2
RED LED
HOUSING CONNECTOR
4 BLACK
2 WHITE
3 BLUE
PIN 3 BLUE
MODEL No. P1
(+)
LOAD
LOAD
PIN 2 WHITE
6. Insert flow indicator to complete assembly or install coupling to maintain VDI/VDE 3845 dimensions if accessories
such as a positioner are to be installed.