Dwyer ULL User Manual

Series UL Transmitters
TM
Specifications - Installation and Operating Instructions
Bulletin L-UL
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Phone: 219/879-8000 www.dwyer-inst.com
able of Contents
hapter 1. Introduction
C
pecifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
S
Measuring Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Chapter 2. Installation
recautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
P
nstalling the Unit on Threaded Flange/Thread-Free Flange . . . . . . . . . . . . . . . .3
I
nstalling the Unit via Extension Pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
I
sing a Conduit Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
U
Non-Intrinsically Safe Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Power Supply and Load Resistance Recommendations . . . . . . . . . . . . . . . . . . .4
hapter 3. Set Up
C
eries UL Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
S
et Up and Function Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
S
Resetting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Entering Distance to Empty Level (Tank Height) . . . . . . . . . . . . . . . . . . . . . . . . . .6
Defining Interfering Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Configuring 4 mA Current Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
onfiguring 20 mA Current Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
C
electing Low/High Dynamic Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
S
efining Working Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
D
Selecting Distance or Level Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Entering Factor for Gas Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Restoring the Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Shifting the Blocking Distance (SBD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
erifying the Version Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
V
efining 22 mA Signal Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
D
Chapter 4. Open Channels (ULF)
Selecting the Flow Measurement Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Open Channel Flow Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Flume/Weir Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Flumes/Weirs - European Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Rectangular Suppressed Sharp - Crested Weir (Type 1) . . . . . . . . . . . . . . . . . .11
Rectangular Contracted Sharp - Crested Weir (Type 2) . . . . . . . . . . . . . . . . . . .11
Trapezoidal (Cipolletti) Sharp - Crested Weir (Type 3) . . . . . . . . . . . . . . . . . . . .11
V-Notch (Triangular) Sharp - Crested Weir (Type 4) . . . . . . . . . . . . . . . . . . . . . .11
Khafagi-Venturi Flume (Type 5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Parshall Flume (Type 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Palmer Bowlus Flume Trapezoidal Throat Cross-Selection (Type 7) . . . . . . . . .12
H Flume (Type 8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Neyrpic Venturi Flume/Long-Base Weir (Type 9) . . . . . . . . . . . . . . . . . . . . . . . .13
Flumes/Weirs – American Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Rectangular Suppressed Sharp - Crested Weir (Type 1) . . . . . . . . . . . . . . . . . .13
Rectangular Contracted Sharp - Crested Weir (Type 2) . . . . . . . . . . . . . . . . . .13
Trapezoidal (Cipolletti) Sharp - Crested Weir (Type 3) . . . . . . . . . . . . . . . . . . . .13
V-Notch (Triangular) Sharp - Crested Weir (Type 4) . . . . . . . . . . . . . . . . . . . . . .13
Parshall Flume (Type 5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Palmer Bowlus Flume Trapezoidal Throat Cross-Selection (Type 6) . . . . . . . . .14
H Flume (Type 7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Leopold-Lagco Flume (Type 8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
able of Figures
igure 1: Front and Side View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
igure 2: Threaded Flange/ Thread - Free Flange Monitoring . . . . . . . . . . . . . . . . .3
Figure 3: Extension Pipe Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Figure 4: Conduit Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Figure 5: Non-Intrinsically Safe Positive Ground Connection . . . . . . . . . . . . . . . . . .4
igure 6: Non-Intrinsically Safe Negative Ground Connection . . . . . . . . . . . . . . . . .4
igure 7: Functions Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
igure 8: Display and Function Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
igure 9: Scan Distance Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Figure 10: Defining Working Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Figure 11: Rectangular Suppressed Sharp - Crested Weir . . . . . . . . . . . . . . . . . . .11
Figure 12: Rectangular Contracted Sharp - Crested Weir . . . . . . . . . . . . . . . . . . . .11
igure 13: Trapezoidal (Cipolletti) Sharp - Crested Weir . . . . . . . . . . . . . . . . . . . . .11
igure 14: V-Notch (Triangular) Sharp - Crested Weir . . . . . . . . . . . . . . . . . . . . . . .11
igure 15: Khafagi-Venturi Flume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Figure 16: Parshall Flume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Figure 17: Palmer Bowlus Flume Trapezoidal Throat
Figure 18: H Flume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
igure 19: Neyrpic Venture Flume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
igure 20: Long-Base Weir . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
igure 21: Rectangular Suppresses Sharp - Crested Weir . . . . . . . . . . . . . . . . . . .13
Figure 22: Rectangular Contracted Sharp - Crested Weir . . . . . . . . . . . . . . . . . . .13
Figure 23: Trapeziodal (Cipolletti) Sharp - Crusted Weir . . . . . . . . . . . . . . . . . . . . .13
Figure 24: V-Notch (Triangular) Sharp - Crested Weir . . . . . . . . . . . . . . . . . . . . . .13
Figure 25: Parshall Flume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
igure 26: Palmer Boweus Flume Trapezoidal Throat
igure 27: H Flume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Figure 28: Leopold Lagco Flume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Figure 29: Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Cross-Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
ross-Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
C
Chapter 5. Troubleshooting
22 mA Signal Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Appendix A – Gas Factor Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Appendix B – Installation Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Appendix C – Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Page 1
hapter 1: Introduction
C
he unit is available in three separate series: The ULB for solids, the ULL for
iquids, and the ULF for open channel flow liquids.
l
Depending on the series, the unit can be used for the following measurement tasks:
• Dust-free tanks with solids (ULB)
• Open channel flow (ULF) Liquid tanks with calm surfaces (ULL)
he ULF and ULL have a range of up to 49.21 ft (15 m) with an accuracy of 0.25%
f the maximum measuring range (version dependent).
o The ULB has a range of up to 28 ft (8.5 m) with an accuracy of 0.25% of the maximum measuring range (version dependent).
