Dwyer F7-SB, F7-SS2, F7-PP, F7-BT, F7-MPP F7 Manual

Series F7 Liquid Level Switches
C
B
EXTERNALLY
WELDED FLANGE
PIPE
ELBOW
PIPE
13/16 [20.62]
3-15/32 [88/09]
13/16 [20.62]
SWITCH CLOSED POSITION
POSITION
]
13/16 MIN
LEAD WIRES
A
1-7/32 MAX
[29.2]
Specications - Installation and Operating Instructions
Bulletin E-75
SWITCH ACTION (Normally open/Normally closed) Vertical Models
Vertical mount models are shipped with normally open switch contacts which close as
the oat rises toward the mounting threads. Reverse switch action by removing the oat, rotating it end-for-end and replacing it on the stem.
Contacts in horizontal models F7-HPS-1 (internal mount) and F7-HPS-2 (external mount), are normally open when the oat is down and normally closed when the oat is up. Models F7-HPS-1 and -2 also have indicating arrows on the stem end to conrm oat alignment. See installation notes on reverse. Horizontal model F7-HSS is in the normally open position when the indicating arrow points up, and normally closed when the arrow points down.
INSTALLATION
Choose a location away from ll pipes, drains, or other areas where turbulence or wave motion might occur. Turbulence will cause false actuations and shorten contact life. Excess contaminants in uid may inhibit oat operation and occasional wipe-down may be necessary. Care should be taken that switches are always operated within electrical ratings. Read and understand all safety precautions on back of this sheet before installing.
MOUNTING
Install vertical mount models in an appropriate 1/8˝ NPT tting. Vertical models mount internally, oriented within 30° of vertical, or select optional ttings for external mounting. Model F7-HPS-1 must be mounted internally, which means the switch must be secured to the wall of the tank or vessel from the inside. Install horizontal model F7-HPS-1 in a 5/8˝ (16 mm) hole and secure with nut provided. Tank wall should not exceed 1/8˝ (3 mm). Model F7-HPS-2 requires a horizontal 1/2˝ NPT(F) tting and can be tted to the tank or vessel from the outside. Model F7-HSS requires a horizontal 1/2˝ NPT(F) tting and can be mounting from the inside or outside (internally or externally) of the tank or vessel.
DWYER INSTRUMENTS, LLC
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
F7-SB
Dimensions, Inches [mm]
Model F7-SB
F7-SS2 F7-PP F7-BT F7-MPP
(A) Stem Length
2.75 [70]
2.06 [52]
2.18 [55]
2.18 [55]
1.63 [41]
(B) Float Diameter
1.13 [29]
1.0 [25]
1.18 [30]
1.18 [30]
0.63 [16]
(C) Float Height
1.38 [35]
1.0 [25]
1.0 [25]
1.0 [25]
0.63 [16]
(D) Actuation from HEX
1.0 [26]
0.73 [19]
0.69 [18]
0.69 [18]
0.47 [12]
FITTING
COUPLING
D
2-23/64 [59.92]
MAX
40∞ MAX
1-19/32
[40.46]
F7-HPS-2, EXTERNAL HORIZONTAL MOUNT F7-HPS-2, INTERNAL HORIZONTAL MOUNT
2 [50.80]
SPECIFICATIONS Electrical Rating (Maximum): F7-SB, SS2: Power: 50 W any combination of V and
A not to exceed 200 V (DC or AC peak) or 1.5 A (DC or AC peak); F7-PP, BT, HSS: AC: 30 VA, 0.14 A @ 200 V; DC: 0.28 A @ 24 V, 0.07 A @ 120 V. F7-MPP: 10 VA,
0.1 A @ 120 VAC; F7-MPP-NO: 50 VA, 0.2 A @ 240 VAC; F7-HPS: 15 VA, 1 A @ 220 VAC/DC. Mounting Connections: 1/8˝ NPT(M) (all vertical mount), 1/2˝ NPT(M) (F7-HPS-2, F7-HSS), M16 x 2 (F7-HPS-1). Wire Leads: F7-SB, SS2, PP, BT: 22 AWG x 18˝ (46 cm); F7-MPP, HSS: 22 AWG x 24˝ (61 cm); F7-HPS: 22 AWG x 39˝ (1 m). Enclosure Rating: F7-HSS: Explosion-proof, Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III. Weight: F7-SB, 2 oz. (58 g); F7-SS2, 1.2 oz. (34 g); F7-PP, 0.8 oz. (23 g); F7-BT,
0.7 oz. (20 g); F7-HPS-1, 1.5 oz. (43 g); F7-HPS-2, 2 oz. (57 g); F7-HSS, 3 oz. (94 g); F7-MPP, 0.8 oz. (23 g).
MODEL CHART
Model Vertical Mount F7-SB
F7-SS2
F7-PP
F7-BT
F7-MPP
Horizontal Mount F7-HPS
-1, -2 F7-HSS
*PBT - Polybutylene Terephthalate
Optional Fittings (for Exterior Mounting of Vertical Models) A-347, 1/8˝ x 1-1/4˝ NPT C.S. adapter. A-347-SS, 1/8˝ x 1-1/4˝ NPT 316 SS adapter. A-348, 1/8˝ x 1-1/2˝ NPT C.S. adapter. A-348-SS, 1/8˝ x 1-1/2˝ NPT 316 SS adapter.
