This instruction manual concerns the installation, operation, and maintenance of the flow transmitter, detectors,
and signal cables of the ultrasonic flow meter system. This manual should be read carefully prior to installation
and operation.
zRead the manual to gain an adequate understanding of proper operation of the equipment prior to
installation and operation. Improper results or hazardous conditions may result of improper installation,
operation or maintenance.
zThe specifications of this flow meter are subject to change without prior notice for improvement of the
product.
zDo not attempt to modify the flow meter. Manufacturer shall not bear any responsibility for hazardous
conditions or improper operation as a result of unauthorized modification. If it becomes necessary to
modify the flow meter, contact the manufacturer in advance for consulation and permission.
zThis instruction manual should always be kept on hand by the party responsible for operation.
zAfter reading the manual, store it in an accessible location for reference.
zThis instruction manual should be delivered to the end user upon purchase or installation.
zIf the instruction manual has been lost, request an appropriate replacement.
Modbus is a registered trademark of Schneider Automation.
zReproduction of this manual in whole or part is strictly prohibited
without prior written permission.
zContents of the manual are subject to change without prior notice.
Note
Issued in August, 2008
-i-
Bulletin F-107-UXF3
SAFETY PRECAUTIONS
Before using this product, read the following safety precautions to ensure proper use.
The following items are necessary for safe operation and must be fully observed.
These safety precautions are ranked in 2 levels; "DANGER" and "CAUTION".
Warning/Symbol Meaning
Incorrect handling of the device may result in death or serious injury.
Incorrect handling may lead to a risk of physical damage or significant injury.
The items noted under "" may also result in serious equipment malfunction if not fully observed,
depending on the circumstances.
All the items must be fully observed.
Caution on mounting and piping
zThis unit is not explosion-proof. Do not use it in a place with explosive
gases. Otherwise, this may result in serious accidents such as explosion,
fire, etc.
zThe unit should be installed in a place conforming to the installation
requirements noted in this instruction manual. Otherwise, it may cause
electric shocks, fire or malfunction of the unit.
zInstall the flow meter according to the following steps to prevent it from
damage, error or malfunction.
zDuring installation, ensure the inside of the unit is free from cable chips
and other foreign objects. Otherwise, it may cause fire, failure or
malfunction.
zThe items under "Caution on Installation" noted in this manual must be
fully observed. Careless installation may result in trouble or malfunction of
the unit.
Cautions in wiring
zWhen performing wiring termination, observe appropriate instructions to
prevent ingress by moisture, dew condensation or water leaks, follow
“Section 3.4 – Flow transmitter wiring” described in this manual.
zBefore performing the wiring work, be sure to turn OFF the main power.
Otherwise, electric shock may result.
zDo not perform wiring work outdoors in inclement weather to prevent
insulation deterioration and dew condensation. Otherwise, malfunction or
accelelerated deterioration may result.
zBe sure to connect a power source of correct rating. Use of improper
power sources out of rating may cause fire.
zThe unit must be grounded as specified. Otherwise, it may result in electric
shocks, malfunction, etc.
zThe signal cable and analog output signal cable should be wired as far
away as possible from high-voltage lines to prevent entry of noise signals
as it will result in malfunction of the unit.
zTo prevent malfunction of the unit, the analog output signal cable and the
power supply cable may require separate conduits.
-ii-
Bulletin F-107-UXF3
Caution on maintenance and inspection
zThe unit should be inspected every day to ensure proper operation.
zWhen measuring the insulation resistance between the power/output
terminal and the case, follow “Section 6.2.3 – How to measure insulation
resistance” described in this manual.
zIf the fuse is blown, detect and eliminate the root cause, and then replace
the fuse with a spare. If there are no spares, replace the fuse with the
appropriate part specified in this manual. Use of a fuse other than
specified or its short-circuit may cause an electric shock or fire. The fuse
should be replaced according to “Section 6.3 – How to replace the fuse”
described in this manual.
-iii-
Bulletin F-107-UXF3
CAUTION ON INSTALLATION LOCATION
(1) A location that provides enough space for periodic inspection and wiring work.
(2) A location not exposed to direct sunlight nor inclement weather.
(3) A location free from excessive vibration, dust, dirt and moisture.
(4) A location not subjected to radiated heat from a heating furnace, etc.
(5) A location not subjected to corrosive atmosphere.
