Dwyer GSTA, GSTC Manual - GSTA

Page 1
Bulletin AQ-GSTA
3-23/64
®
Series GSTA Carbon Monoxide/Nitrogen Dioxide Gas Transmitters
Specications - Installation and Operating Instructions
[85]
3-45/64
[94.06]
3-1/8
[107.95]
4-17/32 [115.09]
5-7/64
[129.78]
2-15/64
[56.75]
3-59/64
[100]
Duct mountWall mount
2-55/64
[73]
2-15/64
[57]
The Series GSTA Carbon Monoxide/Nitrogen Dioxide Transmitters monitor the gas concentration in underground parking garages and loading docks. Carbon monoxide is commonly used to measure the exhaust of gasoline engines, while nitrogen dioxide is used for diesel engines. Field selectable current and voltage outputs allow the transmitter to be used with almost any building management controller. For carbon monoxide units, the user can adjust the output range to be 0 to 50 PPM up to 0 to 599 PPM. Nitrogen dioxide units come with a standard 0 to 10 PPM range. The output can be inverted to read 20-4 mA or 10 (5) to 0 VDC using internal dip switches.
To maximize the accuracy of the Series GSTA, the sensor can be eld-calibrated using
the A-449 remote LCD display. When the sensor reaches the end of its life, the display will indicate that the sensor needs to be replaced.
WARNING
accordance with the job wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.
CAUTION
CAUTION
CAUTION
designed for AC voltage operation.
NOTICE
replacements will not be covered under warranty, but they can be revived by allowing them to stabilize in an environment above 40% RH for 10 days. Once revived, they need to be recalibrated before use.
INSTALLATION
NOTICE
• The transmitter should be mounted at normal breathing height, approximately 5 to 6
ft above the oor.
• The unit may be mounted in the horizontal or vertical position. It should be mounted in an area that is shielded from direct contact with the elements or direct sunlight.
• Mount in an area that will prevent the sensor from having any direct contact with water.
• The unit should be placed in an area that will give an average of the air quality. Do not place the unit so it will receive direct engine exhaust. Prolonged exposure to direct engine exhaust may damage the sensor.
Disconnect power supply before installation to prevent electrical shock and equipment damage. Make sure all connections are in
Use electrostatic discharge precautions (e.g., use of wrist straps) during installation and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive moisture or corrosive fumes are present.
Do not exceed ratings of this device, permanent damage not covered by warranty may result. The 4-20 mA models are not
The electrochemical sensors should be stored in an environment with a minimum humidity level of 20% RH. If the sensor dries out,
These are general guidelines. Local laws or ordinances will take precedence.
SPECIFICATIONS
Sensor: Field replaceable electrochemical, 2 years typical lifespan. Range: CO: Switch selectable 200 or 500 PPM; NO
Output Drift: <5% per year in air.
Coverage Area: 5000 to 7500 sq ft typical.
Accuracy: CO: ±2% FS., NO Resolution: CO: 1 PPM; NO Temperature Range: -4 to 122°F (-20 to 50°C). Storage Temperature: For best sensor life, 32 to 68°F (0 to 20°C). Humidity Limits: 15 to 90% RH constant; 0 to 99% RH intermittent.
Response Time: <45 s to 90% CO, <25 to 90% NO
Span and Zero Adjustment: Via onboard push-buttons or using optional A-449 display.
Housing: UV resistant glass lled polycarbonate. Output Signals: Switch selectable 4-20 mA (loop powered), 0-5 V @ 5 mA, or 0-10
V @ 5 mA; Switch selectable 0-5 V/1-5 V and 0-10 V/2-10 V; Switch selectable normal or reverse output Power Requirements: Current output: 10-35 VDC; Voltage output: 15-35 VDC or 15-29 VAC.
Electrical Connection: Removable terminal block, knockouts for conduit tting. Calibration: Via onboard push-buttons (LCD model only) or using optional A-449
display. Span gas concentration is eld selectable.
Enclosure Rating: IP64.
Weight: 1 lb (.45 kg).
Compliance: CE.
MOUNTING
1. Remove the cover plugs from the face of the unit and the top cover.
2. Disconnect the display cable from the USB connector on the main circuit board (if present).
3. Remove the desired conduit tting knock out and install conduit tting (not
provided).
4. Position the transmitter where it is to be mounted and mark the mounting holes in each corner of the housing.
5. Drill or punch out marked locations.
6. Place the transmitter box over mounting holes on wall and align. Install wall mount screws (not provided) in mounting holes.
