Dwyer Dwyer 490W-6-HKIT Manual

Series 490W Hydronic Differential Pressure Manometer -
5/8
®
Hydronic Application Software
Specications - Installation and Operating Instructions
5 Commonwealth Ave Woburn, MA 01801 Phone 781-665-1400 Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com
Series 490W Hydronic Differential Pressure Manometer is the most accurate and easy to operate manometer on the market. By using wireless transducers and a versatile handheld, a single operator can monitor and balance a hydronic system in less time than traditional hydronic balancers. The Series 490W utilizes mobile technology to communicate via a Bluetooth connection with the transducers to
means there are no hoses to carry, snag on equipment or needing to be drained. The 490W includes Dwyer’s Hydronic Application Software that contains valve charts for
screen.
INCLUDED WITH THE 490W
1. Handheld test instrument with Dwyer Hydronic App preloaded onto device
2. Pressure transducers (4 per kit) with case
3. Installation and operating manual
4. 1/4˝ SAE 45° x 1/4˝ Male NPT straight adapter (2 per kit)
5. 1/4” Female elbow x 1/4˝ Male NPT tting (2 per kit)
6. Piercing gauge adapters [2 per size] (6 per kit)
-1/8˝ DIA x 1-1/2˝ length
-1/8˝ DIA x 3˝ length
-1/16˝ x 1-1/2˝ length
7. 490W fabric carrying case
8. Piercing gauge adapters and ttings case (2 per kit)
9. Charger cable and power adapter for handheld test instrument
3-17/64 [83]
6-17/64
[159]
SPECIFICATIONS
Wireless Distance: Up to 65´ (19.8 m). Service: Compatible gases & liquids. Wetted Materials: 316 SS, PTFE, brass. Accuracy: 2% of reading, ±1 psi.
Compensated Temperature Range: 14 to 140°F (-10 to 60°C).
Pressure Hysteresis: ±0.25% FS.
Pressure Range: See chart. Process Temperature Limits: -4 to 185°F (-20 to 85°C).
Display: 5˝ Gorrilla
Resolution: 0.01 psi. Process Connections: Two 1/4˝ male NPT. Power Requirements: CR2050 or CR2032 lithium battery, user replaceable. Weight: 2 lb (907 g). Agency Approvals: CE, FCC.
®
glass 3, touch screen, 1280x720.
[16]
1.000
2.940
.944 HEX
MODEL CHART Model English Range Metric Range Maximum Range Available Engineering Units 490W-6-HKIT/NIST 0 to 50 psi, 0 to 200 psi 0 to 344.7 kPa, 0 to 1379 kPa 100 psi (6.89 bar), 400 psi (27.58 bar) psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. Replacement Transducers
A-490W-1 A-490W-2 A-490W-3 A-490W-4 A-490W-5 A-490W-6
0 to 15 psi
0 to 30 psi
0 to 50 psi
0 to 100 psi
0 to 500 psi
0 to 200 psi
1.034 bar
2.069 bar
3.447 bar
6.895 bar
34.47 bar
13.79 bar
30 psig 60 psig 100 psig 200 psig 1000 psig 400 psig
psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c. psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.
FEATURE OUTLINE
Headset speaker
Headphone connection with integral protective
rubber cap
Camera
Power/sleep
button
Backlit
touchscreen LCD
Handheld menu
button
OPERATION Powering On/Off
To turn on the handheld, press and hold the power button. Wait approximately 15
seconds for it to fully power on. Swipe to unlock the unit.
To turn off the unit, either press and hold the power/sleep button and press Power Off when prompted on the LCD or press the reset button.
Handheld Battery
The universal handheld utilizes an internal rechargeable battery. The battery symbol in the top right of the screen shows the status of the battery.
TRANSDUCER BATTERY INSTALLATION
The unit is shipped with a CR2050 lithium battery installed. To replace battery, unscrew
black top cap from transducer. T ilt transducer to remove old battery. Install new battery and replace top cap.
Handheld back
button
Handheld home
button
Figure 1
Volume buttons
NOTICE
the battery is low, the battery symbol will turn red. When this occurs, use the included USB charging cable and charging power adapter to recharge the unit.
NOTICE
When the 490W is received, the handheld test instrument will only have a partial charge. Be sure to fully charge before using. When
The handheld test instrument comes factory paired to the included wireless pressure transducers.
Rugged protective housing
Speaker
Hand strap clip
NOTICE
necessary, use only a CR2050 or CR2032 type such as a Sony CR2050W or
CR2032W.
Note: Do not use Murata batteries.
Low Battery Indicator
A weak battery can cause improper operation or inaccurate measurements. The unit is supplied with a battery that can last up to 2 years, depending on usage. When
transducers are sent in for annual recertication, the battery will be replaced.
Battery life depends on its capacity, operating temperature and signal transmission interval. When battery replacement becomes