Specications - Installation and Operating Instructions
Bulletin F-TDFS2-1
4-3/16
1-21/64
[33.78]
TDFS2-1-P-06TDFS2-1-P-06TDFS2-2-P-06TDFS2-2-P-06
The Series TDFS2 Thermal Dispersion Flow Switch is a thermal ow switch
that indicates whether the ow rate is above or below a user set ow rate. The unit
incorporates two LED status indicators providing visual switch indication. The set ow
rate (setpoint) is eld adjustable and the unit has both NO and NC NPN outputs. See
Figure 1 for output and LED actions on change of ow.
NC = OPEN, NO = CLOSED, LED = GREEN
FLOW
NC = CLOSED, NO = OPEN, LED = RED
Figure 1: Switch setpoint and deadband
OPERATING PRINCIPLE
The TDFS2 uses an impulse thermal dispersion measurement technique to measure
the ow rate. The probe is heated above the process temperature and then is allowed
to cool. The ow rate is determined from the rate at which the probe cools. The
measurement cycle time is approximately 8 seconds.
INSTALLATION
NOTICE
Ensure that the process uid is compatible with the wetted
materials, and do not exceed the maximum device ratings.
DEADBAND
SETPOINT
CABLE
CABLE GLAND
STATUS
INDICATOR
SETPOINT TARGET
PROCESS
CONNECTION
1/2˝ NPT
29/64
[11.68]
1-1/8
HEX
SPECIFICATIONS
Service: Compatible water-based uids.
Wetted Materials: 316 SS.
Pipe Range: 1/2 to 1-1/2˝ (15 to 40 mm) or 2 to 10˝ (50 to 250 mm) (model
selectable).
Setpoint Range: 0.5 to 10 ft/s (0.15 to 3.0 m/s).
Repeatability: 0.07 ft/s (0.02 m/s) +3% of setpoint.
Typical Deadband: 0.1 ft/s (0.03 m/s) +15% of setpoint.
Temperature Limits: Ambient: 5 to 140°F (-15 to 60°C); Process: 5 to 140°F (-15
to 60°C), Storage: -40 to 185°F (-40 to 85°C).
Pressure Limits: 300 psig (20.67 bar).
Response Time: Approximately 8 s.
Power Requirement: 9-24 VDC.
Switching Current: 400 mA, derate 5 mA/°C above 23°C.
Current Consumption: Average: 93 mA; Peak: 300 mA.
Electrical Connection: 1/2˝ NPT female or cable gland with 4 conductor 22 AWG
6´ (1.83 m) long (model selectable).
Process Connection: 1/2˝ NPT or BSPT male (model selectable).
Enclosure Rating: NEMA 4X (IP65).
Housing Materials: 316 SS, 416 SS, polycarbonate, neoprene, and acrylated
urethane.
Switch Type: 1 NO NPN, 1 NC NPN.
Input Power and Protection: 0.5A fuse (resettable) reverse polarity protected.
Switched Output Protection: 0.5A fuse (resettable) reverse polarity protected.
Agency Approvals: CE.
SENSOR
5-5/8
[142.88]
2-25/32
[70.49]
1-1/8
HEX
1-29/32
[48.26]
CABLE
CABLE GLAND
STATUS
INDICATOR
SETPOINT TA
PROCESS
CONNECTION
1/2˝ NPT OR BSPT
SENSOR
WARNING
system. The device and/or object may become a projectile.
NOTICE
NOTICE
operates properly if either is present. The setpoint will shift if the specic heat, density
or viscosity of the uid changes.
Severe injury may occur. Ensure that the system is not pressurized
before installing or removing this device or other objects from the
Do not use with abrasive uid mixtures.
Use caution if uid temperature changes or uid composition
changes are present in the end application. Verify that the device
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
OptionsBSPT 1/2˝ BSPT process connection
*Per ft cable length adder.
2
C
B
P
Phone: 219-879-8000
Fax: 219-872-9057
1/2 to 1-1/2˝ (15 to 40 mm) pipe sizes
2 to 10˝ (50 to 250 mm) pipe sizes
1/2˝ female NPT with PVC cable for
conduit connection
Cable gland with burial rated cable
Cable gland with PVC jacketed cable
www.dwyer-inst.com
e-mail: info@dwyermail.com
APPROXIMATE FLOW RATES FOR COLD WATER IN SS TEE AND CARBON STEEL
APPROXIMATE FLOW RATES FOR COLD WATER IN SS TEE AND CARBON STEEL SCHEDULE 40 PIPE: TDFS2-2-X-X
Pipe Size2˝ (50 mm)3˝ (80 mm)4˝ (100 mm)5˝ (125 mm)6˝ (150 mm)8˝ (200 mm)10˝ (250 mm)
GPM (LPM)5.25-104.98
(19.87-397.39)
0.82-16.47
(3.10-62.35)
11.55-230.91
(43.72-874.09)
1.35-27.01
(5.11-102.24)
19.9-397.9
(75.33-1506.21)
2.33-46.66
(8.82-176.63)
31.24-624.81
(118.26-2365.16)
3.18-63.51
(12.04-240.41)
45.14-902.7
(170.87-3417.08)
78.01-1560.17
(295.30-5905.87)
122.99-2459.81
(465.57-9311.36)
Mount the TDFS2 so that the sensor extends into the ow by 10-25% of the pipe ID.