(6) A location not to be submerged.
(7) A location remote from electrical devices (motor, transformer, etc.) which generate
electromagnetic induction noise, electrostatic noise, etc.
(8) A location not subjected to excessive fluid pulsation such as pump discharge side.
(9) A location that provides enough place for the length of the straight pipe.
(10) A location where ambient temperature and humidity are -20 to +50°C and 95% RH or less for
flow transmitter, -20 to +60°C and 100% RH or less for detector.
Flow transmitter main unit ········································· 1 set
Waterproof gland (Built into the main unit) ················ 1 set
Wall mount frame (Built into the main unit)················ 1 set
Panel mounting bracket (option)
(U bolt, support fixture, butterfly nut 2 pieces,
spring washer 2 pieces, plain washer 2 pieces) ········ 1 set
Detector (SX1-A)
Small size detector···················································· 1 set
Chain × 2··································································· 1 set
Silicone rubber, optional silicone-free grease or
silicone grease ······················································ 1 piece
Detector (SX1-B)
Middle size detector × 2 ············································ 1 set
Wire rope × 2 ···························································· 1 set
Mounting spring × 2··················································· 1 set
Silicone rubber, optional silicone-free grease or
silicone grease ······················································ 1 piece
Detector (SX1-C)
Large size detector × 2·············································· 1 set
Wire rope × 2 ···························································· 1 set
Mounting spring × 2··················································· 1 set
Detector mounting set ···············································1 set
Bulletin F-107-UXF3
Detector (SX2-A)
Small diameter detector ············································ 1 set
Stainless steel belt ···················································· 1 set
Silicone rubber, optional silicone-free grease or
silicone grease ·······················································1 piece
Detector (SX2-B)
High temperature detector ········································ 1 set
Stainless steel belt ···················································· 1 set
Silicone grease (for high temperature detector) ·····1 piece
Signal cable (for SX1) (length specified) × 2 ················ 1 set
Signal cable (for SX2) (length specified) × 2 ················ 1 set
CD-ROM (Instruction manual and loader software)···1 piece
Not included
Power cable
Output signal cable
RS-485 communication cable
Flow transmitter (UXF3)
(IP66)
Pipe mounting bracket
(option)
Detector (SX1-A)
Small size detector
Chain
Detector (SX1-B)
Middle size detector
Wire rope
Mounting spring
Detector (SX1-C)
Large size detector
Wire rope & springs
Detector mounting set
Detector (SX2-A/B)
Small diameter detector
High temperature detector
Stainless steel belt
Signal cable (for SX1)
Signal cable (for SX2)
Acoustic coupler
Silicone rubber
Silicone-free grease
Silicone grease for high
temperature
Silicone grease
-1-
Bulletin F-107-UXF3
1.2. NAME AND FUNCTION OF EACH PART
1.2.1. Flow transmitter : UXF3
(9)
(3)
(4)
(8)
(15)
(13)
(5)
(6)
(1)(2)
No. Name Key Description
(1) Wiring connection port, large Wiring connection port for power cable and output cable.
(2) Wiring connection port, small Wiring connection port for signal cable only.
(3) Indication and setting unit Indicates and sets the flow rate, etc.
Received wave diagnostic
(4)
indication (LED)
(5) Escape key
(6) UP key Selects items, numeric values and symbols.
(7) Shift key Moves the cursor and selects decimal place.
(8) Entry key
(9) LCD display Indicates the flow rate or setting.
(10) Power terminal Connects the power cable.
(11) Input/output terminal Connects signal cable, analog output or DO output cable.
Indicates whether received wave is normal (green) or abnormal
(red).
Returns to the next-higher menu level or cancels the set status.
Enters a selection or registers a setting.
Connects communication cable.
(A communication board is optional)
Mounted if communication synchronization is optionally
designated.
(12)
(11)
(14)
-2-
Bulletin F-107-UXF3
(Page intentionally blank)
- 3 -
Bulletin F-107-UXF3
1.2.2. Reserved
1.2.3. Reserved
1.2.4. Small/middle size detector (SX1-A, SX1-B)
(3)(2)
(1)
SX1-A
No. Name Description
(1) Signal cable Transmits send/receive signals.
(2) Detector Sends and receives an ultrasonic wave.
(3) Chain Fastens the detector on pipe.
(4) Wire rope Fastens the detector on pipe.
