Dwyer BFM User Manual

Bulletin FL-1-BFM
4x 3/4˝ CONDUIT KNOCKOUTS
5-9/64 [130.45]
TRANSFORMER
3[76.20]
6X 1/2˝ CONDUIT KNOCKOUT
1-19/32
[40.64]
1/2
[12.69]
3/32
[2.29]
3
[76.20]
1-1/2
[38.10]
FLOW SENSOR
6´ 18 AWG
WIRE
SENSOR
TIP
PRODUCT LABEL FOR MAIN CONTROLLER UNIT
7
[177.80]
GREEN
LED
1A FUSE
RED LED
RELAY
SENSITIVITY ADJUSTMENT
POTENTIOMETER
BFM FLOW MONITOR
Series BFM Bulk Flow Monitor
Specifications - Installation and Operating Instructions
BFM
Series BFM Bulk Flow Monitor provides effective
monitoring for most flow/no flow conditions in pipes and chutes. It’s sensing techniques, which use a Piezo element, makes the BFM versatile for most flow/no flow applications.
BFS
SPECIFICATIONS BFM Specifications Service: Solids and liquids. Power Requirement: 120VAC, 220VAC or 12VDC. Power Consumption: .1A.
The BFM Control offers many unique advance features
that exceed the industry standards. The BFM Central Processing Unit monitors movement of almost anything through a pipe or chute system. The BFM is ideal for sensing the presence or absence of materials in Pneumatic Conveying Systems. The BFM offers adjustable sensitivity depending on the application demand. Also, it provides easy installation and requires no maintenance. The unit has L.E.D indicators – flow (green)/ no flow (red).
Temperature Limits: 120°F (48.9°C). Output: Relay: SPDT rated 4A @ 125/250VAC, 1/10 HP
@ 125/250VAC, 3A @ 30VDC. TTL: 0-5 V.
Serial Communications: RS-232. Electrical Connection: Screw Terminal. Conduit Connection: Knockouts (two 3/4˝ for power,
three 1/2˝ for sensor and outputs).
Enclosure Rating: NEMA 4. Material: Polycarbonate. Weight: 3 lbs (1.36 kg).
The BFS-1 Sensor yields many advance features. It
externally mounts to the outside of the pipe or chute. It provides mounting tabs for easy installation. The Sensor is prewired with 3´ wire.
BFS Specifications Pipe Size: 1/2˝ to 60˝ (1.27 to 152.4 cm). Enclosure Rating: NEMA 4. Electrical Connection: 3´ (0.9 m) of 18 gauge wire.
Series BFM has many practical applications. You can use it to monitor Oil Spray Systems, Discharge Chutes, Distributors, Screw Conveyors, Drag Conveyors, Water Systems, Air Systems, Pneumatic Systems, Gravity Feed Systems, Slurry Systems, Chemical Processing, Food Processing and Rotary Drums.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Part Number BFM-1 BFM-2 BFM-3 BFS-1
Temperature Limits: 155°F (68.3°C). Materials: PVC Type 1 Grade 1 Grey. Weight: 5 oz (141.8 g).
Descriptions
Control Unit: NEMA 4X, Polycarbonate Housing, Weatherproof, 120VAC Control Unit: NEMA 4X, Polycarbonate Housing, Weatherproof, 220VAC Control Unit: NEMA 4X, Polycarbonate Housing, Weatherproof, 12VDC Sensor
Phone: 219/879-8000 www.dwyer-inst.com
3/4˝ HIGH
VOLTAGE INPUT
1/2˝ LOW
VOLTAGE INPUT
BFM WIRING
The BFM polycarbonate housing comes with 10 PG conduit knockouts in the housing.
• High voltage inputs above 24 volt AC should be routed into the housing through the 3/4˝ (20mm) conduit hole.
• All Low voltage wiring (TTL, RS232, and sensor) should be routed through the 1/2˝ (14mm) conduit hole.
• A 1-Amp fuse is located next to the transformer .
Figure 3
Figure 1
HIGH VOLT AGE INPUTS
Connect the 120VAC, 50/60 HZ, 1 Amp supply on TB2 terminals (Fig. 2):
• 120VAC (Hot) supply to 117V AC terminal (or 12VDC, 240V AC
per the model)
• AC Common to AC COM terminal
• Earth-Ground to E GND terminal. Must connect to prevent accidental electrical shock.
