• Isolated 24 VDC @ 200 mA Transmitter Power Supply
• 2 or 4 Relays with Interlocking Capability + Isolated 4-20 mA Output Options
• Free PC-Based, On-Board, Panel Meter Pro USB Programming Software
• No Assembly Required
• Display Rate & Total at the Same Time
• Rate in Units per Second, Minute, Hour, or Day
• Total, Grand Total or Non-Resettable Grand Total
• Front Panel or Remote Total Reset
• Password Protection for Total Reset
• Total Stored in Non-Volatile Memory
• Assign Any Relay for Rate or Total
• 4-20 mA Output for Rate or Total
• Sampling Relay
• Display Open Channel Flow with Programmable Exponent Feature
• 32-Point Linearization & Square Root Extraction
• Optional SunBright Display Models for Outdoor Applications
• Operating Temperature Range: -40 to 65°C (-40 to 149°F)
• UL & C-UL Listed. E160849; 508 Industrial Control Equipment
• Input Power Options: 85-265 VAC / 90-265 VDC or 12-24 VDC / 12-24 VAC
• Programmable Display, Function Keys & Digital Input
• External 4-Relay & Digital I/O Modules
• RS-232 & RS-485 Serial Communication Options with Modbus RTU
• Wide Assortment of NEMA 4X Enclosures for up to Ten Meters
• 3-Year Warranty
Phone: 219/879-8000 dwyer-inst.com
Page 2
Series APM Analog Panel Meter Instruction Manual
Disclaimer
The information contained in this document is
subject to change without notice. Dwyer
Instruments, Inc. makes no representations or
warranties with respect to the contents hereof
and specifically disclaims any implied warranties
of merchantability or fitness for a particular
purpose. See Warranty Information and Terms &
Conditions on www.dwyer-inst.com
details.
•Read complete instructions prior to installation
and operation of the meter.
for complete
FREE Panel Meter Pro
Programming Software
• Risk of electric shock or personal injury.
• This product is not recommended for life support
applications or applications where malfunctioning
could result in personal injury or property loss.
Anyone using this product for such applications
does so at his/her own risk. Dwyer Instruments,
Inc. shall not be held liable for damages resulting
from such improper use.
WARNING
Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Limited Warranty
Dwyer Instruments, Inc. warrants this product
against defects in material or workmanship for
the specified period under “Specifications” from
the date of shipment from the factory. Dwyer
Instruments’ liability under this limited warranty
shall not exceed the purchase value, repair, or
replacement of the defective unit. See Warranty
Information and Terms & Conditions on
www.dwyer-inst.com
Registered Trademarks
All trademarks mentioned in this document are
the property of their respective owners.
The meter can be powered from the Micro USB connection.
When using the Micro USB connection, DO NOT apply AC or DC
power to the meter.
The easiest and quickest way to program your MPM
meter is to use the FREE Panel Meter Pro
programming software. This software is loaded into
the meter and connects and installs directly to your
PC with a USB cable. We recommend that the first
thing you do after taking the meter out of the box is
connect the MPM to your PC with the provided USB
cable – do not use a different cable. DO NOT apply
AC or DC power to the meter while your PC is
connected to the meter as it will disrupt the USB
connection. You don’t even have to apply an input
signal.
Panel Meter Pro programming software is intuitive,
and most customers can get their meter programmed
as they like without even looking in the manual.
In addition to programming, the software may be used
for:
• Monitoring
• Datalogging using your PC
• Generating and saving programming files for
later use
Once your meter is programmed the way you want it,
you can wire it up for your application per the
instructions in this manual and install it. If you find that
you need to make adjustments to the programming
after the meter is installed, you can use the front panel
buttons and the instructions in this manual to do so.
4 digital inputs & 4 digital outputs
(2 may be connected)
Series
Meters
Material
PME-10
1-10
Plastic NEMA 4X
PME-20
1-6
Plastic NEMA 4X
PME-30
1-6
Stainless Steel NEMA 4X
PME-40
1-6
Painted Steel NEMA 4
PME-00
1-2
Plastic NEMA 4X
Introduction
Front, back and in between, the APM meter boasts
specifications, features and functionality that make it
the only 1/8 DIN analog input flow rate/totalizer you
will ever need. The number one feature that makes
the APM such a useful device is its built-in 24 VDC @
200 mA power supply to drive the transmitter. This
feature not only saves the cost of an external power
supply, but also greatly simplifies wiring. In addition,
there is a second 24 VDC @ 40 mA power supply
provided with the 4-20 mA output option.
