Your GFC Mass Flow Controller was carefully packed in a sturdy cardboard carton, with anti-static cushioning materials to withstand shipping shock. Upon
receipt, inspect the package for possible external damage. In case of external
damage to the package contact the shipping company immediately.
1.2 Unpack the Mass Flow Controller
Open the carton carefully from the top and inspect for any sign of concealed shipping damage. In addition to contacting the shipping carrier please forward a copy
of any damage report to your distributor or Dwyer directly.
When unpacking the instrument please make sure that you have all the items indicated on the Packing List. Please report any shortages promptly.
1.3 Returning Merchandise for Repair
Please contact the customer service representative of your distributor or Dwyer if
you purchased your Mass Flow Controller directly, and request a Return
Authorization Number (RAN). Equipment returned without an RAN will not
be accepted. Dwyer reserves the right to charge a fee to the customer for equip-
ment returned under warranty claims if the instruments are tested to be free from
warrantied defects.
Shipping charges are borne by the customer. Items returned "collect" will
not be accepted!
It is mandatory that any equipment returned for servicing be purged and neutralized of any dangerous contents including but not limited to toxic, bacterially infectious, corrosive or radioactive substances. No work shall be performed on a
returned product unless the customer submits a fully executed, signed SAFETY
CERTIFICATE. Please request form from the Service Manager.
1
2. INSTALLATION
2.1 Primary Gas Connections
Please note that the GFC Mass Flow Controller will not operate with liquids. Only
clean gases are allowed to be introduced into the instrument. If gases are contaminated they must be filtered to prevent the introduction of impediments into the
sensor.
Caution: GFC transducers should not be used for monitoring OXYGEN
gas unless specifically cleaned and prepared for such application.
For more information, contact your distributor or Dwyer.
0
Attitude sensitivity of the Mass Flow Controller is ±15
flow path of the flow meter must be horizontal within those stated limits. Should
there be need for a different orientation of the meter, re-calibration may be necessary. It is also preferable to install the GFC transducer in a stable environment,
free of frequent and sudden temperature changes, high moisture, and drafts.
Prior to connecting gas lines inspect all parts of the piping system including ferrules and fittings for dust or other contaminants. Be sure to observe the direction
of gas flow as indicated by the arrow on the front of the meter when connecting
the gas system to be monitored.
Insert tubing into the compression fittings until the ends of the properly sized tubings home flush against the shoulders of the fittings. Compression fittings are to
be tightened according to the manufacturer's instructions to one and one quarter
turns. Avoid over tightening which will seriously damage the Restrictor Flow
Elements (RFE's)!
. This means that the gas
Compression fittings should not be removed unless the meter is being cleaned or
calibrated for a new flow range.
Using a Helium Leak Detector or other equivalent method perform a thorough
leak test of the entire system. (All GFC's are checked prior to shipment for leakage within stated limits. See specifications in this manual.)
2.2 Electrical Connection
GFC transducers require a +12VDC (+24VDC optional) power supply with a minimum current rating of 1100 mA to operate. The operating power input is supplied
via the 15-pin "D" connector located at the side of the flow transducer enclosure.
On GFC's purchased without an LCD readout, a readout panel meter, digital multimeter, or other equivalent device is required to observe the flow signal.
A built in SETPOINT potentiometer is supplied with all GFC transducers for local
control of the flow. A variable analog 0 to 5 VDC (or 4 to 20 mA) reference input
is required for remote control.
2
PINFUNCTION
1Flow Signal Common
20 to 5 VDC Flow Signal Output
3Common
4Open Purge
5Common, Power Supply
6(unassigned)
7+12 VDC (+24 VDC*) Power Supply
8Remote Setpoint
94 to 20 mA Return (Common)
10Common, Setpoint Signal
11+5VDC Reference for Remote Setpoint
12Valve Off Control
(Open Collector Compatible)
13+12 VDC (+24 VDC *) Power Supply
144 to 20 mA Flow Signal Output
15Chassis Ground
FIGURE 2-a GFC 15-PIN "D" CONNECTOR CONFIGURATION
*+24 VDC power supply configuration is optional for only GFC-110/111/113/114
models.
WARNING: DO NOT CONNECT 24Vdc POWER SUPPLY UNLESS
YOUR GFC CONTROLLER WAS ORDERED AND CONFIGURED
FOR 24Vdc
Important notes:
In general, "D" Connector numbering patterns are standardized. There are, however, some connectors with nonconforming patterns and the numbering sequence
on your mating connector may or may not coincide with the numbering sequence
shown in our pin configuration table above. It is imperative that you match the
appropriate wires in accordance with the correct sequence regardless of the particular numbers displayed on your mating connector.
