Dwyer TID User Manual

Bulletin E-90-TID
Series TID Temperature/Process Indicator
Specifications - Installation and Operating Instructions
The affordable Series TID allows user to monitor
temperature or a process value. Temperature ranges are available from -58 to 302°F using one of our PTC or NTC thermistors. Process values can be displayed from -999 to 999 counts using a 4 to 20 mA signal from one of our various transmitters. The process indicator has an adjustable span and zero on the 4 to 20 mA models.
Installation
Note: Unit must be mounted away form vibration, impacts, water, and corrosive gases.
• Cut hole in panel 2.80 x 1.14 in (71 x 29 mm).
• Apply silicone (or rubber gasket) around the perimeter of the hole to prevent leakage.
• Insert unit into hole of panel.
• Slide removable fitting clips onto unit from the back until secure to panel.
• Remove back cover to wire unit.
• Wiring diagram is displayed on the top of the unit.
SPECIFICATIONS Inputs: PTC/NTC thermistor or 4 to 20 mA. Display: 3-digits; red, green or blue display. Range: -58 to 302°F (thermistor); -999 to 999 counts (4
to 20 mA). Power Requirements: 110 VAC, 230 VAC, 12 VAC/DC, 24 VAC/DC.
Accuracy: Better than 1%. Resolution: 1° or 0.01 count. Front Panel Rating: IP64. Agency Approvals: CE.
THERMISTOR CONNECTION DIAGRAM
LOVE CONTROLS DIVISION
DWYER INSTRUMENTS INC. P.O. BOX 338 - MICHIGAN CITY, INDIANA 46361, U.S.A.
Phone: 219/879-8000 www.love-controls.com Fax: 219/872-9057 e-mail:love@love-controls.com
List of Parameters (Current Models Only)
Description Units Range Lc Value for 4 mA input Range -999 to 999 Hc Value for 20 mA input Range -999 to 999 P1 Decimal Point Selection no yes H5 Access code Numeric 0 to 99
Parameter Descriptions Lc = Value for 4 mA input
If P1 = Yes the value is displayed with decimal point Hc = Value for 20 mA input
If P1 = Yes the value is displayed with decimal point P1= Decimal Point
If P1= Yes LC, Hc and probe values are displayed with decimal point
H5 = Access code to parameters
Parameter Programming
• Press SET for 8 seconds. The Access code value 00 is shown on the display (unit comes with code set at 00 from factory).
• With the UP and DOWN arrows, code can be set to user needs.
• Press SET to enter the code. If the code is correct, the first parameter label is shown on the display (Lc).
• Move to the desired parameter with the UP and DOWN arrow keys.
• Press SET to view the value on the display.
• The value can be modified with the UP and DOWN arrows.
• Press ENTER to enter the value and exit.
• Repeat until all necessary parameters are modified.
• Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
Maintenance, Cleaning and Repair
After final installation of the unit, no routine maintenance is required. Clean the surface of the display controller with a soft and damp cloth. Never use abrasive detergents, petrol, alcohol, or solvents. All repairs must be made by authorized personnel.
* The keyboard code can be reset to ZERO by turning off the controller and turning it on again while keeping the SET key depressed.
Display Message
The display normally shows the temperature of the probe. In case of error the following messages are shown:
• Er = Memory error
• 00 = Open probe
• -- = Short circuit probe