Use PTFE tape on the process connection to reduce the risk of leaks. For proper ow
measurement, the sensor must be fully submerged in the uid. Bubbles, turbulence,
and sediments will cause improper operation. For best operation, mount 30° to
150° off vertical on horizontal runs (see Figure 2). Allow a straight run of at least 12
pipe diameters upstream and 5 pipe diameters downstream to ensure optimal ow
measurement. For optimal repeatability, ensure the ow switch is not operating in the
transition region (laminar to turbulent ow).
30°30°
BUBBLES
[AVOID]
OKOK
SEDIMENT
30°30°
Figure 2: Mounting orientation
ELECTRICAL CONNECTION
The power input and switched outputs are individually fused at 0.5A and are reverse
polarity protected. A shielded 4 conductor cable provides the electrical connection to
the TDFS2. The cable drain wire must be connected to earth ground in CE applications
or when strong RF elds are present.
Two open collector switched outputs are provided. One is normally open (NO), and the
other output is normally closed (NC). The output logic is shown in Table 1.
The setpoint may be adjusted with the supplied magnet. There are two setpoint targets
on the unit located under the LED status indicator on opposite sides of the unit (see
Figure 4). Either setpoint target may be used, and either end of the magnet may be
used. If the setpoint does not set easily, try reversing the magnet.
STATUS
INDICATO
SETPOINT
TARGET
Figure 4: Set point target
Steps:
1) Ensure that the unit is properly installed and powered.
2) Set the system ow to the desired setpoint ow rate.
3) Tap the setpoint target three times with the supplied magnet. Move the magnet
approximately 2 inches away from the target between each tap. The taps should
be approximately 1 second apart. The LED status indicator will blink slowly when
the setpoint request is recognized. The slow blink will stop when the setpoint has
been stored.
POWER (RED)
NO (WHITE)
NC (GREEN)
GROUND (BLACK)
HOUSING (DRAIN WIRE)
Figure 3: Wiring diagram
Ensure that units with conduit opening are properly sealed with appropriate conduit.
LOAD(S)
EARTH
GROUND
+
–
DC SUPPLY
9-24 VDC
STATUS INDICATOR
The status indicator (See Figure 4) provides visual indication of the TDFS2 status.
Two status indicators are located on opposite sides of the unit. Each status indicator
has one red LED and one green LED. Table 2 describes the status indicator states.
If an error condition is present, the unit will continue measurement attempts until the
problem has cleared. The status indicator will cycle on and off during this time.
DescriptionColorState
Off
Dimmed Pulses
Steady
Intermittent
Slow Blink
NOTICE
PRESSURE DROP
TDFS2-1-X-XTDFS2-2-X-X
Velocity
ft/s (m/s)
0.5 (0.15)
1.0 (0.31)
2.0 (0.61)
3.0 (0.91)
4.0 (1.22)
5.0 (1.52)
6.0 (1.83)
7.0 (2.13)
8.0 (2.44)
9.0 (2.74)
10.0 (3.05)
1/2˝ (15 mm)
in w.c (kPa)
0
0
0
0.2 (0.045)
0.5 (0.125)
0.7 (0.174)
2.6 (0.648)
3.3 (0.822)
4.3 (1.071)
3.5 (0.872)
4.5 (1.121)
N/A
Any
Red
Green
Red and Green
Any
Green
Red and Green
Alternating
Table 2: Status indicator states
Design a fail-safe system that takes into consideration the
possibility of switch failure, power failure and operator error.
3/4˝ (20 mm)
in w.c. (kPa)
0
0
0.2 (0.045)
0.4 (0.099)
0.7 (0.174)
1.2 (0.299)
1.7 (0.423)
2.1 (0.523)
2.7 (0.673)
3.4 (0.847)
4.2 (1.046)
Waiting for rst measurement or unit is off
Start of a measurement cycle (normal
operation)
Flow is below the setpoint
Flow is above the setpoint
Error condition:
(1) Process temperature is out of range
(2) Internal fault
A setpoint adjustment was requested
Flow is in the nominal range
Flow is below the nominal range
Setpoint will be limited to the maximum
allowable ow
2-1/2˝ (65 mm)
in w.c. (kPa)
0
0.1 (0.013)
0.1 (0.045)
0.4 (0.095)
0.7 (0.164)
1.0 (0.252)
1.4 (0.358)
1.9 (0.482)
2.5 (0.625)
3.1 (0.787)
3.9 (0.967)
Table 3: Pressure drop (water)
4˝ (100 mm)
in w.c. (kPa)
0
0
0
0.1 (0.018)
0.1 (0.033)
0.2 (0.053)
0.3 (0.078)
0.4 (0.107)
0.6 (0.141)
0.7 (0.180)
0.9 (0.224)
6˝ (150 mm)
in w.c. (kPa)
0
0
0
0
0.1 (0.017)
0.1 (0.025)
0.1 (0.035)
0.2 (0.047)
0.2 (0.060)
0.3 (0.075)
0.4 (0.091)
MAINTENANCE/REPAIR
Upon nal installation of the Series TDFS2, no routine maintenance is required. The
Series TDFS2 is not eld serviceable and should be returned if repair is needed. Field
repair should not be attempted and may void warranty.
This symbol indicates waste electrical products should not be disposed
of with household waste. Please recycle where facilities exist. Check with
your Local Authority or retailer for recycling advice.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact
customer service to receive a Return Materials Authorization (RMA) number before
shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.
PARTS
Replacement magnets (part number 100571-00) may be ordered from Dwyer
Instruments, Inc.