Series AVPT Pencil Style Air Velocity Transmitter
Specications - Installation and Operating Instructions
Bulletin AQ-AVPT-A
10 [254]
6˝ probe length 12˝ probe length
The Series AVPT Pencil Style Air Velocity Transmitter uses thermal anemometer
technology to provide high accuracy and stable air velocity measurements in imperial
and metric units. The Series AVPT can be congured with either a voltage output or
BACnet MS/TP communication to provide universal inputs to a variety of monitoring
equipment. Models are available with xed cable lengths of 20 or 78 inches with ying
leads or a 5-pin M12 connector on a 24 inch cable. Probes are available in lengths
of 6 or 12 inches. A mounting ange included with the product provides the ability to
vary insertion depth.
Models are available in 3% or 5% accuracy to suit a variety of applications, while the
optional BACnet MS/TP communication protocol allows units to be daisy-chained to
provide access to all of the velocity and temperature measurements.
MODEL CHART
Example AVPT -S 03 C1 A 06 127 -FC AVPT-S03C1A06127-FC
Series AVPT Pencil style air velocity
Accuracy S
H
Velocity
Range
Electrical
Connection
Output Type A
Probe
Length
BACnet
Address
Options FC
01
02
03
04
05
10
15
20
C1
C2
M1
B
06
12
127 000-127 whole integer
transmitter
Standard ±5% of reading
+40 FPM
High accuracy ±3% of
reading +40 FPM
1000 FPM
2000 FPM
3000 FPM
4000 FPM
5 m/s
10 m/s
15 m/s
20 m/s
Cable whip 20˝ (0.5 m)
Cable whip 78˝ (2 m)
M12 24˝ (0.6 m)
Analog 0-5 V and 0-10 V
BACnet MS/TP
6˝
12˝
with BACnet output
Factory calibration
certicate
NIST
NIST traceable certicate
16 [406]
SPECIFICATIONS
Service: Clean air.
Ranges: 1000, 2000, 3000, or 4000 FPM (5, 10, 15, or 20 m/s); Model specic.
Accuracy: Standard: ±(5% reading +40 FPM); High accuracy: ±(3% reading +40
FPM); Model specic.
Power Requirements: 24 VAC/VDC ±20%.
Current Consumption: < 50 mA.
Outputs: Analog: 0-10 V (0-5 V congurable).
BACnet MS/TP: Selectable at time of order.
Supported Baud Rate: 9600, 19200, 38400, 57600, 76800, and 115200.
Voltage Output Load Resistance: 10k Ω minimum (10 V output with AC supply);
1k Ω minimum all other conditions.
Electrical Connection: Cable: Plenum rated cable with 22 AWG conductors.
5-Conductor Cable whip: 20˝ (0.5 m) or 78˝ (2 m).
5-pin M-12: 24˝ (0.6 m); model specic.
Response Time (90%): 4 s, typical.
Operational Temperature Limits: -4 to 140 °F (-20 to 60 °C).
Storage Temperature Limits: -40 to 140°F (-40 to 60°C).
Probe Length: 6˝ or 12˝; model specic.
Enclosure Rating: NEMA 3.
Mounting Orientation: Flow direction must be parallel to the sensor tip; See
Installation section for details.
Weight: 1.4 oz (40 g); based on M12 connection with 12˝ probe length.
Agency Approvals: CE, RCM, BTL, UL plenum rated (UL tested).
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com

INSTALLATION
Included Duct Mount Flange:
The transmitter should be mounted away from fans, corners, heating and cooling
coils, and other equipment that will affect the measurement of the air velocity. It is
recommended that the AVPT is mounted at least 10 duct diameters downstream of any
disturbances and 5 duct diameters upstream of any disturbances, if possible.
1. Mark and drill a 0.750-0.938˝ (20-24 mm) diameter hole into the duct.
2. Insert and center the duct mount ange in the previously drilled hole and mark
location of the three mounting screw holes.
3. Remove the mounting ange and drill or punch the mounting holes in the marked
locations.
4. Fasten the ange to the duct using three #8 x 1/2˝ pan head sheet metal screws.
Do not over tighten screws.
5. Insert the AVPT probe into the duct mount ange and set the desired insertion
depth.
6. Note the ow direction and unit alignment as shown on sensor tip and product
label, tighten probe retention set screw on the duct mount ange to afx the probe
in place.
Voltage Output Operation:
CAUTION
RESULT.
The minimum receiver load for the voltage output model is 1 kΩ except when using
an AC supply and 10 V output, where 10 kΩ should be used. The resistance due to
the wire should be low compared to the receiver load resistance. While the voltage
at the device remains unchanged with a full load current ow, resistive losses in the
wiring do cause errors in the voltage delivered to the receiver. For example, a 1%
accurate gage, the resistance of the wires should be less than 0.1% of the value of
the receiver load.
The conguration wire may be left unconnected for default 0-10 V output operation as
seen in Figure 2, or connected to power supply common to congure a 0-5 V output
operation as seen in Figure 3.
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL
Electrical Connection:
The cable supplied with the analog voltage output version of the Series AVPT allows
access to the device power and the voltage output signal. An additional signal is also
provided to congure the voltage output (0-10 V/0-5 V) .
Power Supply:
Choose a power supply with a voltage and current rating sufcient to meet the power
specications under all operating conditions. If the power supply is unregulated, make
sure the output voltage remains within the required voltage range under all power line
conditions. Ripple on the supply should not exceed 100 mV.
When using an AC supply with the analog output, be sure that the supply common
is adequately grounded or DC referenced to allow minimum of ripple or noise on the
analog signal.
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
CAUTION
RESULT.
PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL
PWR (RED)GND (BK)
+
POWER
-
Figure 1: Power supply wiring
PWR (RED)
GND (BK)
POWER
Figure 2: 10 V output wiring
PWR (RED)
GND (BK)
CFG (WH)
+
POWER
For models ordered with optional M-12 electrical connections. Reference Table 1 for
wiring color and pinout designation.
-
Figure 3: 5 V output wiring
Wire Color M-12 Pin
White
Black
Green
Brown
Red
Table 1: M-12 wiring pinout
VOUT (GRN)
CFG (WH)
VOLTAGE
RECEIEVER
VOUT (GRN)
+
-
1
2
3
4
5
VOLTAGE
RECEIVER
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
MAINTENANCE/REPAIR
Upon nal installation of the Series AVPT, no routine maintenance is required; though
sensor should be kept clean and free of dirt or debris.
This symbol indicates waste electrical products should not be disposed
of with household waste. Please recycle where facilities exist. Check with
your Local Authority or retailer for recycling advice.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping the
product back for repair. Be sure to include a brief description of the problem plus any
additional application notes.