The second most important feature about these
meters is they can display flow rate and total at the
same time. In fact, the 6-digit dual line display can be
programmed for a wide variety of flow applications,
including: flow rate and tag, total and tag, total and
grand total, and even non-resettable grand total.
Another reason why the APM Meter is the only flow
rate/totalizer you will ever need is its NEMA 4X rated
front panel. This means you can install the APM in
panels exposed to moisture, dust and other adverse
conditions.
Other key features include four relays and 4-20 mA
output option, remote total reset, advanced input
signal conditioning like square root extraction and
programmable exponent for open channel flow.
Finally, all these features and capabilities can easily
be programmed with free Panel Meter Pro software.
Ordering Information
Standard Models
Options Installed
Accessories
PMA-10
PMA-12
Using the APM Like an MPM
Process Meter
The APM is essentially a MPM process meter with
flow totalization capability. The flow totalization
capability can easily be de-activated for customers
that would prefer their APM behave like a MPM
process meter. For instructions on how to do this, see
Setting Up the Rate/Totalizer Meter (setup) on page
21 for details.
Enclosures
6
Page 7
Series APM Analog Panel Meter Instruction Manual
99999 to 999999), with lead
Update Rate
Overrange
units
is
instruction manual at www.dwyer-inst.com).
Methods
Three programmable passwords restrict
manually
share one 5 A fuse
Rejection
Operating temperature range:
relays, digital I/O, and serial communication
color: black
Front Panel
Torque
Weight
Specifications
Except where noted all specifications apply to
operation at +25°C.
General
Display
Display
Intensity
Display
Line 1: 0.6" (15 mm) high, red LEDs
Line 2: 0.46" (12 mm) high, red LEDs
6 digits: each (zero blanking.
Eight user selectable intensity levels.
Default value is six.
5/second (200 ms)
Isolation
Overvoltage
Category
Environmental
Connections
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation Overvoltage
Category III.
-40 to 65°C (-40 to 149°F)
Storage temperature range:
-40 to 85°C (-40 to 185°F)
Relative humidity:
0 to 90% non-condensing
Removable screw terminal blocks accept
12 to 22 AWG wire, RJ45 for external
Display flashes 999999
Underrange Display flashes -99999
Display
Assignment
Programming
Noise Filter
Filter Bypass
Recalibration
Max/Min
Display
Rounding Select 1, 2, 5, 10, 20, 50, or 100
Password
Display lines 1 & 2 may be assigned to
rate, total, grand total, alternate (rate/total,
rate/grand total, rate/units, total/units, and
grand total/units), set points, max/min,
(line 2 only), and Modbus input. Additional
displays are available if parameter totaloff, and parameter d-SCAL is on: gross,
alternating gross/net, PV1, PV2, and PCT
(refer to the APM Analog Panel Meter
Four front panel buttons, digital inputs, or
PC with Panel Meter Pro software.
Programmable from 2 to 199
(0 will disable filter)
Programmable from 0.1 to 99.9% of
calibrated span
All ranges are calibrated at the factory.
Recalibration is recommended at least
every 12 months.
Max/min readings reached by the process
are stored until reset by the user or until
power to the meter is turned off.
(e.g. rounding = 10, value = 123.45,
display = 123.50).
modification of programmed settings and
two prevent resetting the totals.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function
keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total
Enclosure
Mounting
Tightening
Overall
Dimensions
Warranty
adapters.
1/8 DIN, high impact plastic, UL 94V-0,
NEMA 4X, IP65
1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies
are provided.
Screw terminal connectors: 5 lb-in
(0.56 Nm)
4.68" x 2.45" x 5.64"
(119 mm x 62 mm x 143 mm)
(W x H x D)
9.5 oz (269 g)
3 years parts & labor. See Warranty
Information and Terms & Conditions on
www.dwyer-inst.com
for complete details.