Make sure power is OFF when connecting or disconnecting any cables in the system.
The power input is protected by a 1600mA M (medium time-lag) resettable fuse.
If a shorting condition or polarity reversal occurs, the fuse will cut power to the flow
transducer circuit. Disconnect the power to the unit, remove the faulty condition,
and reconnect the power. The fuse will reset once the faculty condition has been
removed.
Use of the GFC flow transducer in a manner other than that specified in this manual or in writing from Dwyer, may impair the protection provided by the equipment.
3
FIGURE 2-b, POTENTIOMETER AND JUMPER LOCATIONS
2.2.1 Valve Control Configuration
There are three basic valve control options. (a) LOCAL or REMOTE control; (b) 0
to 5 VDC or 4 to 20 mA setpoint signal - *note: this only applies for the REMOTE
control configuration; (c) 2% cutoff active or not active. NOTE: 2% cutoff not available for GFC 57 /67 /77. When active, the 2% cutoff will shut off the power to the
valve when a setpoint of less than 2% of the full scale flow range is set. Figure 22 shows the jumper configurations for the three basic valve control options.
The factory default jumper settings are: LOCAL control, 2% cutoff, and 0 to 5
VDC.
Function
0 to 5 VDC
4 to 20 mA
local
remote
2% cutoff on
2% cutoff off
2.2.2 Remote LCD Readouts
GFC Mass Flow Controllers are available with optional remote reading LCD displays supplied with a three foot long wire to accommodate most applications. This
configuration includes the upper block element which serves as the LCD readout
mounting. Special lengths of remote extension wiring (up to 9.5 feet [3 meters])
are available on request.
NJ1A
2 - 3
1 - 2
FIGURE 2-c, VALVE CONTROL CONFIGURATION JUMPERS
NJ1B
5 - 6
4 - 5
NJ1C
8 - 9
7 - 8
NJ1D
11 - 12
10 - 11
NJ1E
13 - 14
14 - 15
4
2.2.3 Panel Mounting Readouts
Another option for the GFC Mass Flow Controller is the Panel Mounting Remote
Readout.
In this configuration the LCD readout is supplied with a three foot long extension
wire, and no aluminum housing around the LCD. The LCD readout for panel
mounting includes a bezel with two plastic screws which conveniently fit into a rectangular cut-out for panel mounting (see Figure 2d).
FIGURE 2-d CUTOUT DIMENSIONS FOR LCD PANEL MOUNTING.
3. PRINCIPLE OF OPERATION
The stream of gas entering the Mass Flow transducer is split by shunting a small
portion of the flow through a capillary stainless steel sensor tube. The remainder
of the gas flows through the primary flow conduit. The geometry of the primary
conduit and the sensor tube are designed to ensure laminar flow in each branch.
According to principles of fluid dynamics the flow rates of a gas in the two laminar flow conduits are proportional to one another. Therefore, the flow rates measured in the sensor tube are directly proportional to the total flow through the transducer.
In order to sense the flow in the sensor tube, heat flux is introduced at two sections of the sensor tube by means of precision wound heater-sensor coils. Heat is
transferred through the thin wall of the sensor tube to the gas flowing inside. As
gas flow takes place heat is carried by the gas stream from the upstream coil to
the downstream coil windings. The resultant temperature dependent resistance
differential is detected by the electronic control circuit. The measured gradient at
the sensor windings is linearly proportional to the instantaneous rate of flow taking place.
An output signal is generated that is a function of the amount of heat carried by
the gases to indicate mass-molecular based flow rates.
GFC Mass Flow Controller models GFC-110/111/113/114 also incorporate a proportionating solenoid valve and models GFC-1143/1144/1145 a motorized valve.
The closed loop control circuit of the GFC continuously compares the mass flow
output with the selected flow rate. Deviations from the setpoint are corrected by
compensating valve adjustments, thus maintaining the desired flow parameters.
5
4. SPECIFICATIONS
FLOW MEDIUM: Please note that GFC Mass Flow Controllers are designed to work with
clean gases only. Never try to meter or control flow rates of liquids with any GFC's.
CALIBRATIONS: Performed at standard conditions [14.7 psia (1.01 bars) and 70
0
(21.1
C)] unless otherwise requested or stated.
0
F
ENVIRONMENTAL (per IEC 664): Installation Level II; Pollution Degree II.
ACCURACY: ±1.5% of full scale, including linearity for gas temperatures ranging from
0
59
F to 770F (150C to 250C) and pressures of 5 to 60 psia (0.35 to 4.1 bars).