Figure 1 : Front and Side View
PECIFICATIONS
S
ervice: ULB: Bulk solids, ULF/ULL: Compatible liquids.
S
etted Materials: Sensor: Polypropylene or PVDF (upon request), Acoustic
W
indow: ECTFE.
W
Ranges: (see “Measuring Ranges”). Accuracy: 0.25% of max range (at 20°C). Resolution: 0.04˝ (1 mm).
lind Zone: (See “Blind Zone”).
B
eam Angle: 5° @ 3db point.
B
emperature Limits: -40 to 158°F (-40 to 70°C).
emperature Compensation: Automatic.
ax. Loop Resistance: 727 Ω at 28 VDC.
M
lectrical Connection: Screw terminal.
E
onduit Connection: 1/2˝ NPT conduit or cable gland (optional).
C Process Connection: 2˝ NPT or 2˝ BSP (optional). Enclosure Material: ABS and UV resistant. Enclosure Rating: NEMA 4 (IP65). Mounting Orientation: Vertical.
emory: Non-volatile.
M
isplay: 4 character LCD.
D
nits: ft, m (upon request).
U Programming: 4 button. Weight: 3.1 lb (1.4 kg).
Measuring Ranges
0.82 to 11.5 ft
0.25 to 3.5 m
1.96 to 28 ft .6 to 8.5 m
0
.82 to 16.4 ft
0
0.25 to 5 m
1.96 to 49.2 ft
0.6 to 15 m
0.82 to 16.4 ft
0.25 to 5 m
1.96 to 49.2 ft
0.6 to 15 m
LB for solids
U
ULF for open­channel flow
ULL for liquids
tandard
S
Extended Range Short Range
Standard
Short Range
Standard
Blind Zone (Measured from the tip of the sensor)
ULB-11 ULL-1XXX ULF-X1-XXX ULB-12 ULL-2XXX ULF-X2-XXX
0.8 ft (0.25 m)
1.96 ft (0.6 m)
Page 2
hapter 2: Installing the Unit
C
recautions
P
Ensure that the unit is mounted in an area that meets the stated temperature,
• pressure and technical specifications.
• Ensure that high-voltage sources or cables are at least 40˝ (1 m) away from the sensor and its cable.
Use round cables with minimum diameter of 0.24 to 0.28˝ (6 to 7 mm) to ensure
hat the unit remains sealed per IP65 standards.
t
Ensure that cables are routed correctly and tightened along walls or pipes.
Installation and operation of this product should be performed according to the
• Product Installation and Operating Instructions. Otherwise the use of this product is prohibited.
hen installing the unit ensure that it is:
W
Mounted above the dead-zone area.
OTE: If the device enters the blocking distance (dead- zone
N
or blind zone), it will not measure correctly.
• Positioned at least 1.64 ft (0.5 m) away from the tank walls. Add 4˝ (10 cm) spacing for each 40˝ (1 m) in range.
nstalling the Unit on Threaded Flange/Thread-Free Flange
I
he unit is available in 2˝ NPT or 2˝ BSP (upon request).
he unit can be installed with threaded-flange mounting or with thread-free flange
igure 2: Threaded Flange/Thread-Free Flange Mounting
OTE: When installing a thread-free flange mounted unit, you will need a 2˝
N
(50.8 mm) locking nut to secure the unit inside the tank.
To Install the Unit:
1. Insert the threaded end of the unit into the opening at the top of the tank or pipe. . Bolt the unit into place in one of the following ways:
2
Threaded-flange mounting: Screw the unit into a flange with a threaded
• ˝ (50.8 mm) hole.
2
Thread-free mounting: Place the unit in the flange, and bolt it from within
the tank with a 2˝ (50.8 mm) locking nut.
• Perpendicular to the surface of the target. NOTE: Even the slightest difference in angle may affect echo quality.
• Placed as far as possible from noisy areas, such as a filling inlet.
NOTE: When installed in a humid environment it is recommended to position the sensor on a tripod on top of the vessel.
NOTE: Tighten the locking nut hand tight only. When tightening the nut, hold the lower part of the unit, and make sure that the seal is leak proof.
Page 3
nstalling the Unit Via Extension Pipes
I
f the level of the measured surface falls within the dead-zone, (blind zone) area,
I
ou should use an extension pipe to mount the unit.
y
When using an extension pipe, ensure that:
• The sensor is positioned in the center of the pipe.
• The pipe extension is exactly perpendicular to the surface
f the target.
o
The internal pipe diameter is at least 3.0˝ (76.2 mm) wide.
The pipe is preferably made of plastic and must have a
mooth interior surface.
s
• The pipe should not protrude inside the tank.
• The tank opening should be at least the size of the internal pipe diameter and have a smooth edge.
hen installing the unit with extension pipes, measure from sensor’s lower edge
W
nd follow these specifications:
a
ipe Length
P
1.64 ft (0.5 m)
OTE:
N
. It is always recommended to use the interference signal feature (Pr03) to locate
1
nterfering signals when using an extension pipe.
i
2. The sensor's lower edge may be
a) aligned with the extension pipe's upper edge or b) protrude it by up to 2.56˝ (6.5 cm). See Figure 3 below:
Internal Pipe Diameter
≥ 3.0˝ (76.2 mm)
on-Intrinsically Safe Connections
N
Figure 5: Non-Intrinsically Safe Positive Ground Connection
Figure 6: Non-Intrinsically Safe Negative Ground Connection
ower Supply and Load Resistance Recommendations
P
The following table specifies the recommended resistance range for each power supply voltage (Non-Intrinsically Safe).
