Dwyer TS2 User Manual

(3.000)
(1.338)
(2.375)
(1.100)
Series TS2 Digital Temperature Switch
250 VAC 16A 30 LRA
Power
Supply
OUTPUT
7
89
10
11
1
2
Probe Input
t
Specifications - Installation and Operating Instructions
ulletin T-TS2
B
DESCRIPTION
Monitor and control temperature for heating and cooling applications with the Series TS2 Digital Temperature Switch. The Series TS2 offers twelve programmable functions to customize the unit to fit application requirements. Use the 16 Amp SPDT relay output to drive a motor, compressor, or fan. Designed with the OEM in mind, the TS2 offers the ability to configure multiple units with the touch of a button.
The TS2 features set point adjustments, static defrost timing, compressor mean time, hysteresis, and ambient probe adjustment. Security protection is offered using a password code. The Series TS2 Digital Temperature Switches are designed to operate with PTC (1000Ω @ 25°C) probes sold separately.
INSTALLATION
The thermostat must be installed by authorized professionals. It should be located in a place free of vibrations, impacts, water and corrosive gases.
A hole measuring 71 x 29 mm must be cut in the panel where the thermostat is to be fitted (apply silicone to make it leaktight). Then, the fixing cups must be fitted, sliding them onto the thermostat until secure. Do not force tightening of the screw if the U-brackets are used. The connections must be covered with the rear cover for this.
WIRING INSTRUCTIONS
Avoid installing the probe’s cables in proximity with any power cable. If the length of the probe cables measures more than 100 meters, a recalibration adjustment must be made (parameter P1).
SPECIFICATIONS Probe Range: -58 to 302°F (-50° to 150°C). Input: PTC thermistor 1000Ω @ 25°C. Output: SPDT relay rated 16A @ 240 VAC resistive. Horsepower Rating (HP): 1 HP. Control Type: ON/OFF. Power Requirements: 115 VAC, 230 VAC, 12 VAC/VDC or 24 VAC/VDC
(depending on model).
Accuracy: ±1°C. Display: 3-digit, Red, 1/2˝ digits. Resolution: ±1 digit. Memory Backup: Nonvolatile memory. Ambient Operating Temperature: 14 to 158°F (-10 to 70°C). Storage Temperature: -4 to 176°F (-20° to 80°C). Weight: 2.3 oz (65 g). Agency Approvals: CE,cURus.
FRONT OPERATION PUSH BUTTONS
Pushing SET once gives access to the SP. Pushing for 8 seconds gives way to the requested code. After entering the correct code, all parameters are accessible. This button alternates between text parameters and their value. It validates the modified parameters. When pressed with DOWN, it exits parameter programming.
Pressing this arrow allows the user to go to the next parameter or increase the value viewed on the display. When pressed for 8 seconds, it activates or deactivates defrosting.
Pressing this arrow allows the user to go to the previous parameter or decreases the value viewed on the display. When pressed for 8 seconds, it activates or deactivates the continuous cooling cycle. When pressed simultaneously with SET, it exits the programming mode.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyermail.com
Phone: 219/879-8000 www.dwyer-inst.com
PROGRAMMING PARAMETERS
exits
Access only to Set Point SP (without code protection):
• Press and release SET. SP text appears on the display.
• Press SET again. The real value is shown on the display.
• Modify the value using the UP and DOWN keys.
• Press SET to store the new SP value.
• Press SET and DOWN to quit programming, or wait 1 minute for the controller to TIMEOUT.
Access to all parameters (code protected):
• Press SET for 8 seconds. The access code value 00 is shown on the display.
• Using the UP and DOWN buttons, select the code (factory-set code is
00).
• Press SET to enter the code. If it is correct, the first parameter label will be shown on the display (SP).
• Move to the desired parameter with the UP and DOWN keys.
• Press SET to see the value.
• Modify the value with the UP and DOWN keys.