(5) Mounting spring Removes the play of wire rope.
SX1-B
(5)(1)
(2)
(4)
- 4 -
1.2.3. Large size detector (SX1-C)
(3)
(4)
Bulletin F-107-UXF3
(2)
(1)
SX1-C
No. Name Description
(1) Signal cable Transmits send/receive signals.
(2) Detector Sends and receives an ultrasonic wave.
(3) Wire rope Fastens the detector on pipe.
(4) Mounting spring Removes the play of wire rope.
- 5 -
Bulletin F-107-UXF3
1.2.4. Small diameter/High temperature detector (SX2-A, SX2-B)
(1)(1)(4)(3)(3)(2)(4)
(5)(8)(6)
SX2-B
SX2-A
No. Name Description
(1) Signal cable Transmits the send/receive signals.
(2) Sensor unit Sends and receives an ultrasonic wave.
(3) Element holder Attaches the sensor unit firmly to the pipe.
(4) Lock nut Fixes the sensor unit mounting position.
(5) Scale Reads the spacing between the sensor units.
(6) Frame Fastens the sensor unit on pipe.
(7) High temperature
detector
(8) Stainless steel belt Fastens the sensor frame on pipe.
Sends and receives an ultrasonic wave.
(5)(8)(6)
(7)
- 6 -
Bulletin F-107-UXF3
2. INSTALLATION AND BEFORE START OF
OPERATION OF THE FLOW TRANSMITTER
2.1. Outline of installation procedure
Section 3.3
Section 3.4
Power ON *
Section 4.4 Parameter protection * Metric system is selected for unit.
*
NG
Section 4.6
OK
Section 5 Mounting of detector *
NG (LED display is red)
Section 6.6.1.3 Checking the RAS information Section 6.6.2
OK (LED display is green)
Section 6.6.2
Check the data display AGC U AGC D
AGC U P/H U
AGC D
P/H U Section 6.6.6 Checking received waveforms
P/H D
Contact manufacturer's service representative.
Section 4.7 Zero Adjustment *
Basic operation Section 4.9.1.3 Output limit
Section 4.8.1 How to set the unit system Section 4.9.2 Setting the total
Section 4.9.1.2 Setting of analog output at error
Application operation
Section 4.9.1 Setting of flow rate range
Section 4.10.1 Setting automatic 2 ranges
Section 4.10.2 Setting the Bi-directional range Section 4.10.5.3 Setting the flow switch
Section 4.10.3 Setting the Bi-directional auto 2
Section 4.10.6Setting the DI input
Section 7.3 ORDERING INFORMATION
Section 6 CHECK AND MAINTENANCE
Installation of flow transmitter
Flow transmitter wiring
Checking and Setting of Piping
Specifications/Detector
Displaying the data in
maintenance mode
35% or more
5528 to 6758
range)
(Burnout) Section 4.9.4 Setting the LCD indication
range
Run (Measurement)
Check the power supply specifications and wiring before
turning on the power. (Refer to “1.2.Check on type and
specifications”.)
The initial display language is English. Switch the languages
as required.
Section 4.6.2 Piping parameter setting method
Be careful not to mount the sensor units with wrong mounting
dimension. Mount it with the dimension displayed at the
process setting of the piping parameter. (Refer to “5.
Mounting of detector”.)
Displaying the data in
maintenance mode
Check the data display
35% or more
Outside the range
P/H D
Before performing zero point adjustment, check that the pipe
is filled with fluid, the fluid is in still state, and that the
measurement status is normal.
Section 4.9.3 Setting the DO output Section 4.9.1.1 Setting of flow rate range (single
Section 4.9.3.1 How to validate the total pulse
output
Section 4.10.5.2 How to validate the alarm
output
Section 4.10.5.4 How to validate the total
switch
of 5528 to 6758
-7-
Bulletin F-107-UXF3
3. INSTALLATION
Select an installation location that satisfies the following conditions for ease of maintenance and inspection, service life of
the instrument, and assurance of reliability all considered.
CAUTION
(1) A location where ambient temperature and humidity are -20 to +55°C and 90% RH or less for transmitter
(UXF3), -20 to +80°C and 90% RH or less for detector (SX1) and -20 to +60°C and 90% RH or less for
detector (SX2).
(2) A location not exposed to direct sunlight nor inclement weather.