Power Supply Voltage
18 V 24 V 28 V
Minimum Resistance Value
0 Ω 41 Ω 68 Ω
Maximum Resistance Value
272 Ω 545 Ω 727 Ω
a
Figure 3: Extension Pipe Recommendation
Using a Conduit Adapter
1. Remove the four retaining screws from the conduit adapter cover.
2. Pull the electrical wires through the 1/2˝ NPT conduit connection or gland.
3. Connect the -24 V wire to Terminal 1, connect the +24 V wire to Terminal 2 on
the wiring block.
4. Return the adapter's cover to its place properly. Make sure that the O-ring is
placed correctly. Fasten the four retaining screws.
Figure 4: Conduit Adapter
NOTE: The conduit adapter should not exceed a torque of 50 lb-in.
To maintain a proper seal, make sure that conduit is firmly screwed to the conduit's adaptor.
NOTE: The resistance value is the total sum of the series resistor (or PLC
resistance) and the lines resistance. The minimum voltage level on terminals should not be less that 18 VDC.
To maintain a proper seal, make sure that conduit is firmly screwed to the conduit's adaptor.
Ripple/Noise Parameters Recommended for the Power Supply
The following ripple/noise parameter is recommended for the power supply:
• 100 mV p-p max.
Power Supply Types Recommendations
• Prefer a regulated switching power supply.
• A rectified power supply is not recommended.
• When powering by a battery, avoid the using of switched charger.
Feeding Via PLC
• Verify that the voltage level on the unit’s terminals is at least 18 VDC.
• Check PLC specifications for grounding options.
• It is good practice to add a 150 Ω series resistor between the unit's positive terminal and the PLC.
Page 4
hapter 3: Setting Up and Calibrating the Unit
C
his chapter explains how to set up and calibrate the unit for accurate
easurement monitoring.
m
he unit is supplied with preprogrammed default settings, making it ready for
eight, as described on page 6. When using the unit, the tank height is calculated
h
s the distance from the surface of the sensor to the bottom of the tank. You should
a
nter this value whenever tank height is required. (For flow measurement, enter the
e
recise flume height.)
p
The ULF, ULL and ULB units contain eleven, ten and nine programs respectively. These programs are referred to as functions, which enable you to change the
efault settings and calibrate as required. These functions are accessed from a
d
unctions menu. The functions Pr01, Pr02, Pr04 and Pr05 are the most important
f
o ensure correct usage of your device (with the addition of Pr00 if using the
t appropriate ULF series). Function Pr03 may be used if there are interfering signals. The remaining functions (Pr06, Pr07, Pr08, Pr09 and Pr10) enable you to customize the unit for your monitoring requirements or to restore factory default settings.
he diagram below shows the functions available in the functions menus for the
eries ULF, ULL and ULB. Some functions are only relevant for particular series.
S
sing Series UL Functions
U
he LCD display screen, functioning in "normal" mode, provides continuously
pdated measurement readings. The display screen is also used to view the
u
enu options, function settings and data values, accessed by using the function
m buttons.
The picture below shows the upper part of the unit.
Figure 8: Display and Function Buttons
The function buttons are used to perform various operations, summarized in the
ollowing table.
f
utton
B
Uses Include:
Accessing the functions menu (when pressed
simultaneously with )
Selecting functions
• Progressing to the next step of a function
• Moving from left to right between displayed digits
• Saving changes to data
• Accessing the functions menu (when pressed
simultaneously with )
• Exiting the functions menu to restore the
distance reading
• Moving from right to left between displayed digits
• Exiting a function without saving changes
• Clearing error messages
• Scrolling through the functions menu
• Scrolling through available data values in
functions
• NEXT button only: Recording interfering signals
or
Figure 7: Function Menus
Setting flow measurement parameters (function Pr00) for the Series ULF (Open Channels) is described in Chapter 4, Open Channels (ULF). Setting parameters for all other functions and accessing the functions are described in this chapter.
NOTE: Within some functions, the digits in the displayed value can be individually modified. This is indicated by a flashing digit (flashing digits are shown in gray in the display illustrations. In this case, the ENT and ESC buttons enable you to move between the digits. Each flashing digit can be modified using the BACK and NEXT buttons.
Start Up and Function Access:
Page 5
Press/Action
Connect unit to power supply
After a brief pause
and
(simultaneously)
or
Display:
For example:
For example:
Explanation
Temporary display while unit takes a reading.
Distance reading.
Enters the functions menu.
Used to search for the required menu selection.
Accesses the selected function.
OTE: If an error message appears, press the ESC button to return to the
N
ain menu.
m
alues are displayed in feet and inches or meters and centimeters (model
V
ependent).
d
Resetting the Unit
he Pr01 function enables you to do a reset by refreshing the measurement
eading. (Other saved function settings are not changed.) After resetting, the actual
r
eading is displayed on the LCD, and the unit begins to scan (same as in turning
r
he unit on/off).
t
The reset function may sometimes be required after changing one of the settings or after receiving an error message.
OTE: During reset the unit will display 8.8.8.8 followed by 22 mA current output.
N
To Reset The Unit:
Press/Action
and
(simultaneously)
fter a brief pause
A
and
simultaneously)
(
Display
or example:
Explanation
Required menu selection.
Temporary display while unit takes a reading.
Distance reading.
Returns to the functions menu.
efining Interfering Signals
he Pr03 function enables you to locate and store up to six interfering signals (false
choes) in the unit’s memory to avoid having obstructions, such as a tank agitator
e or a sidewall, interfering with the measurement of the contents. Defining interfering signals is done while the tank is empty.
Each reading (scan distance) taken using the Pr03 function is stored as an interfering signal, until a reading is achieved that indicates the real echo. If six interfering signals are already stored, the next read values will not be saved.
OTE: The reading of the actual target height may not be exact, for example, a
N
arget height of 19.69 ft (6 m) may give a reading in the range 19.62 to 19.75 ft (5.98
t to 6.02 m).
The displayed values are in distance units.
