Dwyer STRA User Manual

Series STRA Duct Mounted Airflow Measurement Station
AIR STRAIGHTENER
[F]
[D]
AIRFLOW
TOTAL PRESSURE
(T.P.) TAKEOFF
1/4˝ COMPRESSION
FITTING
[L]
STATIC PRESSURE
(S.P.) TAKEOFF
1/4˝ COMPRESSION
FITTING
3.25
[H]
[W]
.25˝ RADIUS BEADED EDGE (TYP)
TOTAL PRESSURE
(T.P.) TAKEOFF
1/4˝ COMPRESSION
FITTING
AIRFLOW
STATIC PRESSURE (S.P.) TAKEOFF 1/4˝ COMPRESSION FITTING
[L]
[L+2.5]
[W]
[F]
[H]
TOTAL PRESSURE
(T.P.) TAKEOFF
1/4˝ COMPRESSION
FITTING
STATIC PRESSURE
(S.P.) TAKEOFF
1/4˝ COMPRESSION FITTING
AIRFLOW
Specifications - Installation and Operating Instructions
CIRCULAR FLANGE DIMENSIONS Station
Size “D” 8˝ – 15˝ 16˝ – 44˝ 45˝ – 72˝ 73˝ & Over
Flange Thickness .064˝ .064˝ .188˝ .188˝
OVAL FLANGE DIMENSIONS (OPTIONAL) Station
Width “W” Up to 44˝ Over 44˝
*NOTE: All oval flow stations without flange have a casing length of 8˝.
Flange Size “F” 1˝ 1-1/2˝ 1-1/2˝ 2˝
Flange Thickness .064˝ .188˝
Casing Length “L” 8˝ 8˝ 10˝ 12˝
Flange Size 1-1/2˝ 1-1/2˝
*Casing Length “L” 8˝ 10˝
Bulletin F-STRA
RECTANGULAR FLANGE DIMENSIONS Station
Size “H” or “W” 8˝ – 72˝ 73˝ & OVER
SELECTABLE SIZES:
1. OVAL OR RECTANGULAR “H” OR “W” DIMENSIONS IN INCHES CAN BE THE FOLLOWING: 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34, 36, 40, 44, 48, 52, 56, 60, 66, 72, 78, 84, 90, 96, 102, 108, 114 or 120.
2. CIRCULAR “D” DIMENSION IN INCHES CAN BE THE FOLLOWING: 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 36, 40, 44, 48, 54, 60, 66, 72, 78, 84, 90, 96, 102, 108, 114 or 120
The Series STRA Airflow Measurement Station consists of single or multiple airflow elements, factory mounted and pre-piped in a casing designed for flanged connection to the ductwork. The station also incor­porates an airflow straightening section using a honeycomb which has a 1/2 inch opening by 3 inch depth. Standard materials consist of a G90 galvanized casing, 6063-T5 anodized aluminum flow sensors, and 3003 aluminum air flow straightener, suitable for most HVAC applications. The Series STRA Air Flow Measurement Station has been developed for use in duct systems having a highly turbulent condition at the point of measure­ment. The airflow averaging element, utilized in the Series STRA, is a head type device, which generates a differential (velocity) pressure signal similar to the orifice, venturi, and other head producing primary elements. The Series STRA is constructed so that strategically located sensing ports (based on duct size) continually sample the total and static pressures, when inserted normal to flow. The total pressures sensed by the upstream ports are con­tinually averaged within the element in an isolated chamber. The static sensing ports (located where the influence of the velocity head is zero) are averaged in a se cond i solat ion ch amber. Multiple elements are manifolded together for connection to a differential measurement device (gage, trans­mitter, etc.) for flow measurement and indication purposes.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Flange Size “F” 1-1/2˝ 2˝
SPECIFICATIONS Accuracy: Within 2% of actual flow when installed in accordance with
K Factor: 0.97. Velocity Range: 100 to 10,000 fpm (0.51 to 51 m/s). Wetted Material: Elements: 6063-T5 anodized aluminum; Casings: 16
ga G90 galvanized steel, 3003 aluminum air flow straightener. Temperature Limits: Galvanized Casings and Aluminum Elements 350°F (177°C) continuous operation (in air), 400°F (204°C) intermittent operation (in air).
Humidity: All Airflow Stations 0 to 100% non condensing. Process Connections: 1/4˝ compression fittings.
Phone: 219/879-8000 www.dwyer-inst.com
Circular Flange Dimensions
Station
Size
6˝ - 15˝ 16˝ - 44˝ 45˝ - 72˝
73˝ & Over
Circular Stations
Standard circular airflow measuring stations include a 16 gage galvanized casing with attached 90° connecting flanges as listed above.
Flange
Thickness
0.064˝
0.064˝
0.188˝
0.188˝
Flange
Size
1˝ 1-1/2˝ 1-1/2˝
Casing
Length “L”
8˝ 10˝ 12˝
Rectangular Flange Dimensions
Station
Size
8˝ - 72˝
73˝ & Over
Rectangular Stations
Standard rectangular airflow measuring stations include a 16 gage galva­nized casing, 8 inches long, with formed integral 90° connecting flanges as listed above.
Flange
Size
1-1/2˝
Oval Flange Dimensions (Optional)
Station
Size
Up to 48˝
Over 48˝
Oval Stations
Standard oval airflow measuring stations include an 18 gage galvanized casing, 8 inches long between beads with 1-1/4 inch connecting sleeve on each end (10-1/2 inch overall length). Actual O.D. dimensions are 1/4 inch less than specified duct I.D. dimensions.
INSTALLATION
The elements may be installed in any duct configuration. However, the accuracy of the installation is dependent on the flow conditions in the duct. The minimum installation requirements for the elements based upon a uniform velocity profile approaching the duct disturbance for flow rates less than 2,500 fpm are shown below. Add one duct diameter to the installation requirements shown below for each additional flow rate of 1000 fpm. These are not ideal locations. It is always best to locate the ele­ments as far as possible from all duct disturbances, with upstream distur­bances being the most critical consideration.
Flange
Thickness
0.064˝
0.188˝
Flange
Size
1-1/2˝ 1-1/2˝
Casing
Length “L”
10˝
ELBOWS
Notes:
Round Ducts: D = Duct diameter
TRANSITIONS
Rectangular Ducts:
D = 4HW
π
π
H = Duct height W = Duct width