Dwyer SLD User Manual

Series SLD Single Channel Leak Detection Relay
Specifications - Installation and Operating Instructions
19/64 (7.54)
Bulletin L-43
2-3/8
(60.32)
The Series SLD is a specialized control for monitoring the shaft seal of a submersible pump motor. A leak is detected by sensing the status of a resistive float switch installed in the seal cavity. When the resistance drops below the sensitivity rating the output relay energizes and the LED illuminates. When the fault condition clears, the output relay resets automatically.
Important: Read the following carefully and completely before installing or connecting SLD units.
Note: DO NOT exceed specified electrical rating. Doing so may result in damage to control unit and load device.
INSTALLATION
1.Lock out all electrical current to relevant control panel during installation.
2.Fasten a standard 11-pin socket in the control panel.
3.Make the appropriate connections as shown in the wiring diagram (Figure A) to the corresponding numbered contacts on socket.
4. Fit the Series SLD controller in the 11-pin socket.
3
(76.20)
1-3/4
(44.45)
SPECIFICATIONS Power Requirement: 120 VAC, 50/60 Hz. Power Consumption: 2 VA (approximate). Isolation Voltage: 2500 V. Temperature Limits:
Operating: -4 to 131°F (-20 to 55°C); Storage: -40 to 185°F (-40 to 85°C).
Switch Type: DPDT. Switch Voltage: 9 VDC. Electrical Rating: 10 A @ 250 VAC resistive, 360 VA inductive. Response Time:
Energize: 15 ms (approximate); Release: 8 ms (approximate).
Indicators: Red LED illuminates when leak is detected. Enclosure: Polycarbonate dust cover. Mounting: 11-pin socket. Weight: 8 oz (227 g). Agency Approvals: UL 508.
RESISTIVE
FLOAT
SWITCH
HOT
NEUTRAL
N.C.
CONTACT
N.O.
CONTACT
6
7
5
4
3
2
111
LOAD
8
9
ALARM
10
5.ADJUSTABLE SENSITIVITYMODELS ONLY: Set the potentiometer on face of unit to desired resistance.
6.Resume power to control panel and monitor system for proper functionality.
MAINTENANCE
Upon final installation of the Series SLD Single Channel Leak Detection Relay, no routine maintenance is required. A periodic check of the system calibration is recommended. The Series SLD is not field serviceable and should be returned if repair is needed
Figure A
(field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.