SCC OPEN SIGNAL Family
Model SCC-FRQ/V Single Channel Module
NOTE: THIS IS A FACTORY CONFIGURED UNIT
FACTORY CONFIGURATION
Each SCC-FRQ/V unit is configured and calibrated 
at the factory for the input signal range and voltage output range printed by the factory on the 
SCC unit’s side-label.
The SCC-FRQ/V unit is capable of accommodating a 0 to 25KHz input frequency at a signal magnitude of up to 250 volts and provides a 0 to 5V or 
0 to 10V output signal. Unit re-configuration 
requires Dwyer Instruments, Inc. Configurator 
Utility.
This SCC unit may be reconfigured by a user at 
any time via their personal computer (PC) or 
handheld personal computer (HPC) by installing 
Dwyer Instruments, Inc. Windows®/PC or Windows®/CE HPC based SC Configurator Utility, interfacing the SCC unit to the computer’s RS-232C 
comm port with an SCC Configuration Cable (sold 
separately), and then changing the unit’s input/ 
output configuration settings.
OPERATIONAL DESCRIPTION
The SCC family of single channel signal conditioning and isolating modues are intelligent, user 
programmable, high-accuracy, user friendly, signal conditioning units.
Each SCC model supports one (1) specific analog 
signal-type on its input channel and outputs either one (1) high-level current or voltage signal 
depending upon model. A diverse SCC model 
family permits users to select the model which 
meets their unique signal conditioning needs.
SCC models may be purchased with a factory preset configuration for plug-n-play application or
TERMINALS
available unconfigured so user may configure the 
unit to meet their unique need. All SCC models 
may be configured/reconfigured by a user at anytime through use of an optional SC Configuration 
Package.
Theory of Operation - An analog world input signal 
arriving at the SCC unit is isolated, filtered, amplified, scaled and/or linearized (as required) by the 
units onboard microprocessor under the direction 
of the unit’s configuration parameters set by the 
user (or factory) via Windows®/PC or Windows®/ 
CE HPC (Handheld Personal Computer) based SC 
Configurator Utility.
The conditioned signal is then converted to a high 
level analog current or voltage output signal (depending upon model) and presented at the unit’s 
isolated output.
REQUIREMENTS
Mandatory:
• 15 - 32VDC, 30mA external supply voltage
Optional:
• SC Configuration Package (Part No. SCCCC-A1) Package consists of: SC 
Configurator Utility and SCC Configuration Cable.
INSTALLATION
1. Mount SCC unit on standard TS32 or TS35 
DIN rail.
2. See wiring diagram on reverse side. Connect 
external 15 to 32VDC power source to SCC 
unit: 
  Positive (+) to SCC terminal +VDC 
  Negative (-) to SCC terminal -FRQ/-VDC
WIRING
TERMINAL
BLOCK
ENCLOSURE
ENCLOSURE
COVER
3 . Connect input frequency device to SCC unit:
  Positive (+) to SCC terminal +FRQ 
  Negative (-) to SCC terminal -FRQ/-VDC
4. Connect output actuator/device to SCC unit: 
  Positive (+) to SCC terminal +V OUT 
  Negative (-) to SCC terminal -OUT
DIAGNOSTIC TOOLS
Two LEDs one RED and one GREEN are located 
on the front face of the SCC’s enclosure and provide user with visual indication as to unit operation.
LED FUNCTIONALITY
LED’s have three operational states:
Steady ON 
Steady OFF 
Blinking
Condition: GREEN = BLINKING
RED = Steady OFF
Meaning: Module is processing data.
Condition: GREEN = Steady ON
RED = Steady ON 
Meaning:   1) Configuration data is not loaded in 
module memory. -OR- 2) During module re-configuration both LED’s are normally ON indicating data is being properly transferred to or from 
module memory.
Condition: GREEN = BLINKING
RED = BLINKING 
Meaning:  The measured input signal is outside 
the modules configured range. When the signal is 
within configured range the LED’s indicate normal operation.
All other combinations indicate the module is not 
operating correctly.
