Bulletin DA-DW-USB-LCD
Green double fl ash
Every 20 seconds: logger full, no alarm
Green single fl a sh
Every 30 seconds: delayed start
Every 20 seconds: low battery, logging, no alarm
Every 10 seonds: logging, no alarm
Red/Green single fl ash
Every 20 seconds: logger full, last value equal to
Red double fl ash
Every 10 seconds: logging, high alarm
Every 20 seconds: logging, high alarm, low battery
Red single fl as h
Every 10 seconds: logging, low alarm
Every 20 seconds: logging, low alarm, low battery
No LEDs fl ash
LEDs disabled during configuration to save battery
power and increase logging life/logger stopped/
battery empty
DW-USB-6-LCD
DW-USB-2-LCD
DW-USB-2-HA-LCD
Green triple fl ash
Logger full, no alarm on the channel
Red triple fl as h
Logger full, alarm on the channel
Green double fl ash
Delayed start
Green single fl ash
Logging, no alarm
Red single fl as h
Logging, low alarm on the channel
Red double fl ash
Logging, high alarm on the channel
No LEDs fl ash
Logger stopped or batter y empty
or exceeds the low or high alarm
X
1
-1/16
[
26.99]
1
-3/64
[
26.59]
Y
L
ED
MODEL DW-USB-X
L
CD
S
CREEN
FUNCTION
BUTTON
M
ODEL DW-USB-X-LCD
LED
Series DW-USB-LCD Compact USB Data Logger With Display
Specifications - Installation and Operating Instructions
odel
M
DW-USB-2-LCD
DW-USB-2-HA-LCD
DW-USB-6-LCD
Overall Length (X)
4-31/32˝
-31/32˝
4
-19/64˝
5
Base Length (Y)
4-57/64˝
-57/64˝
4
5-15/64˝
Body/Clip
Vented No
clip
ented No
V
clip
Plug No
n bottom clip
i
Cap
Transparent
ransparent
T
Transparent
LED
Red/Green
ed/Green
R
Red/Green
The portable Series DW-U SB-LCD USB Data Loggers displays and r ecords
temperature, humidity and dew point. The easy-to-read LCD display shows the current
temperature or humidity along with the minimum and maximum reading since last
reset. For applications that require more accuracy, a high accuracy temperature and
humidity model is available. Thermocouple models can accept any J, K, or T type
thermocouple with a mini-plug connector. Series DW-USB-LCD data loggers use a
free downloadable a Windows
®
based software which allows selection of the sampling
rate, start time, high/low alarm settings, and temperature unit application. For quick
downloading of data, the data logger can be plugged directly into a PC’s USB port
with no cable required. Downloaded data can then be graphed, printed, or exported
to other spreadsheet applications.
OPERATING INSTRUCTIONS
LED FLASHING INDICATORS
SPECIFICATIONS
Range:
DW-USB-2-LCD: Temperature: -31 to 176° F (-35 to 80°C);
Humidity: 0 to 100% RH;
DW-USB-2-HA-LCD: Temperature: -31 to 176° F (-35 to 80°C);
Humidity: 0 to 100% RH;
DW-USB-6-LCD: K-type: -328 to 2372°F (-200 to 1300°C), J-type: -202
to 1652°F (-130 to 900°C), T-type: -328 to 662°F (-200 to 350°C).
Accuracy:
DW-USB-2-LCD: Temperature ±1°F (±0.5°C) Humidity ±3.0%;
DW-USB-2-HA-LCD: Temperature ±0.6°F (±0.3°C), Humidity ±2.0%;
DW-USB-6-LCD: ±2°F (±1°C).
Resolution: Temperature: 1°F (0.5°C); Humidity: 0.5% RH.
Memory Size: Thermocouple models: 32510 readings; Temperature/humidity
models: 16382 readings.
Sampling Mode: Continuous with data rollover.
Sampling Rate: Selectable from 10 seconds to 12 hours for
temperature/humidity models; 1 second to 12 hours for thermocouple models.
Display: 2.5 digit LCD.
Computer Requirements: Windows
®
2000, Windows
®
XP, Windows VISTA
®
32-bit
operating systems.
Power Requirements: 3.6 1/2 AA battery (included).
Housing: ABS plastic blend.
Alarms: Programmable high/low.
Interface: USB port.
