Specifications - Installation and Operating Instructions
CIRCULAR FLANGE DIMENSIONS
Station
Size “D”
8˝ – 15˝
16˝ – 44˝
45˝ – 72˝
73˝ & Over
Flange
Thickness
.064˝
.064˝
.188˝
.188˝
OVAL FLANGE DIMENSIONS (OPTIONAL)
Station
Width “W”
Up to 44˝
Over 44˝
*NOTE: All oval flow stations without
flange have a casing length of 8˝.
Flange
Size “F”
1˝
1-1/2˝
1-1/2˝
2˝
Flange
Thickness
.064˝
.188˝
Casing
Length “L”
8˝
8˝
10˝
12˝
Flange
Size
1-1/2˝
1-1/2˝
*Casing
Length “L”
8˝
10˝
Bulletin F-STRA
RECTANGULAR FLANGE DIMENSIONS
Station
Size “H” or “W”
8˝ – 72˝
73˝ & OVER
SELECTABLE SIZES:
1. OVAL OR RECTANGULAR “H” OR “W” DIMENSIONS IN INCHES CAN BE THE FOLLOWING: 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34, 36, 40, 44, 48, 52, 56, 60, 66, 72, 78, 84, 90, 96, 102, 108, 114 or 120.
2. CIRCULAR “D” DIMENSION IN INCHES CAN BE THE FOLLOWING: 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 36, 40, 44, 48, 54, 60, 66, 72, 78, 84, 90, 96, 102, 108, 114 or 120
The Series STRA Airflow Measurement Station consists of single or
multiple airflow elements, factory mounted and pre-piped in a casing
designed for flanged connection to the ductwork. The station also incorporates an airflow straightening section using a honeycomb which has a
1/2 inch opening by 3 inch depth. Standard materials consist of a G90
galvanized casing, 6063-T5 anodized aluminum flow sensors, and 3003
aluminum air flow straightener, suitable for most HVAC applications. The
Series STRA Air Flow Measurement Station has been developed for use in
duct systems having a highly turbulent condition at the point of measurement.
The airflow averaging element, utilized in the Series STRA, is a head type
device, which generates a differential (velocity) pressure signal similar to the
orifice, venturi, and other head producing primary elements. The Series
STRA is constructed so that strategically located sensing ports (based on
duct size) continually sample the total and static pressures, when inserted
normal to flow. The total pressures sensed by the upstream ports are continually averaged within the element in an isolated chamber. The static
sensing ports (located where the influence of the velocity head is zero) are
averaged in a se cond i solat ion ch amber. Multiple elements are manifolded
together for connection to a differential measurement device (gage, transmitter, etc.) for flow measurement and indication purposes.
SPECIFICATIONS
Accuracy: Within 2% of actual flow when installed in accordance with
published recommendations.
K Factor: 0.97.
Velocity Range: 100 to 10,000 fpm (0.51 to 51 m/s).
Wetted Material: Elements: 6063-T5 anodized aluminum; Casings: 16
ga G90 galvanized steel, 3003 aluminum air flow straightener.
Temperature Limits: Galvanized Casings and Aluminum Elements
350°F (177°C) continuous operation (in air), 400°F (204°C) intermittent
operation (in air).
Humidity: All Airflow Stations 0 to 100% non condensing.
Process Connections: 1/4˝ compression fittings.
Phone: 219/879-8000www.dwyer-inst.com
Circular Flange Dimensions
Station
Size
6˝ - 15˝
16˝ - 44˝
45˝ - 72˝
73˝ & Over
Circular Stations
Standard circular airflow measuring stations include a 16 gage galvanized
casing with attached 90° connecting flanges as listed above.
Flange
Thickness
0.064˝
0.064˝
0.188˝
0.188˝
Flange
Size
1˝
1-1/2˝
1-1/2˝
2˝
Casing
Length “L”
8˝
8˝
10˝
12˝
Rectangular Flange Dimensions
Station
Size
8˝ - 72˝
73˝ & Over
Rectangular Stations
Standard rectangular airflow measuring stations include a 16 gage galvanized casing, 8 inches long, with formed integral 90° connecting flanges
as listed above.
Flange
Size
1-1/2˝
2˝
Oval Flange Dimensions (Optional)
Station
Size
Up to 48˝
Over 48˝
Oval Stations
Standard oval airflow measuring stations include an 18 gage galvanized
casing, 8 inches long between beads with 1-1/4 inch connecting sleeve
on each end (10-1/2 inch overall length). Actual O.D. dimensions are 1/4
inch less than specified duct I.D. dimensions.