7. Proceed with wiring according to Figures 1 and 2.
8. Set DIP SWITCH and IOUT/VOUT SWITCH as desired. Refer to Figure 3.
9. Reconnect the LCD cable to the USB port on the main circuit board (if present).
10. Replace cover and cover plugs on the face of the unit.
2: ±3% FS, at the time of calibration.
2: 0.1 PPM.
2: 10 PPM.
2.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
Page 2
DUCT MOUNTING
RECEIVER
V OUT WIRING
RECEIVER
I OUT WIRING
CURRENT/VOLTAGE
H
MENU SWITCHES
SENSOR
Duct mounting kit includes an air ow pitot tube, air lter with barbed connections, two
short pieces of tubing and one long piece of tubing.
1. Mount the pitot tube into the duct observing the ow direction marked on the pitot
tube.
2. Attach the two short pieces of tubing to the barbed connections on each side of the
air lter.
3. Attach the remaining side of one of the short pieces of tubing to the barbed connection on the transmitter.
4. Attach the remaining side of the other short piece of tubing to the high port on the pitot tube.
5. Attach the long piece of tubing to the open barbed connection on the transmitter.
6. Attach the other end of the long tubing to the low port on the pitot tube.
SWITCH LOCATIONS
SELECT SWITCH
DIP SWITC
Figure 3
Setting the Current/Voltage Select Switch
To access the current/voltage select switch, remove the cover of the unit. The current/ voltage select switch is located on the circuit board as shown in Figure 3. Set the
switch to ˝IOUT˝ for current, ˝VOUT˝ for voltage.
DIP SWITCH Settings
To access the DIP SWITCH, remove the cover of the unit. The DIP SWITCH is located on the circuit board as shown in Figure 3.
ALL DIP SWITCHES ARE FACTORY SET TO “ON”.
WIRING
Use maximum 18 AWG wire for wiring terminals. Refer to Figure 1 or Figure 2 for wiring information. The terminal block is removable for ease of installation.
Wiring for 4-20 mA Output
4-20 mA output units may be powered by 10-35 VDC.
2
1
3
4
POWER SUPPLY
+
+
Figure 1
Wiring for 0-5 or 0-10 V output
The 0-5 or 0-10 V units may be powered by 15-35 VDC or 15-29 VAC. Note polarity when using DC power. The maximum load is 5 mA
(1 K Ω for 0-5 V or 2 K Ω for 0-10 V).
POWER SUPPLY
-
+
-
-
2
1
3
4
5 V / 10 V Output Select (Applies only to Voltage Output)
DIP SWITCH #1 OFF: Output = 0-5 V DIP SWITCH #1 ON: Output = 0-10 V
Zero Suppression (Applies only to Voltage Output)
DIP SWITCH #2 OFF: Output range = 1-5 V or 2-10 V, depending on output range DIP SWITCH #2 ON: Output range = 0-5 V or 0-10 V, depending on output range
Output Normal or Invert
DIP SWITCH # 3 OFF: Output is inverted DIP SWITCH # 3 ON: Output is normal
Menu Function (CO Model only)
DIP SWITCH #4 OFF: User ADJ (Output Range) DIP SWITCH #4 ON: Sensor calibration/range = 200 PPM
-
Figure 2
+
Page 3
"ADJ".
T
If the unit only requires zero calibration place the unit in an area that contains fresh air (no CO or NO2 gas).
In order to calibrate the span, hook up a model unit as shown in Figure 4. If CO model, set menu function switch to 200 ppm.
In the home position, the display reads actual gas concentration.
Place the unit in an area that contains fresh air (no CO or NO2 gas). minutes to stabilize.
ZERO CALIBRATION
USER ADJ as required.
To
calibration gas
VIEWING THE RANGE
NOTE: Requires auxilary display A-449. Hook up as shown in Figure
4. Upon power up the unit will momentarily display the range.
SPAN DIGIT
The range of the unit is factory set to 200 ppm CO. Also, the range is user adjustable to any value from 50 to 599 ppm CO. If dip switch is set to User ADJ, the factory setting is 100 ppm CO.
SETTING THE USER RANGE
NOTE: Requires auxilary display A-449. Hook up as shown in Figure
4. Set output range switch to "USER ADJ".
or
The range can be displayed at any time by pressing the span key for 5 seconds when in the home position.
A-507
calibration
adapter
SPAN DIGIT
ZERO
VALUE
SPAN DIGIT
Press the digit key to scroll through the digits. The digits will blink as they are selected.