6
5
2
1
SNAP-ON TAB
(TERMINAL MARKERS)
4
3
SNAP-ON TAB 
(COVERS COMM CABLE PORT)
GREEN LED
CABLE
PORT
RED LED
TERMINAL
SET SCREW

15 to 32 V D C
Power Source
+VDC
 INPU T
FREQUENCY
-FR Q/-VDC
+FRQ
+V OUT
+I OUT
-OU T
ANALOG
ACTUATOR
or
DEVICE
SCC-FRQ/V Wiring Diagram
CONFIGURATION CHANGE
An SCC’s configuration can only be changed 
through use of a personal computer running our 
Windows® based SC Configurator Utility and a 
special configuration communication cable to 
interface the SCC unit and personal computer 
together. (See Requirements - on reverse side for 
purchasing information.)
Instructions on how to accomplish configuration 
change are included with SC Configuration 
Package and not covered here.
SPECIFICATIONS
Input Power: 15-32VDC 
Isolation: 2 way output to power/input 1500V peak 
Over Voltage: 240VRMS continuous 
Step Response to 99%: 0.3 seconds 
Operating Temp.: -40 to +75°C 
Storage Temp.: -40 to +85°C 
Mounting: 32 and 35mm DIN Rail & G Rail 
Dimensions: 75mm H X 12.2mm W X 60 mm D 
(2.95” X 0.485” X 2.5”), 24 modules can be installed 
per linear foot of DIN Rail 
Diagnostics LEDs: Active and alarm indications 
Maximum Wire Size: 14 AWG 
Input Type: Frequency 
Input Range: (Fully scalable to user input 
specifications)
Warning: This unit is protected against abnormally
high and low voltages. Marginally low voltages, marginally high voltages and power fluctuations for extended 
periods of time can cause permanent damage.
Caution: When installing the unit’s wiring do not
over-tighten the wiring terminal set screws. Turn set screw 
until wire’s resistance is encountered and wire is securely 
captured. Over tightening will cause damage to the unit.
Recommended torque: 1.0 in/lbs
 Frequency Input: 0 to 25 KHz   0 to 10 KHz
0 to 1KHz    0 to 100 KHz
At a magnitude of: 0 to 24 V    0 to 12 V 
(requires hardware 0 to 5 V     0 to 50 V 
change) 0 to 250 V
Output: 
       V oltage -- 0 to 5V or 0 to 10V
Accuracy: ±0.05%
TRADE SECRETS AND PROPRIETARY NOTICE -- This document and the software 
described therein contains valuable trade secrets and proprietary information of Dwyer 
Instruments, Inc. and are copyrighted with all rights reserved. Under the copy righted laws, 
this document and the driver software supplied by Dwyer Instruments, Inc. may not be 
copied, in whole or part, without the written consent of Dwyer Instruments, Inc., except 
in the normal use of the software or to make a backup copy. The same proprietary and 
copyright notices must be affixed to any copies to be made for others, whether or not sold, 
given, or loaned to another person. Under the law, copying includes translating to another 
language or format.
Dwyer Instruments, Inc. in developing this product and drivers for applicable programmable 
logic controllers has attempted to offer the most current, correct and clearly expressed 
information possible. Nonetheless, errors can occur. Except as expressly set forth above, 
Dwyer Instruments, Inc. does not warrant that driver software is free from bugs, errors, 
or other application limitations.
WARRANTY  -- Manufacturer (Dwyer Instruments, Inc.) warrants that its product, under 
normal use and specified use, is free from defects and poor workmanship for a period of 
twelve (12) months from the date of shipment from the Dwyer Instruments, Inc. factory. 
Dwyer Instruments, Inc. makes no other warranties or representations express or implied, 
whether of merchantability, suitability of fitness for a particular purpose or otherwise
Dwyer Instruments, Inc. quality products were designed, and are manufactured with tight 
tolerance specifications. Any attempt to repair or otherwise modify Dwyer Instruments, 
Inc. products will result in the termination of all warranty benefits. Although Dwyer 
Instruments, Inc. may choose to repair a product returned under warranty, it will not attempt 
to repair products that are beyond the warranty period. Evaluation and repair costs of 
product beyond the warranty period would likely exceed replacement costs. As such, Dwyer 
Instruments, Inc. supports the policy of “repair by replacement”.