D
igure 9: Scan Distance Process
Use Pr02 function to enter the distance from sensor face to empty level of the tank. When sensor face coincides with tank top, enter the height of the tank. Default value is the maximum range for your model. If you enter a value that exceeds this highest value, an Err error message is displayed and the value is not saved.
NOTE: For flow measurements, enter the precise distance from the sensor to the bottom of the flume.
Modified to read between 0 and 5 (feet) U.S. Standard Units or between 0 and 1 (meters) metric units (model dependent).
To Enter Tank Height Value:
Press/Action
Entering Distance to Empty Level (Tank Height)
Display
For example:
or
or
OR
Explanation
Required menu selection.
Indicates the measurement unit in feet (F) or meters (M) (upon request).
Displays last saved tank height or default value (maximum value in range).
Used to enter a new value.
To save the new value, press when standing on the far right digit. After YES is displayed, the display returns to the functions menu. To return to the main menu without saving, press when standing on the far left digit.
To Define Interfering Signals:
Press/Action
or
After a brief pause
NOTE: If the value represents an interference, false echo or false target: press NEXT. If the value represents the real target, real distance: press ENT.
Display
For example:
For example:
Explanation
Required menu selection.
Select Search to locate acoustic interferences, or Clear to delete stored interferences.
Displayed after the selection for 3 seconds and then the menu returns to Pr03. Temporary display while the unit searches for interfering signals.
Depth to interfering signal.
Saves the interfering signal, then searches again and displays the next reading. Continue to press this button to save up to six interference readings. Actual target height reading indicates that there are no more interfering signals. Saves the entered values.
Page 6
onfiguring 4 mA Current Output
C
r04 function enables you to enter values to be used as the 4 mA mark for remote
P
onitoring. You can define the 4 mA values for level, distance or flow
m measurements (depending on series). The measurement value types should be defined in Pr04. These definitions will be applicable as well for the 20 mA values defined in Pr05.
o set 4 mA and 20 mA for level measurements you should configure Pr04 and
r05 for level values.
P
or example, if we measure a tank with tank height configured for 16.4 ft (5.0 m),
hen setting 4 mA and 20 mA for distance measurements, 4 mA values will
W
epresent the minimal distance between the surface of the target and the sensor,
r and 20 mA values will represent the maximal distance between the sensor and the surface of the target. Therefore, 4 mA represents the full part of the tank and 20 mA represents the empty part of the tank.
Press/Action
or
or
isplay
D
For example:
For example:
Explanation
Required menu selection.
elect the format for 4 mA and 20 mA
S
alues to level (L000), distance (d000)
v or flow (F000) (depending on model).
Last saved 4 mA level or zero default value.
Used to enter a new value.
onfiguring 20 mA Current Output
he Pr05 function enables you to enter values to be used as the 20 mA mark for
emote monitoring.
r
To Enter 20 mA Values:
P
NOTE: The type of measurement (level, distance or flow) selected in Pr04 is also
applicable for Pr05.
The values for 4 mA and 20 mA must be different; otherwise an Err (error message) is displayed.
C
ress/Action
r
o
r
o
R
O
isplay
D
or example:
xplanation
E
equired menu selection.
R
ast saved 20 mA level or default value
L
maximum value in range).
(
Used to enter a new value.
o save the new value, press when
tanding on the far right digit. After YES
s
s displayed, the display returns to the
i functions menu.
o return to the main menu without
aving, press when standing on the
s
ar left digit.
f
or
To save the new value, press when standing on the far right digit. After YES is displayed, the display returns to the functions menu. To return to the main menu without saving, press when standing on the far left digit.
NOTE: The values for 4 mA and 20 mA must be different, otherwise an Err (error message) is displayed.
The values for 4 mA and 20 mA should not be greater than the value used for the tank height (Pr02). Because of the dead-zone (blind zone), the distance between the sensor and the surface of the target at its highest level should be a minimum of
0.82 ft (0.25 m) for ULB Standard Range as well as the ULL and ULF Short Range models. There should be a 1.96 ft (0.6 m) minimum distance for the ULB Extended Range as well as the ULL and ULF Standard Range models.
The first digit of the 4 mA value can be modified to read between 0 and 5 (feet) for U.S. Standard Units or between 0 and 1 (meters) metric units (upon request). After accessing the Pr04 function, the unit generates a fixed current of 22 mA on the 4 to 20 mA line. When the unit reverts to regular scanning mode, the 4 to 20 mA line returns to regular functioning.
The default measurement values for 4 mA and 20 mA in both the ULB and ULL models are level.
The default measurement values for 4 mA and 20 mA in ULF Open Channel Series are flow. When changing from one measurement mode to another, the measurement units will be changed automatically (for example, when changing from (F) feet to (M) meters, the units will change from feet to GPM or meters to M3/H (depending on the model).
The values for 4 mA and 20 mA should not be higher than the value used for the tank height (Pr02).
The first digit of the 20 mA value can be modified to read between 0 and 5 for U.S. Standard Units or between 0 and 1 for metric units (model dependent).
After accessing the Pr05 function, the unit generates a fixed current of 22 mA on the 4 to 20 mA line. When the unit reverts to regular scanning mode, the 4 to 20 mA line returns to regular functioning.
Please refer to Chapter 5 Troubleshooting for 22 mA error indications.
The measurement mode selected for the 4 to 20 mA values will not influence the measurement mode selected for the display (Pr08). In case of power rest, measurement configuration (level, distance, flow) will be saved according to the unit's last configuration.
Page 7
electing Low/High Dynamic Speed (ULF and ULL Series Only)
S
he Pr06 function enables you to choose the required speed level. There are two
ettings available:
s
• SE 0: Low dynamic mode (default setting). This mode provides slower readings with a greater degree of accuracy (rate of up to 31˝/80 cm per min).
• Fail-Safe: 10 minutes.
