Dwyer VPI User Manual

Series VPI Valve Position Indicator
W4
W3
L1
L2
3-27/32
[97.5]
1-61/64
[49.8]
2-25/32
[70.8]
3-51/64
[96.5]
1/2 NPT
4-3/4
[120.5]
BRACKET
H
Specifications - Installation and Operating Instructions
Bracket Dimensions Model
VPI-B01 VPI-B02 VPI-B03 VPI-B04
H in (mm)
1-13/64 [30.5] 1-19/64 [40.5] 1-19/64 [40.5] 2-3/8 [60.5]
L1 in (mm)
3-5/32 [80] 5-1/8 [130]
L2 in (mm)
3-15/16 [100] 5-29/32 [150]
W3 in (mm)
1-3/16 [30]
Bulletin V-37
W4 in (mm)
2 [50]
The Series VPI Rotary Valve Position Indicators are compact yet rugged for confined and severe locations. These versatile units offer visual position indication as well as two internal limit switch­es. The spring-loaded splined cams require no tools for a quick and precise adjustment. The Series VPI is available with mechan­ical or proximity limit switches. The mechanical models feature two SPDT limit switches. The proximity models feature two solid-state inductive limit switches eliminating the need for the cams to make contact with the switches. The NEMA 6 (IP67) rating ensures pro­tection against the ingress of liquid and debris.
ASSEMBLY
INDICATOR COVER
INDICATOR
BASE COVER
MAIN SHAFT
ASSEMBLY
MECHANICAL SWITCH
ASSEMBLY
TERMINAL
SPECIFICATIONS Minimum Rotation Travel: 60°. Maximum Rotation Travel: 360°. Temperature Limits: -4 to 176°F (-20 to 80°C). Switch Type: VPI-M: (2) mechanical SPDT limit switches; VPI-
P: (2) Inductive proximity limit switches. Electrical Rating: VPI-M: AC: 3A at 250 V, 5A at 125 V; DC:
0.2A at 250 V, 0.4A at 125 V, 4A at 30 V. Power Requirements: VPI-P: 12 to 24 VDC, 30 VDC maximum.
Enclosure Material: Aluminum die-casting. Electrical Connections: 8-contact screw terminal strip. Conduit Connection: (2) 1/2˝ female NPT. Enclosure Rating: NEMA 6 (IP67). Mounting: NAMUR. Weight: 1.9 lb (0.88 kg).
BASE BODY
EXPLOSION
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Phone: 219/879-8000 www.dwyer-inst.com
INSTALLATION
BRACKET
BRACKET
ACTUATOR
INSTALLATION
4X M6 BOLT
4X M5 BOLT
4X M6 SPRING
WASHER
4X M5 SPRING
WASHER
ADJUSTMENT
Safety Warning
• VPI Series is designed for non-explosion use. The VPI should not be installed in explosives areas.
• All input and supply pressure to valve, actuator, and other related devices must be turned off when installing.
VPI Installation
Installation Steps
1. Assemble limit switch body with the bracket.
2. Align main shaft of the limit switch box and the stem of the actuator. After the alignment, tighten the bracket onto the actuator.
Adjustment - Upper Switch
Push down upper switch and turn right or left for switch adjust­ment.
ADJUSTMENT-UPPER SWITCH
MICRO SWITCH
CAM
Adjustment - Lower Switch
Pull up lower switch and turn right or left for switch adjustment.
WIRING
Connection - Power
TOP SWITCH
BOTTOM SWITCH
MECHANICAL TYPE <2 SPDT>
CAM
NC
NO
C
TOP
SWITCH
BOTTOM
SWITCH
NC
C
NO
SOLENOID
VALVE
BROWN BLACK BLUE BROWN BLACK BLUE
SOLENOID
VALVE
RED BLACK BLUE YELLOW WHITE BROWN
CONNECTOR
CLOSE OPEN EXT
CLOSE OPEN EXT
1 2 3 4 5 6 7 8
GROUND
1 2
LOAD
3 4 5
LOAD
6 7 8
GROUND
ADJUSTMENT-LOWER SWITCH
MICRO SWITCH
CAM
MAINTENANCE
Upon final installation of the Series VPI Valve Position Indicator, no routine maintenance is required. A periodic check of system calibration is recommended. The Series VPI is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.