Series TSF Thermocouple Limit Control
Specifications - Installation and Operating Instructions
The Series TSF Thermocouple FM Approved Limit Control provides
audible alarm status along with a robust 16 amp relay output. Unit allows the user to easily select automatic or manual reset along with 13 other parameters. The TSF series has a built in reset button on the front panel or can accept an external reset.
The ease of programming and low price make the TSF series the best value limit control on the market.
INSTALLATION Note: Unit must be mounted away from vibration, impacts, water and
corrosive gases.
• Cut hole in panel 2.80 x 1.14 inches (71 X 29 mm).
• Use the included gasket, or apply silicone around the perimeter of the hole to prevent leakage.
• Insert unit into the hole in panel, and secure using the included mounting clips.
• Wire the unit per the wiring diagram on the product label or in IOM.
SPECIFICATIONS Probe Range: 32 to 999°F (0 to 700°C) for Type J thermocouple; 32
to 999°F (0 to 999°C) for Type K or S thermocouples.
Input: Type J, K, or S thermocouple. Output: SPDT relay rated 16A @ 240 VAC resistive. Horsepower Rating (HP): 1 HP. Control Type: ON/OFF; manual/automatic reset. Power Requirements: 115 VAC, 230 VAC, 12 VAC/VDC or 24
VAC/VDC (depending on model).
Power Consumption: 4 VA. Accuracy: ±1% FS. Display: 3-digit, red, 1/2˝ (12.7 mm) digits and sign. Resolution: 1°. Memory Backup: Nonvolatile memory. Ambient Operating Temperature: 32 to 150°F (0 to 65°C). Storage Temperature: -4 to 176°F (-20 to 80°C). Weight: 2.3 oz (65 g). Front Panel Rating: IP64. Agency Approvals: CE, FM, UL.
Wiring Diagram
LOVE CONTROLS DIVISION
DWYER INSTRUMENTS INC.
P.O. BOX 338 - MICHIGAN CITY, INDIANA 46360, U.S.A.
* Use ungrounded thermocouples only with 12 VAC/VDC and 24
VAC/VDC models.
Phone: 219/879-8000 www.love-controls.com Fax: 219/872-9057 e-mail:love@love-controls.com
List of Parameters PARAMETER PROGRAMMING
Description
SP
Set Point
r0
Differential or Hysteresis
r1
Lower Limit for SP
r2
Higher Limit for SP
r3
Control Reset
d0
High or low limit control
c0
Minimum stopping time
c2
Output status with probe error
c3
Alarm energize condition
P1
Probe Adjustment
P5
Probe Type
P6
Probe Response
H1
Display Reading
H5
Access code to parameters
Parameter Descriptions SP = Set Point. Temperature we wish to activate relay output. r0 = Differential or hysteresis. r1 = Lower value for SP. r2 = Higher value for SP. r3 = Alarm reset.
Aut = Automatic hoL = Manual PuP = Reset on Power Up
d0 = High or low limit control.
Where TS is the probe input temperature. If d0 = Hi, r3 = Aut, c3 = No:
If TS ≥ SP relay output OFF, buzzer ON, AL displayed. If TS ≤ SP-r0 relay output ON, buzzer OFF, TS displayed.
If d0 = Hi, r3 = hoL, c3 = No:
If TS ≥ SP relay output OFF, buzzer ON, AL displayed. If TS ≤ SP-r0 it waits for reset to turn relay output ON, buzzer OFF,
TS displayed. If d0 = Hi, r3 = PuP, c3 = No: When the device is powered up relay output OFF, buzzer ON, AL displayed.
If TS ≥ SP relay output OFF, buzzer ON, AL displayed.
If TS ≤ SP-r0 it waits for reset to turn relay output ON, buzzer OFF,
TS displayed. If d0 = Lo, r3 = Aut, c3 = No:
If TS ≤ SP relay output OFF, buzzer ON, AL displayed.
If TS ≥ SP+r0 relay output ON, buzzer OFF, TS displayed. If d0 = Lo, r3 = hoL, c3 = No:
If TS ≤ SP relay output OFF, buzzer ON, AL displayed.
