Dwyer BPS-005 User Manual

Bulletin PC-BPS-005
SNAPTRACK
4-1/16
[103.12]
2
-19/64
[
58.17]
1-15/16
[49.02]
1
1/16
[
17.27]
OUTPUT
VOLTAGE
ADJUSTMENT
REGULATED DC VOLTAGE
OUTPUT
LINE VOLTAGE
TRANSFORMER
J1 J2
J3
24 VAC IN
MODEL BPS-005
MODEL BPS-015
2-13/32
[61.19]
3
[76.20]
2
-1/16
[
52.28]
1
9/32
[
14.97]
4
-1/16
[
103.12]
2
-19/64
[
58.17]
1
-15/16
[
49.02]
11/16
[17.27]
Series BPS Low Cost DC Power Supply
Specifications - Installation and Operating Instructions
The Series BPS Building Automation Power Supply is used to convert
24 VAC to a regulated DC power source for transmitters with 4 to 20 mA outputs. The output voltage can be field adjusted from 1.5 VDC to 29 VDC using a potentiometer. The 1 A or 3 A fuse (depending on model) protects the power supply from over-current conditions. The snap-on bracket can be quickly surface mounted to any flat surface.
rent
CAUTION
.
To prevent overheating, the output current must not exceed the ratio of the output voltage to the input voltage times the rated cur-
Example: For output voltage set at 5 VDC, the output current should not exceed 313 mA. (5V/24V) x 1.5A = 0.313A
Isolation: If the DC ground is connected to the AC ground, the fuse will open. If the AC and DC circuit grounds cannot be isolated, move the shorting jumper from J1 to J2 and add a shorting jumper to J3. In this case the out­put current is limited to 400 mA
NOTICE
and “-” on the output and cut one of the leads on diode (D3). On BPS-015, move jumper from “J1” to “J2” amd short jumper “J3”. Output is reduced to 200 mA on the BPS-005 and 400 mA on the BPS-015.
For applications where the input and output share the common or ground, add a jumper on BPS-005 between “G” on the input
SPECIFICATIONS Input: 24 VAC/VDC 50/60 Hz. Output: 24 VDC (full wave rectified and regulated) adjustable 1.5 to 29
VDC.
Maximum Current Output: 1.5 A or 0.5 A (depending on model). Over-Current Protection: 1 A fuse. Operating Temperature: 32 to 130°F (0 to 55°C). Humidity Limits: 95% (non-condensing). Weight: 0.4 lb.
Agency Approval: RoHS.
WIRING DIAGRAM
©Copyright 2012 Dwyer Instruments, Inc. Printed in U.S.A. 2/12 FR# R6-443738-00
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Phone: 219/879-8000 www.dwyer-inst.com