Non-Volatile
Memory
Power
Options
Fuse
Normal Mode
All programmed settings are stored in
non-volatile memory for a minimum of ten
years if power is lost.
85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max;
12-24 VDC, 12-24 VAC, 15 W max.
Powered over USB for configuration only.
Required external fuse: UL Recognized,
5 A max, slow blow; up to 6 meters may
Greater than 60 dB at 50/60 Hz
7
Page 8
Series APM Analog Panel Meter Instruction Manual
Inputs
Field selectable: 0-20 mA, 4-20 mA
Modbus PV (Slave)
Isolated
Accuracy
±0.03% of calibrated span ±1 count,
span
Temperature
span/°C max from -40 to 0°C ambient
Input Signal
Linear, square root, programmable
calculation
Multi-Point
Linearization
2 to 32 points
Programmable
Exponent
User selectable from 1.0001 to 2.9999 for
open channel flow
Round
Tank
Diameter & Length: 999.999 inch or cm
respectively.
Low-Flow
0.0 to 999,999.9 (0 disables cutoff
always shows zero.
Decimal Point
Up to five decimal places or none:
, or
Calibration
Input Range
Minimum Span
Input 1 & Input 2
4-20 mA
0.15 mA
10 V
0.10 V
An error message will appear if the input 1
and input 2 signals are too close together.
Input
Voltage ranges: greater than 500 kΩ
resettable fuse impedance)
Input
Current input protected by resettable fuse,
after fault is removed.
HART
The meter does not interfere with existing
display secondary HART variables.
Rate Display
Total Display
0 to 999,999; automatic lead zero blanking.
overflow and ▲ LED is illuminated.
Total
Up to five decimal places or none:
decimal point.
Totalizer
Calculates total based on rate and field
which the rate is displayed.
Totalizer
Rollover
999,999,999. Relay status reflects display.
Total
Override
Totalizer
indication.
Programmable
0.1 and 999.9 seconds; applied to the first
total is reset.
Total Reset
User selectable via front panel button, F4
delay, or through serial communications.
Total Reset
Total and grand total passwords may be
grand total from the front panel.
Non-Resettable
The grand total can be programmed as a
password “050873”.
disabled.
Process Input
±10 V (0-5 V, 1-5 V, 0-10 V)
Transmitter
Power Supply
Drift
Conditioning
Terminals P+ & P-: 24 VDC ±10%.
All models selectable for 24, 10, or 5 VDC
supply (internal jumper J4). 85-265 VAC
models rated @ 200 mA max, 12-24 VDC
powered models rated @ 100 mA max.
5 & 10 VDC supply rated @ 50 mA max.
Refer to Figure 4: Transmitter Supply Voltage
Selection on page 14 and
Figure 19: 4-20 mA Output Connections on
page 16.
square root & programmable exponent
accuracy range: 10-100% of calibrated
0.005% of calibrated span/°C max from
0 to 65°C ambient, 0.01% of calibrated
exponent, or round horizontal tank volume
& Total
Overflow
Decimal Point
Overflow
Presets
“T” LED is illuminated while displaying total
or grand total.
Up to 999,999,999 with total-overflow
feature. “oF” is displayed to the left of total
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Total decimal point is independent of rate
programmable multiplier to display total in
engineering units. Time base must be
selected according to the time units in
Totalizer rolls over when display exceeds
Program total reset for automatic with
0.1 second delay and set point 1 for
999,999
Up to eight, user selectable under setup
menu. Any set point can be assigned to
total and may be programmed anywhere in
the range of the meter for total alarm
Horizontal
Cutoff
Range
Impedance
Overload
Transparency
calculates volume in gallons or liters
function). Point below at which display
d.ddddd, d.dddd, d.ddd, d.dd, d.d
±
Current ranges: 50 - 100 Ω (depending on
30 VDC max. Fuse resets automatically
HART communications; it displays the
4-20 mA primary variable and it allows the
HART communications to pass through
without interruption. The meter is not
affected if a HART communicator is
connected to the loop. The meter does not
dddddd
Delay
On Release
Password
Total
relay assigned to total or grand total.