SE 1: High dynamic mode. This mode provides faster readings but with less
recision (rate of up to 39˝/100 cm per min).
p
Fail-Safe: 3 minutes.
NOTE: Fail-Safe timer determines the waiting period from an echo loss until a transmission of an error signal.
o Select the Speed Mode:
ress/Action
P
isplay
D
xplanation
E
equired menu selection.
R
o Define a Working Area:
Press/Action
r
o
Display
For example:
Explanation
Required menu selection.
isplayed when entering the function.
D
Displays the value last saved in the tank height (default). The entered value
hould not be more than double the tank
s
eight and should not exceed the unit's
h
aximum measuring range.
m
sed to enter a new value.
U
Displays the current
peration mode setting.
r
o
r
o
The Pr07 function allows you to add distance range that exceeds the tank's height, thus enabling accurate readings of complicated tank shapes with conic ending. This may be required when the vessel has a conical bottom shape, which is causing false echoes and consequently faulty measurements. The minimal value can be the entered tank height and the maximal value can be double the value of the entered tank height. The default setting is the entered tank height.
Defining Working Area
o
Used to toggle between the operations modes.
aves the selected
S operation mode.
or
Saves the entered value.
Used to move on to the next function.
r
o
electing Distance or Level Display
The Pr08 function enables you to choose whether the unit displays either distance or level measurements. There are two settings available:
d000: Distance mode (default setting): In this mode, the unit displays the distance
L000: Level mode: In this mode, the unit displays the level of the contents from
NOTE: The measurement mode selected for the display will not influence the measurement mode selected for the 4 to 20 mA values (Pr04).
To Select Distance or Level Display:
S
from the sensor to the surface of the contents.
the bottom of the tank.
Press/Action
Display
or
Explanation
Required menu selection.
Displays the current distance/level mode setting.
Figure 10: Defining Working Area
NOTE: It is recommended to use the Pr07 function only in distance mode.
Used to toggle between the modes.
or
Saves the selected mode.
Page 8
ntering Factor for Gas Compensation
E
unction Pr09 enables you to compensate for sound velocity changes in different
ypes of gasses. You can enter the appropriate factor for each type of gas listed on
t the “Gas Factor Table” (Appendix A). For example, the sound velocity in air (at room temperature) is 1125 ft/sec (343 m/sec) and for Methane (Ch (445.82 m/sec). Therefore, a factor of 1463/1125 = 1.30 should be entered to
ompensate for this type of gas. This factor will compensate in cases when the gas
c
ompound consists of 100% Methane. In case the gas is not pure, the sound
c
elocity cannot be estimated and therefore a minor deviation could appear. It is
v
ecommended to use a reference measurement indicator (using a tape or other
r
) 1463 ft/sec
4
measuring device) and compare the measurement results between the unit and the reference measurement indicator. If the result is correct, press ENT. If the accuracy deviation is higher than expected, continue and calibrate the factor to meet the gas
aintained in the vessel. For example, if the gas composition consists of water and
m
as, you can add ± 0.01 to the factor figure already entered to meet your
g
pplication requirements.
a The “Gas Factor Table” supports up to 32 different types of gasses. For any other type of gas, not included in this table, please contact Dwyer Customer Support, (www.dwyer-inst.com).
ress/Action
P
isplay
D
xplanation
E
equired menu selection.
R
Default screen.
efault value.
D
Choose a factor from the “Gas Factor Table” (Appendix A).
or
or
For example:
This is the factor for Ethanol.
Saves the chosen gas factor.
NOTE: Repeat this procedure if the measurement results differ from the actual material level measured with a reference tape (or other reference measurement method). Add or reduce 0.01 to calibrate the factor figure already entered. Updated on-screen results may take a few seconds to appear.
hifting the Blocking Distance (SBD)
S
his function enables you to define an area in which measurement results would
e ignored. This option is applicable for installations requiring extension pipes or
b
ozzles positioned above the material level. This area should approximately fit the
n pipe/nozzle length to eliminate false echoes and to provide accurate and stable measurement readings.
To Shift the Blocking Distance:
ollow the directions given for Entering Distance to Empty Level (Tank Height),
age 6. Instead of entering the tank height value, enter 00.01, and continue as
p
ollows:
f
ress/Action
P
isplay
D
xplanation
E
nsert this code to enter the blocking
I
istance area.
d
This message will flash for a few seconds, indicating an entry to the blocking distance area.
or example:
r
o
r
o
OTE: Shifting of the blocking distance is limited to 4.9 ft (1.5 m). The value
N
ntered to the SBD incorporates the dead zone (blind zone) Value.
e
hifts the blocking distance to 2.46 ft
S
0.75 m).
(
aves this entry and returns to Pr02.
S
Pr10 (Clear) reverts the blocking distance to its default.
Echo received from the defined blocking distance area will be ignored by the unit and the measurement result will be based on the next echo.
When installing via extension pipe, it is recommended to keep approx. 2˝ (5 cm) gap between the shortest distance to target (maximal level) and the lower pipe edge. Set the SBD length to a value that is 2˝ (5 cm) smaller than the distance from the sensor's lower edge to pipe's lower edge, in order to avoid second harmony interference.
Verifying the Version Number
In addition to the functions described, you can verify the UL series version number.
The Pr10 function allows clearing all user-defined settings and reverting to the
Restoring the Default Settings
default factory settings.
Default factory settings are:
Pr00: GPM 1U01 or M³/Hr 1E01 Pr02: Sbd 00.00, E000, Tank Height =default Pr03: Resets all interfering signals Pr04: Solid/Liquid device L000, 00.00 or
Flow device F000, 00.00
Pr05: Solid/Liquid device Tank Height = Pr02
Flow device 55500 M³/Hr or 244400 GPM Pr06: SE 0 (Liquid and Flow) Pr07: Tank Height = Pr02 Pr08: Solid/Liquid device d000 Pr09: 01.00
NOTE: If you decide not to revert to the default settings, press ESC when CLCL is displayed. A redo option is not available when ENT has been pressed.
