Bulletin E-90-TSX
Series TSX Temperature Digital Controller
Specifications - Installation and Operating Instructions
(3.000)
BLUE BUTTONS
(2.375)
(1.338)
(1.100)
The Series TSX are designed for refrigerating or cooling applications. It has two inputs for temperature probes type PTC or NTC
(selectable by parameter). The probe temperature is displayed on
the bright 3-digit display. The user is able to program 23 different
parameters including set point, hysteresis, defrosting time and
ambient probe adjustment using the silicone front keypad. The
configuration key input allows easy programming of the parameters. The unit features error warning and password protection.
Select between red or green display color, temperature display in
°C or °F and 115 VAC, 230 VAC, 24 VAC/DC or 12 VAC/DC
power supplies.
INSTALLATION
NOTE: Unit must be mounted away from vibration, impacts, water
and corrosive gases.
• Cut hold in panel 71 x 29 mm (2.80 x 1.14 inches)
• Apply silicone (or rubber gasket) around the perimeter of
the hold to prevent leakage.
• Insert unit into hole of panel.
• Slide removable fitting clips onto unit from the back until
secure to panel.
• Wiring diagram is displayed on the top of the unit.
• Note: DO NOT INSTALLPROBECABLENEARPOWER
CABLES.
MAINTENANCE, CLEANING, AND REPAIR
After final installation of the unit, no routine maintenance is
required.
Clean the surface of the display controller with a soft and damp
cloth. Never use abrasive detergents, petrol, alcohol or solvents.
Upon final installation of the Series TSX Temperature Digital
Controller, no routine maintenance is required. A periodic check of
the system calibration is recommended. The Series TSX is not
field serviceable and should be returned if repair is needed (field
repair should not be attempted and may void warranty). Be sure
to include a brief description of the problem plus any relevant
application notes. Contact customer service to receive a return
goods authorization number before shipping.
SPECIFICATIONS
Probe Range:
PTC: -58 to 302°F (-50 to 150°C);
NTC: -58 to 230°F (-50 to 110°C).
Input: PTC/NTC thermistor 1000Ω @ 25°C.
Output: 16A SPST relay @ 250 VAC resistive, 5A inductive;
Dual output units also have one 8A SPDT relay @ 250 VAC
resistive, 3A inductive.
Horsepower Rating (HP): 16A: 1HP 240 VAC - 10FLA, 60LRA
250 VAC.
Control Type: ON/OFF.
Power Requirements: 110 VAC; 230 VAC; 24 VAC/DC; 12
VAC/DC (depending on model).
Accuracy: ±1% FS.
Display: 3-digit, red, 1/2˝ (12.7 mm) digits.
Resolution: 0.1° (<100°); 1° (≥100°).
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 14 to 131°F (-10 to 55°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: IP64.
Agency Approvals: UR pending.
Configuration Key TS2-K Compatible
LOVE CONTROLS DIVISION
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
LIST OF PARAMETERS
Description
SP
Set Point
r0
Differential or Hysteresis
r1
Lower Value for SP
r2
Higher Value for SP
d0
Type of Defrosting
d1
Temperature Defrosting Stop
d2
Defrosting Duration
d4
Delay of First Defrosting
d5
Display on Defrosting
d7
Compressor Drip Time
d8
Defrosting Interval Time
d14
Defrost Counting Mode
c0
Minimum Stopping Time
c2
ON Time of Fault Cycle
c3
OFF Time of Fault Cycle
c4
Minimum ON Time
c5
Minimum Time Between 2 Activations
P1
Ambient Probe Adjustment
P2
Defrosting Probe Adjustment
P4
Number of Probes
H1
Keyboard Protection
H5
Access Code to Parameters
H6
Probe Type
PARAMETER DESCRIPTIONS
SP = Set point. Temperature we wish to regulate the
machine (variable from r1 to r2)
r0 = Differential or hysteresis
r1 = Lower value for SP
r2 = Higher value for SP
d0 = Type of defrosting
rE = Defrosting without connecting compressor
in = Defrosting by connecting compressor
d1 = End of defrosting temperature. When this tempera-
ture is reached the defrosting will end
d2 = Defrosting duration (if d2=0 no defrosting is
performed)
d4 = Time to carry out the first defrosting
d5 = Display during the defrosting
Off = The temperature will be shown real time during