If the meter is programmed to reset total to
zero automatically when the preset is
reached, then a delay will occur before the
terminal at back of meter, external contact
closure on digital inputs, automatically via
user selectable preset value and time
entered to prevent resetting the total or
non-resettable total by entering the
•Once the Grand Total has been programmed as
“non-resettable” the feature CANNOT be
Rate/Totalizer
Indication
-99999 to 999999, lead zero blanking.
“R” LED illuminates while displaying rate.
8
Page 9
Series APM Analog Panel Meter Instruction Manual
Deadband
• Automatic (non-latching) and/or
• Manual on/off control mode
Programmable and independent for
will go to alarm state.
can split the optional
Relays
Rating
Noise
Suppression
Relay
Assignment
High or Low
Alarm
Relay
Operation
Relay Reset
Time Delay
Fail-Safe
Operation
2 or 4 SPDT (Form C) internal and/or
4 SPST (Form A) external; rated 3 A
@ 30 VDC and 125/250 VAC resistive load;
1/14 HP (≈ 50 W) @ 125/250 VAC for
inductive loads
Noise suppression is recommended for
each relay contact switching inductive
loads. See Switching Inductive Loads on
page 16 for details.
Relays may be assigned to rate, total, or
grand total.
0-100% of span, user programmable
User may program any alarm for high or
low trip point. Unused alarm LEDs and
relays may be disabled (turn off).
manual reset
• Latching (requires manual
acknowledge) with or without clear
• Pump alternation control (2-8 relays)
• Sampling (based on set point and time)
• Off (disable unused relays and enable
Interlock feature)
User selectable via front panel button, F4
terminal at back of meter, external contact
closure on digital inputs, automatically via
user selectable preset value and time
delay, or through serial communications.
0 to 999.9 seconds, on & off relay time
delays.
each relay.
Programmable and independent for each
relay.
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay
Isolated 4-20 mA Transmitter
Output
Output Source
Scaling Range 1.000 to 23.000 mA for any display range.
Calibration
Analog Out
Programming
Accuracy ± 0.1% FS ± 0.004 mA
Temperature
Drift
Isolated
Transmitter
Power Supply
External Loop
Power Supply
Output Loop
Resistance
Additional
4-20 mA
Outputs
0-10 VDC
Output
Rate/process, total, grand total, max, min,
set points 1-8, or manual control mode
Factory calibrated:
4.000 to 20.000 = 4-20 mA output
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and
break
0.4 µA/°C max from 0 to 65°C ambient,
0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from
input drift.
Terminals I+ & R: 24 VDC ±10%. May be
used to power the 4-20 mA output or other
devices.
All models rated @ 40 mA max.
35 VDC maximum
Power supply Minimum Maximum
24 VDC
35 VDC
(external)
The PD659-1MA-2MA
4-20 mA output into two isolated 4-20 mA
outputs
ThePD659-1MA-1Vcan convert the
optional 4-20 mA output to a 0-10 VDC
output
10 Ω 700 Ω
100 Ω 1200 Ω
Auto
Initialization
Additional
Relays
When power is applied to the meter, relays
will reflect the state of the input to the
meter.
An external module, model PMA-11, is
available to add 4 SPST 3 A relays to the
meter.
9
Page 10
Series APM Analog Panel Meter Instruction Manual
Cable
for
a complete list of capabilities.
Data
Parity
System
Requirements
Microsoft® Windows® XP/Vista/7/8/10
Communications
USB 2.0 (for programming only)
logging)
Configuration
Configure meters one at a time
Power
USB port provides power to the meter.
meter while the USB port is in use.
USB Connection
Function Programming only
Compatibility USB 2.0 Standard, Compliant
Connector
Type
Driver Microsoft® Windows® XP/Vista/7/8/10
Power
Micro-B receptacle
USB A Male to Micro-B Cable
USB port provides power to the meter.
DO NOT apply AC or DC power to the
meter while the USB port is in use.