To Restore the Default Settings:
Press/Action
Display
Explanation
Required menu selection.
Reverts all settings to default factory settings.
• To Verify the Version Number:
Follow the directions given for Entering Distance to Empty Level (Tank Height), page 6. Instead of entering the tank height value, enter 00.17, and continue as follows:
Press/Action
Display
Explanation
After a brief pause
Displays the version number.
Page 9
efining 22 mA Signal Error Messages
D
he unit allows you to define if the following signal error indications: Near Zone and
ost Echo, will be active when the current output reaches 22 mA. The default
L
etting enables 22 mA analog current and error messages to appear on its LCD
s display.
hapter 4: Open Channels (ULF)
C
his section describes how to set flow measurement parameters for open channels
nd explains the flume/weir codes methodology used when setting up flow
a
easurements.
m
Near Zone - Whenever the distance is below the defined Dead Zone (depending
n the series you are using) message will be displayed on the LCD.
o
ost Echo - Whenever the echo is lost, or in cases when the measurement results
xceed the tank height or when a returned echo is not received, message will
e be displayed on the LCD.
You can choose to enable or disable these error messages and 22 mA analog
ignal as follows:
s
d000: Disable
E000: Enable (default setting)
Refer to Chapter 5, Troubleshooting for a detailed list of the 22 mA signal error messages.
To Disable/Enable 22 mA Signal Error in the Unit:
ollow the directions given for Entering Distance to Empty Level (Tank Height),
age 6. Instead of entering the tank height value, enter 00.16, and continue as
p follows:
Press/Action
Display
xplanation
E
hoose disable.
C
Used to toggle between the modes.
r
o
Disables the 22 mA error messages.
NOTE: When the error signals are disabled the following current outputs will be displayed: (Level or flow measurement): will indicate 20 mA and will indicate 4 mA. (Distance measurement): will indicate 4 mA and will indicate 20 mA.
Selecting the Flow Measurement Settings
he Pr00 function enables you to select one of the preset flumes/weirs settings for
low measurements. This function is available only in the ULF Open Channel
f
eries. When setting flow measurement parameters in the Pr00 function, the
s
lume/weir type value (X) is entered first, followed by the letter (U) or (E) that
f represents either American (USA) or European standard flume/weir. The code value (YY) represents the appropriate flume/weir dimensions in the following format: . The open channel types and codes are described in Open Channels
low Measurement.
OTE: Refer to Chapter 3, Setting Up and Calibrating the Unit, for an explanation
N
of accessing and using the functions menu.
All flow measurement values are displayed divided by 1000.
To Select the Flow Measurement Settings:
Press/Action
isplay
D
xplanation
E
Required menu selection.
For example:
Indicates the measurement unit for flow in GPM (American standard) or M
3
/h
(metric standard) (upon request).
Displays last saved flow measurement
etting or default value, with first digit
s
lashing U – American standard or E –
f
uropean standard (upon request).
E
Use to select a new type value (X).
or
Last two digits of the display flash.
Use to select a new flume/weir length code (YY).
or
Selected values are saved.
Open Channels Flow Measurements
The flume/weir type code methodology used when setting up open channels is based on three digits: X(U/E)YY
Where: X refers to the particular flume/weir type U/E refers to either American or European standard flumes/weirs YY refers to the specific flume/weir dimensions
The types of flumes/weirs are available in American standard or European standard (upon request). When working in American standard the default flow measurement units will be GPM, and in European standard the default flow measurement units will be M³/Hr.
Page 10
lume/Weir Types
his is the first value (X) entered for the Pr00 function. The following flume/weir
ypes are available both in European and American standard:
t
uropean Standard
Flumes/Weirs - European Standard
ectangular Suppressed
R
1
harp-Crested Weir, Page 11
S Rectangular Contracted Sharp-
2
Crested Weir, Page 11 Trapezoidal (Cipolletti) Sharp-
3
rested Weir, Page 11
C
-notch (Triangular) Sharp-
V
4
rested Weir, Page 11
C
hafagi-Venturi Flume, Page 12
K
5
Parshall Flume, Page 12
6
Palmer Bowlus Flume
7
rapezoidal Throat Cross-
election, Page 12
S
Flume, Page 12
H
8
Neyrpic Venturi Flume/Long-
9
Base Weir, Page 13
E
ages 11-13
P
ype (X)
American Standard
ages 13-14
P
ectangular Suppressed Sharp-
R
rested Weir, Page 13