SENSOR INPUTS
Connect the low voltage Flow Sensor to the Sensor terminals TB1 (Fig. 4):
• Positive RED (or White) sensor lead to the “+” Sensor terminal on TB1.
• Negative BLACK sensor lead to the “-” Sensor terminal on TB1.
The sensor wiring should be a minimum of 18 AWG strand­ed 2-conductor cable. Use 18 AWG for up to 500´ (155m) and 16 GA up to 2000' (620m).
• All Sensor wire splices must be SOLID and WATER TIGHT.
Figure 2
Figure 4
RELA Y AND LOW LEVEL LOGIC WIRING
SIDE VIEW FRONT VIEW
BFM
SENSOR
BFM
SENSOR
NOTE: PILOT HOLES
ARE DRILLED INTO
FLAT SURFACE AND
MOUNTED WITH
PORPER HARDWARE.
See those sections later in this manual.
SENSOR INST ALLATION
The BFS-1 sensor is in very a rugged polymer housing with a sealed 6´ cable pigtail (Fig. 5):
• Red/Black = Positive
• White/Black = Negative (this is electrically connected to the metal sensor stud)
BFM SENSOR
BLACK LEAD
Figure 6
MOUNTING TO A ROUND OR NON-FLAT SURFACE: (FIG. 7)
• Using strapping (such as heavy duty wire-ties) or clamps to secure the sensor housing to the pipe so the metal sensing
stud makes firm contact with the surface.
RED/WHITE LEAD
Figure 5
MOUNTING PROCEDURES FOR SENSOR:
The BFS-1 Sensor can be screwed, clamped or strapped in place and is able to detect flow through most sheet metal.
• Clean the surface area where the sensor is to be installed. The surface should not have any buildup or scale but does be perfectly clean.
• The sensor stud located at the bottom of the sensor housing must make solid contact with the surface of the pipe to be monitored.
MOUNTING TO A FLA T SURFACE:
Refer to the mounting holes located at each end of sensor housing (Fig. 6).
• Mark mounting holes.
• Drill pilot holes for mounting screws.
• Screw sensor housing to flat surface.
BFM
SENSOR
SIDE VIEW FRONT VIEW
NOTE: STRAPS
OR CLAMPS ARE USED FOR MOUNTING TO
NON-FLAT
SURFACE
Figure 7
BFM
SENSOR
SENSOR LOCA TION:
BE SURE SENSOR STUD
IS MAKING A GOOD TIGHT CONTACT WITH MOUNTING SURFACE.
STUD SENSOR
INPUT
PUMP
TO ENHANCE SENSITIVY INSTALL THE SENSOR WHERE THE FLOW IS MOST TURBULENT OR WHERE MA TERIAL IMPACTS THE PIPE WALL.
THE FOLLOWING POINTS ARE IDEAL (FIG 8):
• Pipe elbow
• Point where material drops into spouting or chutes
• Point where material drops from conveyor onto the chute
TTL LOGIC OUTPUT :
The TTL Logic output is a 5VDC output. To obtain a TTL Logic Output install jumper J3 as indicated
on the BFM PCB. Connect logic level output wiring to the “Out” (+5V) terminal and the Sensor “-” (0V) terminals on TB1.
• NO FLOW: Red LED lights and 0VDC will be present at the “OUT” terminal.
• FLOW: Green LED will light and 5VDC will be present at the “OUT” terminal.
RS232 LOGIC OUTPUT :
The RS232 output is an industry standard 5VDC minimum into 3K load. T o obtain an RS232 logical output do not install jumper J3 as indicated on BFM PCB.
• NO FLOW: Red LED lights and 0 VDC will be present at the "OUT" terminal.
• FLOW: Green LED will light and 5VDC min. will be present at the "OUT" terminal.
Figure 8
LOW LEVEL (LOGIC) OUTPUT WIRING
Low level outputs available (Fig. 9):
• TTL logic output
• RS232 logic output
NOTE: For proper logic input to your computer, consult your computer manual for the correct pin configuration for RS232 or TTL.