Adjust the value of the digit using the value key.
When the desired range has been selected, press and hold the span key until the lower display reads "ADJ". Then the display will sequence to the home position.
Figure 4
ZERO
VALUE
Press and hold the zero key for 5 seconds.
SPAN AND ZERO CALIBRATION
A-449 auxilary display to the
SPAN
ZERO
Simultaneously press span and zero buttons for 5 seconds. The lower display reads “-0-”. The upper display reads “CAL”.
A-449
display
To adjust the display to set the desired span gas calibration value:
SPAN
DIGIT
ZERO VALUE
Hook the unit up to the span calibration gas using calibration adapter A-507 as shown in Figure 4. Span gas flow is to be between
0.5 to 1.0 slpm (1 to 2 scfh). Allow gas to flow for at least 3 minutes.
SPAN DIGIT
Display reads “CAL OK” for 5 seconds, then returns to home position.
Press the digit key to scroll through the digits. The digits will blink as they are selected.
Adjust the value of the digit using the value key.
Press and hold the span key for 5 seconds.
Simultaneously
SPAN
ZERO
DIGIT VALUE
press span and zero buttons for 5 seconds until the upper display reads
ZERO VALUE
Allow 3
Press the zero key for 5 seconds, the unit will sequence to span calibration and display the user set span calibration gas value. Factory setting is 200 ppm for CO,10.0 ppm for NO2.
If the sensor output is no longer sufficient for calibration, then the display reads “BAD SEN”. The sensor must be replaced.
NOTE: In calibration mode, if no key is pressed, then the unit will time out and return to home position after 10 minutes.
When calibration is complete, set menu function to 200 ppm or
Page 4
Sensor Replacement
A replacement sensor is available from Dwyer Instruments. For CO, order part number: A-505
2, order part number: A-506
For NO
WARNING
Replacing the Sensor
1. Remove the cover plugs from the face of the unit and top cover. Locate the sensor, see Figure 3 – the sensor is mounted on three pin sockets. The circuit board is labeled either “CO SENSOR” or “NO2 SENSOR” underneath the sensor.
2. Remove and discard the sensor.
3. Remove the shorting wire spring located on the bottom of the new sensor.
4. Install the new sensor into the three pin sockets.
5. The unit must be re-calibrated whenever a new sensor is installed.
6. Allow 30 minutes for the unit to come to temperature equilibrium prior to calibration. The unit has internal temperature compensation, and the sensor must be at the same temperature as the unit to calibrate properly.
TROUBLESHOOTING
Sensors contain acid. Do not attempt to open sensors. Sensors should be disposed of according to local laws.
Loop Resistance: The maximum allowable loop resistance depends on the power supply voltage. Maximum loop voltage drop must not reduce the transmitter voltage below the 10 VDC minimum. Maximum loop resistance can be calculated with the following equation. Vps is the power supply voltage.
-10.0
ps
Rmax =
Some receivers, particularly loop powered indicators, may maintain a xed loop
voltage to power the device. This voltage drop must also be subtracted from the power supply voltage when calculating the voltage margin for the transmitter. The following
equation takes this into account. Vrec is the receiver xed voltage.
Rmax =
0-10 V Output Models: Verify appropriate supply voltage. The 0-10 V output models require a DC supply of 15-35 V or an AC supply of 15-29 V for proper operation maximum. Maximum output load is 5 mA.
V 20 mA
-10.0-V
Vps
20 mA
rec
1. Verify that the unit is mounted in the correct position.
2. 4-20 mA Models: Verify appropriate supply voltage. The transmitter requires a minimum of 10 and a maximum of 35 VDC at its connection for proper operation. Choose a power supply with a voltage and current rating that meets this requirement under all operating conditions. If the power supply is unregulated, make sure voltage remains within these limits under all power line conditions. Ripple on the supply should not exceed 100 mV.
MAINTENANCE
Upon nal installation of the Series GSTA Transmitter and the companion receiver,
no routine maintenance is required with the exception of calibration. As with all electrochemical type gas sensors, routine calibration is required. It is recommended that units be re-calibrated at 6 month intervals, to maintain the published accuracy, or as required by local ordinances or other requirements. The units will maintain 5% accuracy if they are re-calibrated at 12 month intervals.
Except for sensor replacement and calibration, the Series GSTA is not eld serviceable and should be returned if repair is needed (eld repair should not be attempted
and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Printed in U.S.A. 3/22 FR# 443847-00 Rev. 10©Copyright 2022 Dwyer Instruments, Inc.
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
Loading...