Weight: Temperature/humidity models 1.6 oz (45.4 g); Thermocouple models 1.8
oz (51 g).
Agency Approval: CE, RoHS.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Phone: 219/879-8000 www.dwyer-inst.com
CD INDICATORS
Last
temperature reading
Highest logged
t
emperature reading
Highest logged
humidity reading
L
owest logged
humidity reading
L
owest logged
temperature reading
Last logged
h
umidity reading
Temperature
scale
Relative Humidity
symbol
M
inimum logged
v
alue symbol
M
aximum logged
value symbol
R
eading
Negative symbol
T
emperature scale symbols
M
aximum/Minimum
logged value symbol
LCD INDICATION
Display Logger Status Explanation
Delayed Start
Push to Start
L
ogging
Stopped
This is shown when the logger is set to
start at a specific date and time*
T
his is shown when the logger is setup for
“Push to start” logging
T
his is shown when the logger is running
in “LCD off” mode, and the button is
p
ressed. The display clears again after
three seconds.
If the logger has not been set to log and
the button is pressed, three dashes are
displayed for three seconds
Otherwise the display will remain blank.
DISPLAY AND STATUS FUNCTIONS
LCD INDICATION
DW-USB--2-LCD
DW-USB-6
-LCD
the button is pressed.
*If the logger is set to “LCD off” or “LCD on for 30 seconds” mode, then this will be shown after
L
UTTON OPERATION
B
The button performs two functions:
1. To start the logger when in push to start mode.
2. To enable the display and cycle through the available display modes (see diagram
below).
f the button is not pressed for 30 seconds. The LCD disables and the logger returns
I
o the beginning of the display cycle.
t
OFTWARE INSTALLATION
S
his software must be installed prior to the USB Driver. Please follow the instructions
T
below then refer to the USB Driver Installation based on the Windows
®
operating
system you are using.
. Visit our website www.dwyer-inst.com/DW-USBSoftware and click on the
1
ownload link. If the download folder doesn’t open directly, go to your computer’s
d
Downloads” folder and double-click on the “EasyLogUSBV610_Dwyer” folder.
“
. Double-click on “setup” then follow the on screen instructions to complete the
2
Configuration Software Installation.
3. An EasyLog USB icon will now be placed on your desktop.
SB DRIVER INSTALLATION
U
indows
W
®
P/Windows Vista
X
®
:
You must install the Configuration Software as instructed in the previous section
before going through these steps.
. Insert the USB data logger directly into a USB port on the computer. Installation
1
creens should automatically appear.
s
2. Follow the on screen instructions to complete the Configuration Software
Installation. If a compatibility error window appears, click “Continue Anyway”. This
will not cause any adverse changes/effects on your computer.
3. You can now begin using our data logger by double clicking on the EasyLog USB
con on your computer ’s desktop.
i
®
indows
W
2
000:
You must install the Configuration Software as instructed in the previous section
before going through these steps.
BATTERY INSTALLATION
Before using the data logger, you will need to insert the 3.6 V 1/2 AA battery provided,
following the instructions below.
1. Use screwdriver to gently depress tab of the battery compartment.
2. Pull battery cover towards you, away from the unit.
3. Install the battery, taking note of polarities.
4. Replace battery cover. Cover is secure when tab returns to original position.
. Insert the USB data logger directly into a USB port on the computer. Installation
1
creens should automatically appear.
s
2. Follow the on screen instructions to complete the USB Driver Installation.
3. You can now begin using our data logger by double clicking on the EasyLog USB
icon on your computer ’s desktop.
MAINTENANCE
Upon final installation of the Compact DW-USB-LCD Data Logger, no routine
maintenance is required. Leaving the logger plugged into your computer for an
extended period of time will considerably lower its battery life. A periodic check of
system calibration is recommended. The Series DW-USB-LCD is not field serviceable
and should be returned if repair is needed (field repair should not be attempted and
may void warranty). Be sure to include a brief description of the problem plus any
relevant application notes. Contact customer service to receive a return goods
authorization number before shipping.
©Copyright 2013 Dwyer Instruments, Inc. Printed in U.S.A. 9/13 FR# R6-443584-50 Rev. 1
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Windows® and Windows Vista® are registered trademarks of Microsoft Corporation.
Phone: 219/879-8000 www.dwyer-inst.com