C
ectangular Contracted Sharp-
R Crested Weir, Page 13 Trapezoidal (Cipolletti) Sharp­Crested Weir, Page 13
-notch (Triangular) Sharp-Crested
V
eir, Page 13
W
arshall Flume, Page 14
P
almer Bowlus Flume Trapezoidal
P Throat Cross-Selection, Page 14 H Flume, Page 14
eopold-Lagco Flume,
L
age 14
P
Rectangular Suppressed Sharp-Crested Weir (Type 1)
Code (YY)
Figure 11: Rectangular Suppressed Sharp-Crested Weir
Rectangular Contracted Sharp-Crested Weir (Type 2 )
Code (YY)
Crest Length (cm)
1
0
2
0
3
0 04 05 06 07 08
Crest Length (cm)
01 02 03 04 05 06 07 08 09 10
20 40 60
8 1 1 200 300
20
30
40
50
60
80 100 150 200 300
0 00 50
Trapezoidal (Cipolletti) Sharp-Crested Weir (Type 3)
ode (YY)
C
Figure 13: Trapezoidal (Cipolletti) Sharp-Crested Weir
V-Notch (Triangular) Sharp-Crested Weir (Type 4)
Code (YY)
rest Length (cm)
C
1
0
2
0 03 04 05 06 07 08
V-Notch Angle (°)
01 02 03 04 05 06 07
British Standard
08 09 10
3 4 60
80 100 150 200 300
53.8
28.4
22.5
22.5
0 5
90 60
45 30
90 45
Figure 12: Rectangular Contracted Sharp-Crested Weir
Figure 14: V-Notch (Triangular) Sharp-Crested Weir
Page 11
hafagi-Venturi Flume (Type 5)
K
C
igure 15: Khafagi-Venturi Flume
Parshall Flume (Type 6)
Code (YY)
ode (YY)
1
0
2
0
3
0 04 05 06
7
0
8
0
9
0
01 02 03
4
0
5
0 06 07 08 09 10 11 12 13 14 15
Flume Type
QV 302 QV 303
V 304
Q
V 305
Q
V 306
Q
V 308
Q QV 310 QV 313 QV 316
hroat Width (in)
1 2 3 6
9 12 18 24 36 48 60 72 96
120 144
0 (cm)
1 3 40 50 60
8 1 1 1
almer Bowlus Flume Trapezoidal Throat Cross-Selection (Type 7)
P
01
2
0
3
0
4
0 05 06 07 08
Code (YY)
Flume Size (ft)
2 0
0 00 30 60
igure 17: Palmer Bowlus Flume Trapezoidal Throat Cross-Selection
Flume (Type 8)
H
Code (YY)
onduit Diameter (in) D
C
01
2
0
3
0
4
0
5
0 06 07 08
9
0
0
1
0.5
0.75
1
2.5
4.5
Measurement Point (cm)
1 .5 2
3
6 8
10
2
1
5
1
8
1
1
2 24 27 30
5 7 9
4
1 18 23 28 41
Figure 16: Parshall Flume
Figure 18: H Flume
Page 12
eyrpic Venturi Flume/Long-Base Weir (Type 9)
N
ode (YY)
C
igure 19: Neyrpic Venturi Flume
Code (YY)
Figure 20: Long-Base Weir
Flumes/Weirs - American Standard
Rectagular Suppressed Sharp-Crested Weir (Type 1)
Code (YY)
Venturi Flume Type
01 02 03
4
0
5
0
6
0
7
0 08 09
ong Base Weir Type
10 11 12
3
1
Crest Length (in)
01 02 03 04 05 06 07 08 09
253AX
1
253AY
1
253AZ
1
253A
1 1253B 1253C 1253D
253E
1
253F
1
1 1 1245C 1245D
12.00
18.00
24.00
30.00
36.00
48.00
60.00
72.00
96.00
245A 245B
ectangular Contracted Sharp-Crested Weir (Type 2)
R
ode (YY)
C
Figure 22: Rectangular Contracted Sharp-Crested Weir
Trapezoidal (Cipolletti) Sharp-Crested Weir (Type 3)
Code (YY)
1
0
2
0
3
0 04 05 06
7
0
8
0
9
0
01 02
3
0
4
0
5
0 06 07 08 09
Crest Length (in)
12.00
8.00
1
4.00
2
0.00
3
6.00
3
48.00
60.00
72.00
6.00
9
Crest Length (in)
12.00
18.00
4.00
2
0.00
3
6.00
3
48.00
60.00
72.00
96.00
Figure 21: Rectangular Suppressed Sharp-Crested Weir
Figure 23: Trapezoidal (Cipolletti) Sharp-Crested Weir
V-Notch (Triangular) Sharp-Crested Weir (Type 4)
Code (YY)
01 02 03 04 05
Figure 24: V-Notch (Triangular) Sharp-Crested Weir
Page 13
V-Notch Angle (°)
90 60 45 30
22.5
arshall Flume (Type 5)
P
Code (YY)
0 0 0 0 05 06 07 0 0 1 1 12 13 14 1 1
igure 25: Parshall Flume
Palmer Bowlus Flume Trapezoidal Throat Cross-Selection (Type 6)
Code (YY)
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
hroat Width (in)
1 2 3 4
8 9 0 1
5 6
1 2 3 6
9 1 1 2 30 36 48 6 7 9
20
1 144
Conduit Diameter (in) D
2 8 4
0 2 6
4 6
8 10 12 15 18 21 24 27 30 36 42 48 60 72
Flume (Type 7)
H
Code (YY)
eopold-Lagco Flume (Type 8)
lume Size (in)
01
2
0
3
0
4
0
5
0 06 07 08
Figure 28: Leopold-Lagco Flume
Measurement Point (in)
6
9 12 18 24
0
3
6
3
4
5
Figure 27: H Flume
Code (YY)
01 02 03 04 05 06 0 0 0 10
11 12 13 14 15 16 17
7 8 9
rest Length (in)
C
1.96
2.75 .54
3
.51
5
.08
7
.05
9
11.02
16.14
4 6
8 10 12 15
8
1
1
2
4
2 30 36 42 48 54 60 66 72
Figure 26: Palmer Bowlus Flume Trapezoidal Throat Cross-Selection
Page 14
hapter 5 Troubleshooting
C
his chapter describes how to resolve problems that may occur when calibrating
he unit as follows:
t
Error
escription
D
1. Noise in area. (Indicated by 22 mA if the Error Signals are Enabled).
. Inappropriate power
2
upply/no grounding.
s
aulty power supply.
ensor disconnected.
S
ny combination of three 8s and
A one 1: Indicates an electrical shortage caused by depressing the buttons for too long.
ppears for several seconds
A after restarting the unit. If it is displayed for more than several seconds, it may be due to one of the following:
Power supply voltage is too
low
• Load resistor resistance is too
high or unnecessary
A random pulse that causes
he unit to automatically restart
t
easurement value is greater
M than 9999.
