Dwyer SC1490 User Manual

Loop Alarm™
Model SC1490 and SCL1490
INSTALLATION INSTRUCTIONS
LOVE CONTROLS
LOVE
®
December, 2004 Page 1 of 8 949-0531 Rev. 2
a Division of Dwyer Instruments, Incorporated
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
www.love-controls.com
Getting Started
1.) Using a small screwdriver, ball point pen, etc. set the Input Switch (SW-1) on the side of the unit for the input range to be used.
2.) Set the Output Switch (SW-2) for the output responses required (see Output Programming on page 4).
3.) Mount unit into panel. (see Mounting on page 5).
4.) Connect unit to input signal, output signal, and power wiring (see Wir­ing on page 5).
5.) Check calibration (See Calibration on page 6).
Operation description is on page 6 Specifications are on page 7.
Copyright © 2004 Love Controls Division, Dwyer Instruments, Inc. All rights reserved.
949-0531 Rev. 2 Page 2 of 8 December 2004
INPUT PROGRAMMING
Switches 1 through 6 on SW1 allow selection for RTD type.
Use the chart (Figure 1, below) to select the input type and range for your process. Turn on the appropriate switch(s) (as indicated) on SW1 for the input range desired.
Figure 1
December, 2004 Page 3 of 8 949-0531 Rev. 2
OUTPUT PROGRAMMING
Since the alarms can be set for reverse or direct action, high or low function, and has normally open and normally closed contacts; the number of combinations of actual output behavior is quite large.
First, decide how you want the outputs to behave. Will the relay energize or de-energize at the trip point? Will the relay trip on an increasing or decreasing signal? Is the dead band above or below the trip point?
It is important to answer these questions before setting up the mod­ule. The following Function Chart illustrates the most likely combi­nations of settings.
Function Chart
Figure 2
Using the Figure 3 (next page), set up the switches on SW2 for Alarm A and Alarm B. For dual alarm relays triggered by Alarm A, set switch 5 to DUAL. When switch 5 is set to DUAL (on), switches 6 and 7 have no effect.
949-0531 Rev. 2 Page 4 of 8 December 2004
Figure 3
WIRING
Mount on DIN rail and wire per Figure 5 below.
290-2888
MADE IN U.S.A.
LOVE CONTROLS
MICHIGAN CITY, IN 46361, U.S.A.
DIV. OF DWYER INSTRUMENTS, INC.
TM
MODEL:
S/N:
RTD
+
T/C,V
1
4
N.C.
ALARMA ALARMB
N.C.
7
10
POWER
&I
INPUT
2
5
COM
COM
8
11
3
6
N.O.
N.O.
9
12
For SC1490, power is 85 to 265 Vdc/Vac 50 to 400 Hz.
For SCL1490 power is 12 to 24 Vdc/Vac 50 to 400 Hz. ±20%.
Figure 4
W ARNING: Do not attempt to operate this de­vice with the cover removed. Potentially le­thal voltage is present on some of the internal components. Do not open the unit. There are no internal adjustments or user serviceable parts in the unit.
December, 2004 Page 5 of 8 949-0531 Rev. 2
ALARM CALIBRATION
12345678
ON
1234
ON
12345678
ON
NOTE: Allow the module and socket to come to stable temperature before proceeding. For best results, allow the module to be powered in the socket for at least 20 minutes.
Refer to Figure 5 when using the following proce­dure:
1. Apply the appropriate input for the desired
alarm trip point.
2. Adjust the alarm AL screw for relay trip (LED
changes color).
3. Adjust the alarm DB screw to the full clock-
wise position. Change the input to the de­sired reset point. Slowly tur n the alarm DB screw counter-clockwise until the rela y resets (Alarm LED changes back to original color).
4. Move the input back to the desired trip point
to confirm correct setting.
5. Move the input to the reset point to confirm
correct setting.
6. Repeat as necessary.
AL
B
RESET
A
DB
Figure 5
OPERATION
On power up the module will automatically reset the alarms provided that no alarm condition exists. It may be necessary to reset a low alarm after the process has reached normal conditions.
When the input is within set limits, both LED indicators will be green and the relay contacts will be in the state programmed for nor mal op­eration. If the input reaches either of the trip points, the relay con­nected to that trip point will change state and the LED connected to that point will indicate red.
When the input returns to normal (tr ip point plus dead band for low alarm settings, trip point less dead band for high alarm settings) and switch 4 of SW 2 is set to NON-LATCHING, the relay and LED will automatically return to the non-alarm condition. If switch 4 of SW 2 is set to latching, the red RESET button on the top of the module must be pressed to return the relay and LED to the non-alarm condition.
949-0531 Rev. 2 Page 6 of 8 December 2004
SPECIFICATIONS
Power Supply:
SC1090: 85 to 265 Vdc/Vac 50 to 400 Hz.
SCL1090: 12 to 24 Vdc/Vac 50 to 400 Hz. ±20% Isolation: 1500 V rms between outputs, input, and power. Set Points: Adjustable 0 to 100% of span. Deadband: Adjustable 0.25% to 100% of span. Drift: ±0.02% / °C typical, ±0.05% / °C maximum. Ambient T emperature Range:
Operating: 0° to 55° C (32° to 131° F)
Storage: -40° to +80°C (-40° to +176°F) Humidity Conditions: 0 to 90% up to 40 °C non-condensing, 10 to 50%
at 55 °C non-condensing. Excitation Current: Cu10 = 5 mA; Plt 100, Ni 100, Ni 120Ω =
500µA; Plt 500, NiFe 1000 = 100 µA; Plt 1000 = 50 µA.
Lead Compensation Error: ≈0.02%/Ω. Open Lead Protection: Upscale only. Relay output: SPDT, one per set point, 5A @ 250 VAC, resistive. Latch circuit reset: Automatic at power up. Manual with reset switch
on front of module.
Indicators: One dual color LED per set point. Red = relay on, green
= relay off.
DIMENSIONS
22.5
(0.886)
AL
B
75
RESET
A
All dimensions in millimeters (inches)
(2.950)
DB
(3.880)
9
12
8
11
7
10
December, 2004 Page 7 of 8 949-0531 Rev. 2
DIN EN 50022-35 (not supplied)
35.5
(1.40)
ADAPTER BRACKET FOR SURFACE MOUNTING (OPTIONAL)
KIT#: 1007-35DINADPTR
NOTES
949-0531 Rev. 2 Page 8 of 8 December 2004
Loading...