(3) Space for periodic inspection and wiring work is available.
(4) A location not subjected to radiated heat from a heating furnace, etc.
(5) A location not subjected to corrosive atmosphere.
(6) A location not to be submerged.
(7) A location free from excessive vibration, dust, dirt and moisture.
3.1. Installation location of flow transmitter
Secure at least 100 mm (3.94 in.) of space between the flow transmitter and nearby wall. Also secure a space of opening the front
cover in case of maintenance.
Allow space for cable wiring under the case.
N
E
P
O
147(5.79)
400(15.75) or more
Fig. 3.1 Top view of mounting (Flow transmitter : UXF3) [unit: mm(inch)]
147(5.79)
>100
(3.94)
-8-
Bulletin F-107-UXF3
3.2. Installation location of detector
The measuring accuracy is considerably affected by the detector mounting place, including physical setup of pipe to
measuring a flow rate. Select a location which meets the condition in section 3.2.1. (Length of straight pipe). Also, reserve
enough space for installation and maintenance referring to the following diagram.
>200
(7.87)
>2000
(78.74)
>200
(7.87)
D+1200(47.24) or more >600(23.62) D >600(23.62)
Adequate space for the installation location of detector
D : Pipe diameter
Unit : mm(inch)
-9-
Bulletin F-107-UXF3
3.2.1. Length of straight pipe
The length of upstream and downstream straight pipe of the ultrasonic detector should be long enough to ensure accurate
measurements.
(D is nominal diameter for a pipe)
Type Length of upstream straight pipe Length of downstream straight pipe
L≥5D
L≥10D
90° vending
10D or more
L≥10D
L≥50D
Tee
10D or more
10D or more
Extension pipe
Contraction pipe
Individual valves
Pump
L≥30D
0.5D or more
D
1.5D or more
L≥10D
L≥30D
When adjusting flow rate by the valve on the
upstream side
Isolation valve
Check valve
P
L≥5D
L≥5D
L≥10D
When adjusting flow rate by the valve on the
downstream side
L≥50D
Note) Source: Japan Electric Measuring Instruments Manufacturers' Association (JEMIS-032)
-10-
Bulletin F-107-UXF3
3.2.2. Mounting position
The detector can be installed vertical, horizontal or at any position provided that attention is paid to the following things.
(1) The piping must completely be filled with fluid when it flows.
Air-collecting
Pipe may
not be filled
with liquid.
Pump
Pipe may not be filled with liquid.
Good
Good
(2) Where a horizontal pipe is used, install the sensor within ±45° from the horizontal plane. Otherwise, the measurement
could be impossible if bubbles stay in the upper part of piping or if deposits are accumulated in the lower part of piping.
In case of vertical piping, the detector may be mounted at any position on its periphery provided that the flow is upward.
Pipe
45
Horizontal
45
(3) Avoid installing the sensor on a deformed portion of pipe or welded portion of pipe, or on flange.
Welded part
Welded part is provided.
Welded part is straddled.
Welded part
Welded part is not provided.
Remove the welded part.
-11-
Bulletin F-107-UXF3
3.3. Installation of flow transmitter
The flow transmitter may be mounted on a wall or 2B pipe stand (option).
3.3.1. Wall mounting (Flow transmitter : UXF3)
For wall mounting, use two M8 bolts.
Drill holes according to the mounting hole dimensions shown below, and fasten the flow transmitter using the M8 bolts.
[unit: mm]
Nominal Standard tightening torque
M8
3.3.2. 2B pipe stand mounting (Flow transmitter : UXF3)
When mounting on 2B pipe, be sure to use a complete set of fixtures (U bolt, support fixture, plain washer,
spring washer, nut) furnished if optionally designated. Tighten the nut by hand. If any support fixture is not used
or if the assembly is excessively tightened by tool, the wall mounting fixture may be damaged.
Mount the instrument on 2B pipe stand as illustrated below.
Support fixture
Plain washer
U bolt (M8)
Spring washe
Nut
r
12.5 [Nm]
- 12-
2B pipe stand
Bulletin F-107-UXF3
(Page intentionally blank)
Bulletin F-107-UXF3
3.4. Flow transmitter wiring
3.4.1. Cautions in wiring
(1) Use a special coaxial cable as a signal cable between the detector and flow transmitter. Do not provide a
junction or splice of the signal cable midway.