INSTALLATION
The elements may be installed in any duct configuration. However, the
accuracy of the installation is dependent on the flow conditions in the
duct. The minimum installation requirements for the elements based upon
a uniform velocity profile approaching the duct disturbance for flow rates
less than 2,500 fpm are shown below. Add one duct diameter to the
installation requirements shown below for each additional flow rate of
1000 fpm. These are not ideal locations. It is always best to locate the elements as far as possible from all duct disturbances, with upstream disturbances being the most critical consideration.
Flange
Thickness
0.064˝
0.188˝
Flange
Size
1-1/2˝
1-1/2˝
Casing
Length “L”
8˝
10˝
ELBOWS
Notes:
Round Ducts:
D = Duct diameter
TRANSITIONS
Rectangular Ducts:
D = 4HW
π
π
H = Duct height
W = Duct width
STRA RESISTANCE to AIRFLOW
SERIES STRA SPECIFICATION GUIDE
1. Provide where indicated and/or scheduled airflow traverse elements
capable of continuously monitoring the fan or duct air volumes they serve.
2. Each element shall be designed and built to comply with, and provide
results in accordance with, accepted practice for duct system traversing as
defined in the ASHRAE Handbook of Fundamentals, AMCA publication
#203, as well as the Industrial Ventilation Handbook. The number of sensing ports on each element, and the quantity of elements utilized at each
installation, shall comply with ASHRAE Standard #111 for equal area duct
traversing. Each element shall be of a dual integral chambered design.
3. Each airflow measuring element shall contain multiple total and static
pressure sensing ports placed along the leading edge of the cylinder. The
static pressure chamber shall incorporate dual offset static taps on opposing sides of the averaging chamber, so as to be insensitive to flow angle
variations of as much as ±20 degrees in the approaching airstream.
4. The airflow traverse elements shall be capable of producing steady, nonpulsating signals of true total and static pressure, with an accuracy of 2%
of actual flow for operating velocities as low as 180 feet per minute (fpm).
Signal amplifying sensors requiring flow correction (K factors) for field calibration are not acceptable.
5. The airflow traverse elements shall not induce a measurable pressure
drop, greater than 0.18 inch at 4,000 fpm. The units sound level within the
duct shall not be amplified, nor shall additional sound be generated.
Installation Considerations
1. Primary flow elements shall be installed in strict accordance with the
manufacturers published requirements and with ASME guidelines affecting
non-standard approach conditions. These elements serve as the primary
signals for the airflow systems; it shall be the responsibility of the contractor to verify correct installation to assure that accurate primary signals are
obtained.
2. An identification label shall be placed on each unit casing listing model
number, size, area, and specified airflow capacity.
6. The probes shall be mounted in an eight inch deep, 16 gauge galvanized
steel casing with 90 degree undrilled flanges, fabricated to the duct size,
and shall contain multiple airflow traverse elements interconnected as herein before described.
7. Where primary flow elements are located outside of the manufacturer’s
published installation guidelines the manufacturer shall be consulted, and
approve of any special configurations, such as air equalizers and/or additional and strategically placed measuring points, as may be required.
8. Where the stations are installed in insulated ducts, the airflow passage
of the station shall be the same size as the inside airflow dimension of the
duct. Station flanges shall be sized to facilitate matching connecting ductwork.
Above Pv Values are Based on Standard Air Density of 0.075 lbm ft3which is Air at 68°F. 50% Relative Humidity, and 29.92˝ Hg.
The equation for converting air volume (Q) into velocity (V) and velocity pressure (Pv) is:
Where
V = Q
PV = V 2 x p
A
MAINTENANCE
Since the sensing elements have no moving parts, only periodic cleaning
may be required. The sensing elements should be inspected for fouling of
the sensing holes as part of an annual preventative maintenance program.
Installations having viscous airborne particles may require more frequent
inspection. If the sensing holes on the elements have become fouled or
plugged, the following procedure is recommended. Caution, all instru-
ments must be isolated (removed) from the sensing lines prior to
performing the following cleaning procedure.
Backpurging: Connect clean/dry compressed air, set at a maximum
pressure of 25 psi, to the output pressure ports (total and/or static) of the
sensing element being cleaned. While purging the sensing element, wipe
the surface of the cylinder with a cloth or brush to loosen and remove all
contaminant buildup.
[
[
C
V = Velocity in fpmC = 1096.7
Q = Flow in cfmp = Density of air in lb/ft
A = Area in ft
Cleaning: In applications where the sensing elements are subject to viscous contaminants it is recommended that the surface be washed with a
cleaning agent. The cleaning agent used must be suitable for use on the
type of material the sensing element is constructed of (i.e. aluminum, stainless steel, etc.)
The Series STRA Duct Mounted Airflow Measurement Station is not field
serviceable and should be returned if repair is needed (field repair should
not be attempted and may void warranty). Be sure to include a brief
description of the problem plus any relevant application notes. Contact
customer service to receive a return goods authorization number before
shipping.