Dwyer SVP User Manual

Series SVP Proportioning Solenoid Valve
SOL ENOI D VALVE PS V 
FLOW IN FUNCTION WITH VALVE VOLTAGE  VOLTAGE TOLERANCE FOR DIFFERENT VALVE SIZES.
FLOW
%
FOR 10 PSID
VOLTS
(TOLERANCE
±1.2 5 VOLTS)
10
20
30
40
50
60
70
80
90
100
456
7
89101112
13 14 15 16
Specifications - Installation and Operating Instructions
Bulletin F-82
The SVP Series is a low cost, uniquely designed solenoid valve which
controls or regulates flow in proportion to a variable voltage input. While most solenoid valves simply provide on/off service, this unit adds a total­ly new dimension to solenoid valve performance. Reacting to a 0-24 VDC input signal, the valve opens proportional to the voltage applied, delivering just the right amount of flow needed. Compatible with a wide rage of gases and liquids, this unit provides the solution to even the most demanding applications like process control, chemical mixing, high tech manufacturing and laboratory testing. Another quality feature of this valve is its tight shut-off (NC) when de-energized.
Stocked Models:
Maximum Flow* Orifice IN. (MM)
Model
0.020 (0.51)
SVP-1
0.040 (1.02)
SVP-2
0.055 (1.40)
SVP-3
0.063 (1.60)
SVP-4
*Based on 10 psig (69 kPa) inlet pressure and atmospheric exhaust.
C
V
0.009
0.033
0.055
0.068
Air SCFH (LPM)
7.4 (3.5)
27.5 (13)
45.6 (21.5) 53 (25)
Water GPH (CC/M)
2.0 (125)
6.4 (400)
11.1 (700)
13.5 (850)
Select a location which is free of excessive heat, moisture and vibration. The series SVP Proportioning Solenoid Valve may be held in place by your 1/4˝ metal process tubing or secured to a rigid surface via the two 6-32 tapped holes in the base of the valve body. Flow through the valve should be in the direction of the arrow marked on the body. The Series SVP Valve may be used with most gases or liquids that are compatible with the wetted parts: 316 and 416 stainless steel and Fluoroelastomer. Due to the small orifice size of the Series SVP, the media must be free of scale, particulate, or any other contaminant’s which might interfere with the motion of the valve.
SPECIFICATIONS Voltage Input: 0-24 VDC. Maximum Operating Current: 400 mA. Electrical Connections: Male spade type. Wetted Materials: 316 and 416 stainless steel, Fluoroelastomer,
O-rings.
Maximum Pressure: 500 psig (34.45 bar). Process Temperature Limits: -40°F to 174°F (-40°C to 79°C). Ambient Temperature Limits: -40°F to 130°F (-40°C to 54°C). Type of Operation: Normally closed, valve will close when de-ener-
gized.
Connections: 1/4˝compression fitting. Weight: 12 oz. (340 grams).
The precise flow characteristics of each valve will vary depending on a number of factors, including orifice size and upstream pressure. While it is best to determine valve performance under your own process condi­tions, the flow curve shown in Fig. A can be used for reference purpos­es.
©Copyright 2014 Dwyer Instruments, Inc. Printed in U.S.A. 4/14 FR# RV-440894-00 Rev. 2
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9052 e-mail: info@dwyermail.com
Fig. A
Phone: 219/879-8000 www.dwyer-inst.com
Loading...