Dwyer TSX User Manual

Bulletin E-90-TSX
Series TSX Temperature Digital Controller
Specifications - Installation and Operating Instructions
(3.000)
BLUE BUTTONS
(2.375)
(1.338)
(1.100)
The Series TSX are designed for refrigerating or cooling applica­tions. It has two inputs for temperature probes type PTC or NTC (selectable by parameter). The probe temperature is displayed on the bright 3-digit display. The user is able to program 23 different parameters including set point, hysteresis, defrosting time and ambient probe adjustment using the silicone front keypad. The configuration key input allows easy programming of the parame­ters. The unit features error warning and password protection. Select between red or green display color, temperature display in °C or °F and 115 VAC, 230 VAC, 24 VAC/DC or 12 VAC/DC power supplies.
INSTALLATION
NOTE: Unit must be mounted away from vibration, impacts, water and corrosive gases.
• Cut hold in panel 71 x 29 mm (2.80 x 1.14 inches)
• Apply silicone (or rubber gasket) around the perimeter of the hold to prevent leakage.
• Insert unit into hole of panel.
• Slide removable fitting clips onto unit from the back until secure to panel.
• Wiring diagram is displayed on the top of the unit.
• Note: DO NOT INSTALLPROBECABLENEARPOWER CABLES.
MAINTENANCE, CLEANING, AND REPAIR
After final installation of the unit, no routine maintenance is required.
Clean the surface of the display controller with a soft and damp cloth. Never use abrasive detergents, petrol, alcohol or solvents.
Upon final installation of the Series TSX Temperature Digital Controller, no routine maintenance is required. A periodic check of the system calibration is recommended. The Series TSX is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
SPECIFICATIONS
Probe Range:
PTC: -58 to 302°F (-50 to 150°C); NTC: -58 to 230°F (-50 to 110°C).
Input: PTC/NTC thermistor 1000Ω @ 25°C. Output: 16A SPST relay @ 250 VAC resistive, 5A inductive;
Dual output units also have one 8A SPDT relay @ 250 VAC resistive, 3A inductive. Horsepower Rating (HP): 16A: 1HP 240 VAC - 10FLA, 60LRA 250 VAC.
Control Type: ON/OFF. Power Requirements: 110 VAC; 230 VAC; 24 VAC/DC; 12
VAC/DC (depending on model).
Accuracy: ±1% FS. Display: 3-digit, red, 1/2˝ (12.7 mm) digits. Resolution: 0.1° (<100°); 1° (100°). Memory Backup: Nonvolatile memory. Ambient Operating Temperature: 14 to 131°F (-10 to 55°C). Storage Temperature: -4 to 176°F (-20 to 80°C). Weight: 2.3 oz (65 g). Front Panel Rating: IP64. Agency Approvals: UR pending.
Configuration Key TS2-K Compatible
LOVE CONTROLS DIVISION
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
LIST OF PARAMETERS
Description
SP
Set Point
r0
Differential or Hysteresis
r1
Lower Value for SP
r2
Higher Value for SP
d0
Type of Defrosting
d1
Temperature Defrosting Stop
d2
Defrosting Duration
d4
Delay of First Defrosting
d5
Display on Defrosting
d7
Compressor Drip Time
d8
Defrosting Interval Time
d14
Defrost Counting Mode
c0
Minimum Stopping Time
c2
ON Time of Fault Cycle
c3
OFF Time of Fault Cycle
c4
Minimum ON Time
c5
Minimum Time Between 2 Activations
P1
Ambient Probe Adjustment
P2
Defrosting Probe Adjustment
P4
Number of Probes
H1
Keyboard Protection
H5
Access Code to Parameters
H6
Probe Type
PARAMETER DESCRIPTIONS SP = Set point. Temperature we wish to regulate the
machine (variable from r1 to r2)
r0 = Differential or hysteresis r1 = Lower value for SP r2 = Higher value for SP d0 = Type of defrosting
rE = Defrosting without connecting compressor in = Defrosting by connecting compressor
d1 = End of defrosting temperature. When this tempera-
ture is reached the defrosting will end
d2 = Defrosting duration (if d2=0 no defrosting is
performed)
d4 = Time to carry out the first defrosting d5 = Display during the defrosting
Off = The temperature will be shown real time during defrosting On = The temperature at defrost beginning is frozen on display until the end and until the actual temperature be equal or lower than initial, or 1 hour elapses