In flow mode, appears when the entered tank height is incorrect.
olution
S
. Get away from noise source.
1
. Check that the power supply is
2
ppropriate/ check grounding
a connection.
Make sure that the power supply
orresponds with the specifications
c
escribed in Chapter 2, Installing
d
he Unit. If the problem persists,
t
eplace the power supply.
r Contact Dwyer Technical Support.
Contact Dwyer Technical Support.
Make sure that the power supply corresponds with the specifications described in Chapter 2, Installing the Unit. If the problem persists,
eplace the power supply.
r
Double check the unit configuration (Tank h, type of flume, 4 to 20 mA settings.) Decrease the tank height value.
2 mA Signal Error Messages
2
he following list of messages will appear on the display and coincides with a 22
A analog current error output signal (when the error signals messages are
m
nables):
e
Error
escription
D
ensor disconnected.
S
Near dead zone (blind zone). (Depends on the measurement
efinitions).
d
ank empty. (Depends on the
easurement definitions).
m
. Noise in area.
1
(indicated by 22 mA if the error signals are enabled).
2. Inappropriate power supply/ o grounding.
n
aulty power supply.
indicated by 22 mA if the error
( signals are enabled).
Solution
ontact Dwyer Technical Support.
C
ove the sensor farther from the
M
ead zone (blind zone) area.
d Check the level of material in the tank.
1. Get away from noise source. . Check that the power supply is
2
ppropriate/check grounding
a
onnection.
c
Make sure that the power supply corresponds with the specifications described in Chapter 2, Installing
he Unit. If the problem persists,
t
replace the power supply.
Page 15
ppendix A
A
ppendix B
A
as Factor Table
G
he following table contains 32 different types of gasses and their factor for
actor
.62
0
.63
0
0.74
0.54
0.99 .26
1
.92
0
.53
0
.41
0
0.37
0.56
0.77 .01
1
.38
0
.68
0
0.71
0.90
0.71
0.95 .93
2
.79
3
0.89 .62
0
.29
1
.71
0
1.30
1.01
0.63
1.02
0.72
0.61
0.57
ymbol
S
C
2h4o2
C3h6o C
o
2h4
C
2h3c1
C
2h2
H3n
r
A C
6H6
Br
2
Cbrclf
H
C
C
3
O
C
2
O
C CCI
4
Cl
2
C2h6o C
2h6
C2h6o C
2h4
e
H H
2
H2S C
o
3h8
H
C
4
Ch6n Ne N
2
CH3NO O
2
C3H
8
C3H8O C
4H8
o
2
OCH
2
O
2
Gas
Acetic Acid
cetone
A
cetaldehyde
A
cetyl Chloride
A
cetylene
A Ammonia Argon Benzene
romine
B
romochlorodifluoromrthane
B
utanone
B
H
C
2
3
Carbon Dioxide Carbon Monoxide Carbon Tetrachloride Chlorine Dimethyl Ether
thane
E
thanol
E
thylene
E Helium Hydrogen
ydrogen Sulfide
H Isopropyl Alcohol Methane Methyl Hydrazine Neon
itrogen
N
itromethane
N Oxygen Propane Propanol Tetrahydrofuran
nstallation Tips
I
istance to tank walls
D
urface
S Acoustic noises
Electrical interference
ank installation
ank installation
Sensor
Extension pipes (1)
xtension pipes (2)
E
Extension pipes (3)
Voltage
A battery
ipple and noise
R Type
Rechargeable supply
PLC Connections
Barrier
Tank Height, Level/Distance 4 to 20 settings
5 cm margin
Scan distance (1)
Scan distance (2)
Scan distance (3)
SBD (1)
SBD (2)
1) Choosing Location
ust Be
M
ust Be
M Must Be
t least 19.69˝ (50 cm) from
A
alls + 3.94˝/3.28 ft (10 cm/1
w
) range.
m
ixed on a horizontal surface.
Must Be
ust Be
M
ust Be
M
Shielded away from power
nd sensor cables.
a
ar away from tank inlets,
utlets, physical obstacles.
o
ar away from tank inlets,
Must Be
Exactly perpendicular to the surface of the target.
2) Handling Dead Zone
Must Be
Must Be
At least 3˝ (7.62 cm) internal
iameter and 19.69˝ (50 cm)
d
ong (from sensor low edge to
l
ipe low edge).
p With completely smooth interior surface.
Must Be
) Power Source
3
Must Be
Installed with a flange/not
rotruding into the tank.
p
At least 12 VDC on unit terminals.
Must Be
Rated higher than 12 volts due to normal voltage drop.
ot exceeding 100 mV.
ust Be
M Must Be
N Preferably regulated switching PS (avoid rectified PS).
Must Be
Non operational when switched to recharge.
4) 2-Wire Interface
Must Be
As specified in the user manual, preferably grounded.
Must Be
Connected in EX zones, grounded.
5) Configuration
Must Be
Must Be
Configured correctly.
Defined (consider the extension pipe).
Must Be
Kept between pipe low edge and full level.
Must Be
Preferably be executed in all applications.
Must Be
Executed when the tank is empty.
Must Be
Performed after the old stored data is cleared.
Must Be
Set up in flange and extension pipe installations.
Must Be
At least 1.97˝ (5 cm) before the pipe edge.
Page 16
ppendix C
A
igure 29: Nomenclature
MAINTENANCE/REPAIR
Upon final installation of the Series UL, no routine maintenance is required. The Series UL is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty).
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog or on our website. Contact customer service to receive a Return Goods Authorization number before shipping your product back for repair. Be sure to include a brief description of the problem plus any relevant application notes.
Page 17
©Copyright 2013 Dwyer Instruments, Inc. Printed in U.S.A. 6/13 FR# R4-443852-00 Rev. 3
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Loading...