(2) The signal cable between the detector or flow transmitter should be run in metallic conduits. Upstream and
downstream signal cables may be put in the same conduit but, to avoid interference, do not put the power
cable together with the signal cables.
(3) For output signal, use a shielded cable, where possible.
(4) To avoid noise interference, do not put the cables together with heavy duty line or the like into the same
duct.
(5) If a ground wire is included in the power cable, connect it to ground properly.
(6) A power switch is not provided on the instrument and must be mounted separately if desired.
(7) Seal unused wiring ports with available caps.
3.4.2. Applicable wires
Use the following cables.
z Power cable : 3-wire or 2-wire cabtyre cable
Nominal sectional area 0.75mm
Outside diameter Ɏ11mm (0.433 in)
z Output signal cable : 2-wire or multi-wire cabtyre cable as required
Outside diameter Ɏ11mm (0.433 in)
z Detector-flow transmitter cable : Signal cable by type designation
2
(0.00117 in2) or more
In case of SX1 : High-frequency coaxial double shield cable with characteristic
impedance of 50ȍ
Outside diameter Ɏ7.3mm (0.288 in)
In case of SX2 : High-frequency coaxial double shield cable with characteristic
impedance of 50ȍ
With one-side waterproof BNC connector
Outside diameter Ɏ7.3mm (0.288 in.)
3.4.3. Treatment of wiring port
The casing of the flow transmitter is IP66. However, if installed in a humid place, the wiring ports must be made airtight to
avoid ingress of moisture, condensation, etc. Be sure to use the waterproof glands furnished with the instrument in order to
ensure the waterproof capability. A gland, which is not ready to be used, should be sealed with the supplied cover.
Do not install the instrument where there is a risk of flooding.
- 14 -
3.4.4. Wiring to each terminal
3.4.4.1. Flow transmitter :
Carry out wiring to each terminal according to the following figure.
Bulletin F-107-UXF3
Power supply board terminal block
AC power supply
100 to 120V AC
DC power supply
20 to 30V DC
or 200 to 240V AC
50/60Hz
NL
−+
Communication board terminal block (option)
RS-232C and DIRS-485 and DI
Status input
RS-232C
Non-voltage contact input
TXDDI1GND RXD
Note)
DI1
Status input
Non-voltage contact input
TXDR2
RS-485
TXDR1SHILD
Power cable
Output signal cable
(analog output, DO1,
DO2, DO3, DI)
External ground terminal
Ground terminal (M4)
Downstream
sensor cable
Upstream
sensor cable
Note)
Main board terminal block
−−
+
White
Black
Green
+
DO1DO2DO3
To upstream
sensor
When you use optional PC communication loader cable,
connect the cable of which terminal cap is black to GND,
yellow to RXD and red to TXD.
−
+
+
I out
−
GND
To upstream
sensor
GND
HF1HF2
To downstream
sensor
*1*1
SHSH
White
Black
Green
Iout: Analog output
To downstream
sensor
DO1, 2 : Transistor/open collector
DO3: Relay contact
Note 1) All screws are M3 on the terminal block. Use crimp-style terminals for M3 and whose outer diameter is Ɏ5.8 or
smaller.
Note 2) Be sure to connect ground terminal to external ground terminal. (Class D grounding)
Note 3) For output signal, use multiple core cable as required.
-15-
Bulletin F-107-UXF3
3.4.4.2. Reserved
(Page intentionally blank)
-16-
4. Parameter
4.1. Description of display/setting unit
Display unit and setting unit are as shown below.
4.1.1. Flow transmitter : UXF3 display/setting unit
LED
Bulletin F-107-UXF3
4.1.2. Reserved
- 17 -
Bulletin F-107-UXF3
4.1.3. Description of display/setting unit
ż LCD display: Displays the measurement and setting (indication in 16 digits, 2 lines).
“Measurement display”
Up to 8 digits including the decimal point are displayed in the data field. When the displayed
digits exceed, “<” is displayed at the first digit. When the range exceeds maximum or is below
minimum setting, “OVERFLOW” or “UNDERFLOW” is displayed blinking on the Display 2.
Flow direction, during test mode “T”
Display 1
Display 2
Flow direction
Display 1
Display 2
Display 1
Display 2
ż LED display: Indicates whether the received wave is normal or not.
Set the parameter by setting switches.