-d- = Label -d- is displayed during defrosting until the end and the actual temperature be equal or lower than initial, or 1 hour elapses
d7 = Time since defrosting ends until the compressor can
be connected
d8 = A defrosting cycle is performed every d8 hours (if d8
= 0 no periodic defrosting is performed)
d14 = Defrost counting mode
rt = Controller running hours ct = Compressor running hours
c0 = Minimum stopping time of the load c2 = ON time of fault cycle, when ambient probe is broken c3 = OFF time of fault cycle, when ambient probe is
broken
c4 = Minimum time since the compressor start-up until the
next start-up
P1 = Ambient probe adjustment. If the probe is not place in
the exact point to control use a standard thermometer to offset the measured temperature
P2 = Defrosting probe adjustment. If the probe is not
placed in the exact point to control use a standard thermometer to offset the measured temperature
P4 = Number of probes H1 = Keyboard protection. To modify SET, activate/
de-activate defrosting we have to enter the code and then quit. The protection disappears momentarily. It becomes activated again 1 minute after the last key is pressed.
Units
Degrees Degrees Degrees Degrees Option Degrees Minutes Minutes Option Minutes Hours Option Minutes Minutes Minutes Minutes Minutes Degrees Degrees Option Option Numeric Option
Range
r1 to r2 1 to 20
-58 to r2 r1 to 302 rE/In
-58 to 302 0 to 59 0 to 999 off/on/-d­0 to 999 0 to 24 ct/rt 0 to 59 0 to 999 0 to 999 0 to 999 0 to 999
-10 to 10
-10 to 10 1/2 yes/no 0 to 255 Ptc/ntc
H5 = Access code to parameters (it is set to 0 from
factory)
H6 = Probe Model PTC or NTC PARAMETER DESCRIPTIONS Set Point (SP) is the only parameter the user can access
without code protection.
• Press SET.SP text will appear on the display.
• Press SET again. The real value is shown on the display.
• The value can be modified with the UP and DOWN arrows.
• Press SET to enter any new values.
• Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
Access to all code protected parameters.
• Press SET for 8 seconds. The access code value 0 is shown on the display (unit comes with code set at 0 from factory).
• W ith the UP and DOWN arrows, code can be set to user needs.
• Press SET to enter the code. If the code is correct, the first parameter label is shown on the display (SP).
• Move to the desired parameter with the UP and DOWN keys.
• Press SET to view the value on the display.
• The value can be modified with the UP and DOWN arrows.
• Press SET to enter the value and exit.
• Repeat until all necessary parameters are modified.
• Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
*The keyboard code can be reset to ZERO by turning off the con­troller and turning it on again while keeping the SET pressed.
Activating/Deactivating Defrosting
Holding the UP arrow pressed for 8 seconds the defrosting is acti­vated. Repeating this operation the defrosting is stopped. If a cool cycle is activated the defrosting is disabled.
Default Working
In case of probe error, the control performs a continuous regula­tion, C2 min. load connected - C3 min. load disconnected. In case of memory error, the control performs a continuous regulation, 5 min. load connected - 5 min. load disconnected.
LED Indication and Display Messages
The LED OUT indicates if the load is connected or not. The LED DEF indicates if the control is performing defrosting. In normal operation, the probe temperature will be shown on the display. In case of alarm or error, the following messages can be shown:
• Er = Memory Error
• Ep2 = Defrosting Probe Error
• oo = Open Probe Error
• -- = Short Circuit Probe Error
©Copyright 2007 Dwyer Instruments, Inc. Printed in U.S.A. 8/07 FR# R7-443352-00 Rev.2
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com