defrosting
On = The temperature at defrost beginning is frozen
on display until the end and until the actual
temperature be equal or lower than initial, or 1 hour elapses
-d- = Label -d- is displayed during defrosting until the
end and the actual temperature be equal or lower
than initial, or 1 hour elapses
d7 = Time since defrosting ends until the compressor can
be connected
d8 = A defrosting cycle is performed every d8 hours (if d8
= 0 no periodic defrosting is performed)
d14 = Defrost counting mode
rt = Controller running hours
ct = Compressor running hours
c0 = Minimum stopping time of the load
c2 = ON time of fault cycle, when ambient probe is broken
c3 = OFF time of fault cycle, when ambient probe is
broken
c4 = Minimum time since the compressor start-up until the
next start-up
P1 = Ambient probe adjustment. If the probe is not place in
the exact point to control use a standard
thermometer to offset the measured temperature
P2 = Defrosting probe adjustment. If the probe is not
placed in the exact point to control use a standard
thermometer to offset the measured temperature
P4 = Number of probes
H1 = Keyboard protection. To modify SET, activate/
de-activate defrosting we have to enter the code and
then quit. The protection disappears momentarily. It
becomes activated again 1 minute after the last key is
pressed.
Units
Degrees
Degrees
Degrees
Degrees
Option
Degrees
Minutes
Minutes
Option
Minutes
Hours
Option
Minutes
Minutes
Minutes
Minutes
Minutes
Degrees
Degrees
Option
Option
Numeric
Option
Range
r1 to r2
1 to 20
-58 to r2
r1 to 302
rE/In
-58 to 302
0 to 59
0 to 999
off/on/-d0 to 999
0 to 24
ct/rt
0 to 59
0 to 999
0 to 999
0 to 999
0 to 999
-10 to 10
-10 to 10
1/2
yes/no
0 to 255
Ptc/ntc
H5 = Access code to parameters (it is set to 0 from
factory)
H6 = Probe Model PTC or NTC
PARAMETER DESCRIPTIONS
Set Point (SP) is the only parameter the user can access
without code protection.
• Press SET.SP text will appear on the display.
• Press SET again. The real value is shown on the display.
• The value can be modified with the UP and DOWN
arrows.
• Press SET to enter any new values.
• Press SET and DOWN at the same time to quit
programming or wait one minute and the display will
automatically exit programming mode.
Access to all code protected parameters.
• Press SET for 8 seconds. The access code value 0 is
shown on the display (unit comes with code set at 0 from
factory).
• W ith the UP and DOWN arrows, code can be set to user
needs.
• Press SET to enter the code. If the code is correct, the
first parameter label is shown on the display (SP).
• Move to the desired parameter with the UP and DOWN
keys.
• Press SET to view the value on the display.
• The value can be modified with the UP and DOWN
arrows.
• Press SET to enter the value and exit.
• Repeat until all necessary parameters are modified.
• Press SET and DOWN at the same time to quit
programming or wait one minute and the display will
automatically exit programming mode.
*The keyboard code can be reset to ZERO by turning off the controller and turning it on again while keeping the SET pressed.
Activating/Deactivating Defrosting
Holding the UP arrow pressed for 8 seconds the defrosting is activated. Repeating this operation the defrosting is stopped. If a cool
cycle is activated the defrosting is disabled.
Default Working
In case of probe error, the control performs a continuous regulation, C2 min. load connected - C3 min. load disconnected. In case
of memory error, the control performs a continuous regulation, 5
min. load connected - 5 min. load disconnected.
LED Indication and Display Messages
The LED OUT indicates if the load is connected or not.
The LED DEF indicates if the control is performing defrosting.
In normal operation, the probe temperature will be shown on the
display. In case of alarm or error, the following messages can be
shown:
• Er = Memory Error
• Ep2 = Defrosting Probe Error
• oo = Open Probe Error
• -- = Short Circuit Probe Error