ESC
ESCAPE key : Return to the next-higher menu level or cancels the set status.
O
UD
(Green) : Received wave is normal.
(Red) : Received wave is abnormal.
Data
Data
DataUnit
V E R L O WF
DataUnit
N E RLO WF
Unit
Unit
UP key : Selects items, numeric values and symbols.
SHIFT key : Moves the cursor and selects decimal place.
ENT
ENTRY key : Enters a selection or registers a setting.
Note) For changing the parameter, enter the changed value, and press this key to confirm
that it is registered.
-18-
4.2. Composition of key operation
0.000 m/s
0.000 m3/h
Measurement mode
PAR.PROTECTIONPROTECTION ON
ENT
PROTECTION OFF
Bulletin F-107-UXF3
OUTPUT SETZERO ADJUSTMENTCLEAR
ENT
ENT
SET ZERO
DAMPING
CUT OFF
DISPLAY1ST ROWVELOCITY
ENT
2ND ROW(Same as "1ST")
RANGERANGE TYPESINGLE
ENTENT
ENT
FLOW RATE
FLOW RATE(%)
+TOTAL(ACTUAL)
+TOTAL PULSE
-TOTAL(ACTUAL)
-TOTAL PULSE
ENT
AUTO 2
BI-DIR
BI-DIR AUTO 2
FULL SCALE 1
FULL SCALE 2
RANGE HYS.
BURNOUT (CURRENT)NOT USED
ENT
HOLD
UPPER
LOWER
ZERO
-19-
Bulletin F-107-UXF3
BURNOUT TIMER
OUTPUT LIMIT LOW
OUTPUT LIM.HIGH
RATE LIMIT
RATE LIMIT TIMER
TOTALTOTAL MODESTART
ENT
ENT
STOP
TOTAL RATE
TOTAL PRESET
PULSE WIDTH
BURNOUT (TOTAL)HOLD
BURNOUT TIMER
DO1 OUTNOT USED
ENT
+TOTAL PULSE
-TOTAL PULSE
FULL SCALE 2
ALARMALL
TOTAL RESET
ENT
NOT USED
ENT
HARDWARE FAULT
FLOW SWITCHFLOW SW HIGH
TOTAL SWITCH
AO RANGE OVER
PULSE RANGE OVER
-FLOW DIRECTION
DO2 OUT(Same as "DO1 OUT")
DO3 OUT(Same as "DO1 OUT")
ENT
ENT
-20-
PROCESS ERROR
ENT
FLOW SW LOW
DI1 INPUTNOT USED
CALIBRATION ZERO
CALIBRATION SPAN
OPERATION MODE
MEASURE SETUPSYSTEM UNIT
ENT
FLOW UNIT
TOTAL UNIT
PROCESS SETTINGOUTER DIAMETER
Bulletin F-107-UXF3
ENT
TOTAL RESET
ZERO ADJUSTMENT
ENT
PIPE MATERIAL
MAINTENANCE MODERAS INFORMATION
ENT
CURRENT
OUTPUT SETTING
TOTAL PULSE
WALL THICKNESS
LINING MATERIAL
LINING THICKNESS (Except for "NO LINING")
KIND OF FLUID
VISCOSITY
SENSOR MOUNT
SENSOR TYPE
TRANS.VOLTAGE80Vpp (Initial value)
DO CHECK
DI CHECK
TEST MODE
-21-
Bulletin F-107-UXF3
COMMUNICATIONMODERS-232C
ENT
ENT
RS-485
AUD RATE 9600bps
B
ENT
19200bps
38400bps
PARITYNONE
ENT
ODD
EVEN
STOP BIT1 BIT
ENT
2 BITS
STATION No.
PROTOCOLMODBUS
ENT
M-Flow
SYSTEM LANGUAGEENGLISH
ENT
JAPANESE
GERMAN
FRENCH
SPANISH
REGISTER ID NO.
VER. NO.
MEMORY INITIALIZE
LCD/LED CHECK
DATA DISPLAY
DETAILSTRANS.COUNT128 (Initial value)
ENT
ENT
TRIGGER CONTROLAUTO (Initial value)
ENT
MANUALTRIGGER LEVEL
WINDOW CONTROLAUTO (Initial value)
ENT
MANUALU:OPEN TIME
ENT
ENT
-22-
D:OPEN TIME
Loading...
+ 111 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.