• Press SET to enter it, and exit to next parameter.
• Press SET and DOWN to quit programming, or wait 1 minute for the controller to TIMEOUT.
SETTING THE KEYBOARD CODE TO ZERO
PARAMETERS
PARAMETER DESCRIPTIONS SP = Set Point. Temperature wished to regulate the machine. Can vary
from r1 to r2.
r0 = Differential
For heating control if temperature is > SP then output is OFF. When the temperature drops to <SP - r0 the output is ON.
For cooling control if temperature is < SP then output is OFF. When the
temperature increases to > SP + r0 the output is ON.
r1 = Lower Set Point Limit r2 = Higher Set Point Limit d0 = Heat or Cooling Control. Ht = heating control, Co = cooling control. d2 = Defrosting Time Remaining, in minutes. If d2 = 0, defrosting will not
start.
d8 = Interval Between Two Defrostings, in hours. c0 = Minimum time for compressor to be OFF. Minimum time from
when the compressor stops till it connects again. c1 = Continuous Cycle Time. The remaining time for a continuous cold cycle.
c2 = ON time of fault cycle, during probe error. c3 = OFF time of fault cycle, during probe error. P1 = Ambient Probe Calibration. Offsets degrees to adjust the ambient
probe. P4 = Decimal Point. Display decimal point in normal operation. Always present in parameter menus.
H5 = Access Code to Parameters. Factory-set as 00. H6 = Ambient Probe Type. Sets probe type to be NTC or PTC. t0 = Temperature Display Limit. Maximum temperature shown on the
display, although the real temperature can be greater.
OPERATION IN CASE OF ERROR
If the probe or thermostat memory should fail, the compressor will be
connected for 5 minutes ON then 5 minutes OFF. The keyboard code can be set to zero by holding the SET key and turning the controller off then on again.
LED INDICATIONS
Out: This indicates that the compressor is connected. It waits the programmed minimum stop time of the compressor. Def: This indicates that defrosting is activated.
MESSAGES DISPLAY
In normal operation, the probe temperature will be shown. In case of alarm or error, the following messages will be shown:
• Er- Memory error.
• -- Short-circuited probe error.
• oo- Open probe error.
Description
Set point
SP
Differential or hysteresis
r0
Lower value for set point
r1
Higher value for set point
r2
Heating or cooling control
d0
Time for defrosting
d2
Interval time between defrosting
d8
Minimum stop time for compressor
c0
Continuous cycle time
c1
ON time of fault cycle
c2
OFF time of fault cycle
c3
Ambient probe adjustment
P1
Decimal point
P4
Parameter access code
H5
Ambient probe type
H6
Maximum temperature on display
t0
©Copyright 2014 Dwyer Instruments, Inc. Printed in U.S.A. 2/14 FR# R7-443771-00 Rev. 3
Units
degrees degrees degrees
degrees
option minutes hours minutes hours minutes minutes degrees option numeric option degrees
Range
r1 to r2 1 to 20°
-50 to 150°C
-58 to 302°F
-50 to 150°C
-58 to 302°F Ht/Co 0 to 59´ 0 to 24 0 to 59´ 0 to 24 0 to 999 0 to 999
-10° to 10° yes/no 0 to 255 ptc/ntc
-50 to 150°C
-58 to 302°F
MAINTENANCE
CLEANING
Clean the surface of the display controller with a soft, damp cloth. Never
use abrasive detergents, petrol, alcohol or solvents.
REPAIRS
After final installation of the TS Series Digital Temperature Switch, no
routine maintenance is required. A periodic check of system calibration is
returned to the factory if recalibration or other service is required. After first
obtaining a Returned Goods Authorization (RGA) number, send the
material, freight prepaid, to the following address. Please include a clear
description of the problem plus any application information
available.
Dwyer Instruments,Inc. Attn: Repair Department 102 Highway 212 Michigan City, IN 46360 U.S.A
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyermail.com