RETURNING MATERIAL TO THE MANUFACTURER -- Should it become necessary to 
return any material to the manufacturer (Dwyer Instruments, Inc.), a Return Authorization 
(RA) number must first be obtained. Telephone Dwyer Instruments, Inc. at 219-879-8868 
or 219-879-8000 or Fax 219-879-9057 to request an RA#. Be prepared to: (1) Identify the 
material to be returned (model, S/N, sales order#); (2) Detail the reason for the return; (3) 
Describe the “next step” expectations from Dwyer Instruments, Inc.; (4) Provide a Purchase Order, if a replacement is requested prior to the receipt of the return -- even if it is 
believed that the return is covered under warranty.
When returning material to Dwyer Instruments, Inc., the RA# must be included on all 
shipping documents and prominently displayed on the outside of the shipping container -this will reduce your turn around time.
LIMITATION OF LIABILITY  -- Buyer and/or end users sole remedy shall be the repair 
or replacement of the defective product with any damages limited to the purchase price of 
the product. In no event shall manufacturer have any liability for the direct, indirect, special, 
consequential or incidental damages, including but not limited to loss of profits, use or 
production, or for another claim for damages whether based or claimed in contract, 
warranty, negligence, strict liability, indemnification or otherwise.
COPYRIGHT NOTICE -- This document and the accompany driver software diskette(s) 
are Copyright 1995 - 1997 by Dwyer Instruments, Inc.. All right reserved. The software 
described in document is furnished as-is.
F.C.C. STATEMENT -- This equipment has been tested and found to comply with the 
limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are 
designed to provide reasonable protection against harmful interference in a residential 
installation. This equipment generates, uses and can radiate radio frequency energy and, 
if into installed and used in accordance with the instructions, may cause harmful interference 
to radio communications. However, there is no guarantee that interference will not occur 
in a particular installation. If this equipment does cause harmful interference to radio or 
television reception, which can be determined by turning the equipment off and on, the user 
is encouraged to correct the interference by one or more of the following measures: (1) 
Reorient or relocate the receiving antenna; (2) Increase the separation between the 
equipment and receiver; (3) Connect the equipment into an outlet on a circuit difference from 
that to which the receiver is connected; (4) Consult the dealer or an experienced radio/TV 
technician for help.
INSTALLATION AND SAFETY GUIDANCE NOTES 
Environment - Dwyer Instruments, Inc. products are designed to operate reliably and
safely in their specified environment. However the following guidelines must be followed to 
ensure Safety, Electromagnetic Compatibility and Performance.
• Products have been tested for the Industrial Environment (BS EN 50081-2 and 
50082-2) unless otherwise stated. Operation in any other environment is not 
guaranteed and at the risk of the User.
• The User is required to suppress high energy transients, such as those caused by 
lightning strikes, unless the product is specified for such purposes. Non-resistive 
loads and contact arcing must be suppressed at source.
• Products are intended for installation inside an equipment cabinet or suitable enclosure unless otherwise specified. This should be accessible only to qualified personnel 
during commissioning and maintenance. Open chassis products for use above 50V 
should only be accessible by the removal of a cover using a key or tool.
• Anti-static precautions and conventional Instrumentation best practice must always 
be observed. Each active module should be protected by a suitably rated fuse or 
equivalent protection device.
Product EMC Performance - The performance of Dwyer Instruments, Inc. products 
that fall within the scope of the EMC directive will meet the requirements of the relevant 
performance criteria as determined by the particular tests listed in the EMC standards. 
Products may temporarily be affected by the application of some electromagnetic disturbances but will return to published specification thereafter. Individual product details on 
request.
Directives - Dwyer Instruments, Inc. products are intended for installation by qualified 
personnel into a larger piece of equipment or system and are not accessible by the operator 
or that equipment or system under normal use. They do not contain any moving parts as 
defined by the Machinery Directive and do not fall within the scope of either the Machinery 
Directive or the Low Voltage Directive unless other stated. The responsibility for the final 
equipment or system lies with the builder of that equipment or system. It is the duty of 
the system designer or installation engineer to ensure that our products are used in 
accordance with our instructions and that current safety, wiring and other relevant regulations are followed.
For order entry, application, or customer service assistance,
Dwyer Instruments, Inc.
P.O. Box 373 
Michigan City, IN 46361 (USA) 
Phone: 219-879-8868/219-879-8000 
Fax: 219-879-9057
DS 10-6500-07 Rev. Jun-99
All Prices and Specifications subject to change without notice