CENTERLINE
A
APPROXIMATE
CTUATION LEVEL
3-7/16 [87.29]
1/2 NPT
SWITCH OPEN
Material Float/Stem
Buna-N and Epoxy/316 SS
316 SS (CYC)/316 SS
Polypropylene and Epoxy/Polypropylene Buna-N and Epoxy/PBT*
Polypropylene / Polypropylene
Polysulfone/ Polysulfone 316 SS/316 SS
Phone: 219-879-8000
Fax: 219-872-9057
3/32
[2.54]
3/4
[19.05
[31.0]
1-5/32 MAX
DIA. MAX.
1-33/64
[38.48]
4-5/8 MAX
[116.8]
F7-HSS
40∞ MAX
Max Temp.
220°F 105°C 300°F 149°C 220°F 105°C 220°F 105°C 176°F 80°C
185°F 85°C 392°F 200°C
www.dwyer-inst.com
e-mail: info@dwyermail.com
[20.6]
2-15/64 [56.74]
SWITCH CLOSED
POSITION
Max
Press.
150 psig 10 bar 450 psig 31 bar 100 psig
6.89 bar 150 psig 10 bar 100 psig
6.89 bar
150 psig 10 bar 300 psig
20.7 bar
Min S.G.
0.60
0.75
0.60
0.45
0.90
0.85
0.60
1/2-14 NPT
M16X2
SWITCH OPEN
POSITION
Approx. Deadband
1/16˝ 2 mm 1/16˝ 2 mm 1/8˝ 4 mm 1/8˝ 4 mm 1/8˝ 4 mm
3/16˝ 5 mm 1/8˝ 4 mm
22 AWG
Installation notes - Do not subject reed
Gasket seal for internal
ficient
hand-tight plus one half turn.
Do not exceed 1.5 pounds/
may cause premature switch
wiring entering the device is
or humidity condensate.
switch controls to excessive shock or vibration or any of the following:
• Bending or placing force loads on reed switch housing.
• Over-torquing ttings on reed switch housing.
• Placing pull-out force on lead wires.
foot (2 n/m) tightening
torque. Excessive torque
element or housing failure.
Indicating arrows are provided on the stem
ends to confirm float
alignment.
mounting units should be
preassembled before
insertion through tank wall.
Wall thickness should not
exceed 1/8˝ (3 mm).
When preparing wires for termination, avoid pulling
against the resin seal or
end plug of the float switch.
Avoid installations where
submerged or exposed to
excessive amounts of liquid
Units with tapered pipe
threads should be treated
with Teflon based thread
compound or tape before
insertion in fitting. Suf
torque is achieved at
CIRCUIT INFORMATION FOR REED SWITCH PROTECTION Read information below before installing your new reed switch control!
Exceeding the current capacity of this Reed Switch control may cause FAULTY OPERATION! Be aware of the inductive and capacitive or lamp loads you may be placing on you Reed Switch Control. The circuits below outline possible solutions to preventing overloads due to inrush or surge currents exceeding maximum or when the switch current and product of the inductive back EMF exceed the switch’s power rating. Also the circuit for prevention of overload when switching lament lamps (low “cold” resistance) is outlined below. Failure to follow these measures to protect Reed Switch Contacts may cause the contacts to weld together or result in premature wear.
Possible Circuit Solutions Indicated by Dashed Lines
RC SUPPRESSION
2
SWITCH
C
10
R
(1+50/E)
10*I
R
SWITCH
[uf]
C
Inductive loads
Possible causes -
An electromagnetic relay, electromagnetic solenoid, electromagnetic counter with inductive component as circuit load.
DIODE SUPPRESSION
DIODE
PIV DIODE > V
INDUCTIVE
LOAD
REED
SWITCH
VARISTER PROTECTION
INDUCTIVE
LOAD
REED
SWITCH
VARISTER
USED IN
AC CIRCUITS
INDUCTIVE
LOAD
REED
SWITCH
Capacitive loads
Possible causes -
A capacitor connected in series or
parallel with Reed Switch control. In a closed circuit, a cable length (usually greater than 50m [162.5 ft.])
used to connect reed switch may
also introduce static capacitance.
Lamp loads
Possible causes -
A tungsten lament lamp load.
SURGE LIMITER FOR
CAPACITANCE IN SERIES
+V
L =0.5~5 mH
P
R
A
L
P
C
REED
LOAD
SWITCH
CURRENT LIMITING RESISTOR
IN SERIES
+V R
L
V-0.12 R
R
2
SWITCH
RESISTOR PROTECTION
FOR CAPACITIVE LOAD
+V
R = 50~500 Ohms
R
REED
SWITCH
A
R
B
C
LOAD
R
CURRENT LIMITING RESISTOR
R
L
SWITCH
REED
SWITCH
+V R
5R > R
INDUCTIVE PROTECTION FOR
CABLE LENGTH CAPACITANCE
LOAD
CABLE LENGTH
OVER 50 METERS
IN PARALLEL
L
L
R
L
P
L = 0.5~5 mH
P
[162.5 FT]
REED
SWITCH
REED
SWITCH
DWYER INSTRUMENTS, LLC
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Printed in U.S.A. 4/23 FR# 440677-00 Rev. 6©Copyright 2023 Dwyer Instruments, LLC
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com