Loop Alarm™
Model SC1290 and SCL1290
INSTALLATION INSTRUCTIONS
LOVE CONTROLS
LOVE
®
December, 2004 Page 1 of 8 949-0530 Rev. 2
a Division of Dwyer Instruments, Incorporated
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
❍
❍
www.love-controls.com
❍
Getting Started
1.) Using a small screwdriver, ball point pen, etc. set the Input Switch
(SW-1) on the side of the unit f or TCB (Thermocouple Break) direction,
the thermocouple type, and the input range to be used.
2.) Set the Output Switch (SW-2) for the output responses required (see
Output Programming on page 4).
3.) Mount unit into panel. (see Mounting on page 5).
4.) Connect unit to input signal, output signal, and power wiring (see Wiring on page 5).
5.) Check calibration (See Calibration on page 6).
Operation description is on page 6
Specifications are on page 7.
Copyright © 2004 Love Controls Division, Dwyer Instruments, Inc. All rights reserved.
949-0530 Rev. 2 Page 2 of 8 December, 2004
INPUT PROGRAMMING
Determine the direction of the TCB (Thermocouple Break) and set switch 1
on SW1 to OFF for upscale action or ON for do wnscale action (See Figure 1).
Switches 2 through 5 on SW1 allow selection for thermocouple type.
Only one of these switches should
be on. Turning on more than one
of these switches may cause the
SC1290 to operate in an unpredictable manner .
For a type J thermocouple, turn on
switch 2.
For a type K or type T thermocouple, turn on switch 3.
For a type E thermocouple, turn on
switch 4.
For a type R or type S thermocouple, turn on switch 5.
Use the chart (Figure 2, below) to select the input type and range for your
process. Turn on the appropriate switch(s) (as indicated) on SW1 f or the input
range desired.
Figure 1
Figure 2
December, 2004 Page 3 of 8 949-0530 Rev. 2