REPEATABILITY: ±0.5% of full scale.
TEMPERATURE COEFFICIENT: 0.15% of full scale/
0
C.
PRESSURE COEFFICIENT: 0.01% of full scale/psi (0.07 bar).
RESPONSE TIME: GFC-110/111: 300ms time constant; approximately 1 second to
within ±2% of set flow rate for 25% to 100% of full scale flow.
GFC-113/114: 600ms time constant; approximately 2 seconds to
within ±2% of set flow rate for 25% to 100% of full scale flow.
GFC-1143/1144/1145:1800ms time constant; approximately 5
seconds to within ± 2% of set flow rate for 25% to 100% of full
scale flow.
GAS PRESSURE: 500 psig (34.5 bars) max; optimum pressure is 20 psig (1.4 bars).
MAX DIFFERENTIAL PRESSURE: 50 psid for GFC17/37/57/67/77, 40psid for GFC47.
GAS AND AMBIENT TEMPERATURE: 32
0
F to 1220F (00C to 500C).
RELATIVE GAS HUMIDITY: Up to 70%.
LEAK INTEGRITY: 1 x 10
-7
sccs He max to the outside environment.
ATTITUDE SENSITIVITY: No greater than ±15 degree rotation from horizontal to vertical;
standard calibration is in horizontal position.
OUTPUT SIGNALS: Linear 0 to 5 VDC (1000 Ω minimum load impedance) and 4 to 20
mA (50 to 500 Ω loop resistance); 20 mV peak to peak max noise for
GFC-110/111/113/114 and 100 mV peak to peak max noise for GFC-1143/1144/1145.
COMMAND SIGNAL: Analog 0 to 5 VDC (100 Ω input impedance) or 4 to 20 mA (0 to
250 Ω loop resistance).
Contact your distributor or Dwyer for optional RS232 or IEEE488 interfaces.
TRANSDUCER INPUT POWER: +12 VDC, 1100 mA maximum;
GFC-110/111/113/114 have an OPTION of +24 VDC, 650 mA maximum -
IF SPECIFIED AT TIME OF ORDERING AND CONFIGURED ACCORDINGLY.
6
WETTED MATERIALS:
GFC-110/111/113/114/ GFC-1143/1144/1145: 416 Stainless steel and 316 stainless steel
with VITON®O-rings seals; BUNA-N®, NEOPRENE®or KALREZ®O-rings are optional.
GFC-217/237/247/257/267/277: 416 Stainless steel and 316 stainless steel with VITON
®
O-rings seals; BUNA-N®, NEOPRENE®or KALREZ®O-rings are optional.
Dwyer makes no expressed or implied guarantees of corrosion resistance of mass flow
meters as pertains to different flow media reacting with components of meters. It is the
customers sole responsibility to select the model suitable for a particular gas based on
the fluid contacting (wetted) materials offered in the different models.
INLET AND OUTLET CONNECTIONS: GFC-110/111/GFC-113 -¹/₄" compression fittings.
Optional fittings are: 1/8" or 3/8" compression fittings and 1/4" VCR
®.
LCD DISPLAY: 3½ digit LCD (maximum viewable digits "1999"), 0.5 inch high characters.
On aluminum or stainless steel models the LCD display is built into the upper block element
and may be tilted over 90 degrees for optimal viewing comfort. Remote or panel mounting
remote reading is optional.
Standard readings are in direct engineering units for the given gas and flow rate (i.e. standard liters/minute [slpm], standard cubic centimeters/minute [sccm], standard cubic
feet/hour [scfh], etc.). 0 to 100% LCD calibration scaling is available upon request at time
of order. Contact your distributor or Dwyer when non-standard display settings are desired.
TRANSDUCER INTERFACE CABLE: Optional shielded cable is available mating to the GFC
transducer 15-pin "D" connector.
4.1 CE Compliance
Any model GFC bearing a CE marking on it, is in compliance with the below
stated test standards currently accepted.
EMC Compliance with 89/336/EEC as amended;
Emission Standard: EN 55011:1991, Group 1, Class B
Immunity Standard: EN 55082-1:1992
7
FLOW RANGES
Table I GFC-110/111 Low Flow Mass Flow Controllers*
codescc/min [N2]codestd liters/min [N2]
GFC-1101/2101
GFC-1102/2102
GFC-1103/2103
GFC-1104/2104
GFC-1105/21050 to 200
GFC-1106/21060 to 500
Table II GFC-113 Medium Flow Mass Flow Controllers*