RELA Y OUTPUT WIRING Relay (CTR1) Contact Specifications:
• 4 amp at 125 or 250 VAC
• 1/10 HP at 125 or 250 VAC
• 3 amp at 30 VDC
Relay Output Wiring on TB2 (Fig. 10):
• COM = Common contact
• N/C = Normally closed
• N/O = Normally open
Figure 9
Figure 10
SOUNDING AN ALARM TO INDICATE DECREASED
STOP
START
STARTER
COIL
NORMAL STARTER CIRCUIT
STOP
START
STARTER
COIL
TB2
COM
N / 0
M / C
STARTER CIRCUIT WITH BFM SHUTDOWN
FLOW:
Before the “controlled” equipment can be started again, the following must occur:
An alarm will sound when flow drops below the preset amount (Fig. 11):
• When flow drops the relay contacts close to energize the alarm.
• The power to the alarm (connected to the COM terminal) is from the motor starter circuit so the alarm can only sound when the motor is running. When the motor Stop button is pressed the alarm will silence.
START
MACHING
SUPPLYING
MATERIAL
NOTE: AUXILLARY SET OF
NORMALLY CLUSED
CONCACTS (CLOSED WHEN
STARTER IS ENERGIZED).
MOTOR
STARTER
SWITCH
117VAC
ALARM
TB2
COM
N/0
N/C
AC COM
Figure 11
SHUTTING DOWN EQUIPMENT WHEN FLOW DECREASES:
• Material is flowing past the BFS-1 sensor .
• The Green L.E.D. (FLOW) indicator light is lit indicating material flow.
• Y ou may have to hold down the Start button until flow reaches the preset rate.
As long as material continues to flow past the BFS-1 sensor above the preset rate, the machine equipment supplying mate­rial will continue to run. If the rate of material flow falls below the preset level, the relay will open and the machine equip­ment supplying the material will stop.
Figure 13
Equipment shut down mode is required if the flow rate drops below the preset level. The relay is often wired to stop the equipment that is supplying the material (Fig. 12 and 13).
Figure 12
SENSITIVITY RANGE ADJUSTMENT AND CALIBRA­TION
The BFM has (3) three sensitivity range inputs. Select the range to get the desired sensitivity for the application.
WARNING: TO AVOID ELECTRICAL SHOCK DISCONNECT AC SUPPL Y VOLTAGE BEFORE ADDING OR REMOVING JUMPERS ON TB1.
• Minimum (low) range: Install jumper J2 (only)
• Medium range: No jumpers installed (as shipped from factory)
• Maximum (high) range: Install jumper J1 (only)
ADJUSTING THE SENSITIVITY RANGE:
NOTE: The sensitivity range is factory preset to the Medium range (no jumpers installed). Verify that the supply voltage and the flow sensor are wired and installed correctly prior to test­ing (Fig. 14). After selecting proper sensitivity range, proceed to the next calibration section.
1. With no material flowing, turn the Sensitivity adjustment to
full clockwise position:
• RED LED will turn on.
2. Start the material flowing at the full rate you wish to moni-
tor:
• If the GREEN LED turns on, then turn the Sensitivity adjust-
ment fully counterclockwise. If that causes the RED LED to turn on then the correct sensitivity range is selected. If that does not cause the RED LED to turn on (Green stays lit) then install jumper J2 (Minimum range) and repeat the test begin­ning with step #1.
• If the GREEN LED does not turn on when material is flow-
ing, then install jumper J2 (Maximum range) and repeat the test beginning with step #1.
Figure 14
BFM CALIBRA TION:
Perform sensitivity range jumper selection before performing calibration.
1. Stop all material from flowing.
2. T urn the Sensitivity adjustment fully clockwise.
3. Start material flowing at the minimum full flow rate desired
• GREEN L.E.D. will light to indicate FLOW .
4. T urn the Sensitivity adjustment counter clockwise until the
RED LED lights to indicate NO FLOW .
5. Turn the Sensitivity adjustment clockwise very slowly until
GREEN LED lights to indicate FLOW .
6. Calibration is now complete.
FINAL SYSTEM CHECK:
• Stop or reduce flow of material and the GREEN LED (FLOW)
will go out and the RED LED (NO FLOW) will light.
MAINTENANCE
Upon final installation of the Series BFM Bulk Flow Monitor, no routine maintenance is required. A periodic check of system calibration is recommended. The Series BFM is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
©Copyright 2008 Dwyer Instruments, Inc. Printed in U.S.A. 12/08 FR#R2-443673-00
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Phone: 219/879-8000 www.dwyer-inst.com
Loading...