If TS ≥ SP+r0 it waits for reset to turn relay output ON, buzzer OFF,
TS displayed. If d0 = Lo, r3 = PuP, c3 = No: When the device is powered up relay output OFF, buzzer ON, AL displayed.
If TS ≤ SP relay output OFF, buzzer ON, AL displayed.
If TS ≥ SP+r0 it waits for reset to turn relay output ON, buzzer OFF,
TS displayed.
c0 = Minimum stopping time of the load. c2 = Output status with probe error. c3 = Energize relay on alarm condition (Determines fail state during
power loss).
Yes = Relay energized during alarm condition, No = Relay de-energized during alarm condition.
P1 = Ambient probe adjustment. P5 = Ambient probe type (tcJ = Type J, tch = Type K, tcS = Type S). P6 = Probe response rate (0 = 8 sec, 1 = 4 sec, 2 = 2 sec, 3 = 1 sec). H1 = Display reading during normal operation (PU = process temp, SP
= set point). H5 = Access code to protected parameters (factory set at 0).
©Copyright 2013 Dwyer Instruments, Inc. Printed in U.S.A. 10/13 FR# 443532-00 Rev. 3
Units
Degrees Degrees Degrees Degrees Option Option Seconds Option Option Degrees Option Numeric Option Numeric
Range
r1 to r2 1 to 99 0 to r2 r1 to 999 Aut/hoL/PuP Hi/Lo 0 to 999 Off/On No/Yes
-30 yp 30 tcJ, tch, tcS 0 to 3 PU/SP 0 to 255
Set Point (SP) is the only parameter the user can access with code protection.
Press SET. SP text will appear on the display.
• Press SET again. The set point value is shown on the display.
• Use the UP and DOWN arrows to modify set point value.
• Press SET to save any new values.
• Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit the programming mode.
Access to all code protected parameters:
• Press SET and hold for 8 seconds. The access code value 0 is shown on the display. With the UP and DOWN arrows, enter the access code (unit comes with access code set at 0 from the factory).
• Press SET to enter the code. If the code is correct, the first parameter label is shown on the display (SP).
Move to the desired parameter with the UP and DOWN arrows.
• Press SET to view the value on the display.
Use the UP and DOWN arrows to modify the parameter value.
Press SET to save the value and exit the parameter.
Repeat until all necessary parameters are modified.
Press SET and DOWN at the same time to quit programming, or wait
one minute and the display will automatically exit programming mode.
NOTICE
depressed.
Reset an alarm:
When the parameter r3 = Aut, the alarm condition will automatically reset once the probe temperature reading returns to non-alarm conditions. When the parameter r3 = hoL, the alarm condition will remain activated until a reset signal is received either by pressing the RST key on the front face of the control or by closing contact to the rear input.
• When d0 = Hi The reset is accepted when the probe temperature TS ≤ SP - r0.
• When d0 = Lo The reset is accepted when the probe temperature TS ≥ SP + r0.
LED indication, buzzer and display messages:
The LED Alarm indicates if the relay output is connected or not. When the relay output is connected the message AL is displayed alternated with the temperature ambient of the probe. In normal operation the probe temperature will be shown on the display. In case of alarm or error, the following messages can be shown:
Erl = memory error ooo = open probe error
--- = ambient temperature out to range
In case of alarm or error the internal buzzer is activated. The buzzer can be silenced by pressing the SET and DOWN arrows at the same time (when a new alarm or error occurs the buzzer will sound again).
MAINTENANCE
Upon final installation of the Series TSF Thermocouple Limit Control, no routine maintenance is required. A periodic check of the system calibration is recommended. The Series TSF is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
Cleaning and Repair:
Clean the surface of the display controller with a soft damp cloth. Never use abrasive detergents, petrol, alcohol or solvents.
he keyboard security code can be reset to ZERO by turning off
T the controller and turning it on again while keeping the SET key
LOVE CONTROLS DIVISION
DWYER INSTRUMENTS INC.
P.O. BOX 338 - MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000 www.love-controls.com Fax: 219/872-9057 e-mail:love@love-controls.com