On-Board Digital Input (F4)
Function
Contacts
Logic Levels
Additional I/O
Reset total, remote operation of front-panel
buttons, acknowledge/reset relays, reset
max/min values. See Function Keys & Digital I/O Available Settings on page 39
3.3 VDC on contact. Connect normally
open contacts across F4 to COM
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Up to 2 external modules, model PMA-12
with 4 digital inputs and 4 digital outputs
each can be added.
Modbus® RTU Serial
Communications
Slave Id 1 – 247 (Meter address)
Baud Rate 300 - 19,200 bps
Transmit
Time Delay
Byte-To-Byte
Timeout
Turn Around
Delay
Note: Refer to the APM Modbus Register Tables located at
www.dwyer-inst.com
Programmable between 0 and 199 ms
8 bit (1 start bit, 1 or 2 stop bits)
Even, Odd, or None with 1 or 2 stop bits
0.01 – 2.54 second
Less than 2 ms (fixed)
for details.
Panel Meter Pro
(Standard USB A to Micro USB B)
RS-232 adapter, RS-485 adapter and
RS-485 to USB converter
(programming, monitoring, and data
DO NOT apply AC or DC power to the
10
Page 11
Series APM Analog Panel Meter Instruction Manual
UL & c-UL
Listed
USA & Canada
UL 508 Industrial Control Equipment
UL File Number
E212517
Front Panel
UL Type 4X, NEMA 4X, IP65; panel
gasket provided
Low Voltage
EN 61010-1:2010
control, and laboratory use
Emissions
EN 55022:2010
Class A ITE emissions requirements
Radiated
Emissions
Class A
AC Mains
Emissions
Class A
Immunity
EN 61326-1:2013
standard
RFI -
Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical
Transients
±2kV AC mains, ±1kV other
Electrostatic
Discharge
±4kV contact, ±8kV air
RFI Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-
Field
30 A/m 70%V for 0.5 period
70%V for 25 periods
Voltage
Interruptions
<5%V for 250 periods
Compliance Information
Safety Information
Safety
Directive
Safety requirements for measurement,
Electromagnetic Compatibility
Conducted
Measurement, control, and laboratory
equipment
EN 61000-6-2:2005
EMC heavy industrial generic immunity
Amplitude
Fast
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
•Read complete instructions prior to installation
and operation of the meter.
• Risk of electric shock or personal injury.
• Hazardous voltages exist within enclosure.
Installation and service should be performed only
by trained service personnel.
Installation
There is no need to remove the meter from its
case to complete the installation, wiring, and
setup of the meter for most applications.
Instructions are provided for changing the
transmitter power supply to output 5 or 10 VDC
instead of 24 VDC. See Figure 4: Transmitter Supply Voltage Selection on page 14.
Unpacking
Remove the meter from box. Inspect the
packaging and contents for damage. Report
damages, if any, to the carrier.
If any part is missing or the meter malfunctions,
please contact your supplier or the factory for
assistance.
Frequency
Magnetic
Voltage Dips 40%V for 5 & 50 periods
Note:
Testing was conducted on meters installed through the
covers of grounded metal enclosures with cable shields
grounded at the point of entry representing installations
designed to optimize EMC performance.
11
Page 12
Series APM Analog Panel Meter Instruction Manual
G
aske
t
Panel
Moun
ting
Bracket
Mounting
Screw
Mi
cro U
SB
Connec
ti
on
Rem
ov
ab
l
e
Connec
tor
s
0.39"
(10 mm)
4.18"
(106 mm)
1.72"
(44 mm)
4.77"
(121 mm)
5.07"
(129 mm)
2.41"
(61 mm)
4.41"
(112 mm)
4.18"
(106 mm)
3.61"
(91.5 mm)
Optional
Connectors
Installed
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Panel Mounting Instructions
•Prepare a standard 1/8 DIN panel cutout –
3.622" x 1.772" (92 mm x 45 mm). Refer to
Figure 1: 1/8 DIN Panel Cutout and Mounting
below for more details.
•Clearance: allow at least 6.0" (152 mm) behind
the panel for wiring.
•Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to
maintain Type 4X rating: 0.06" (1.5 mm) steel
panel, 0.16" (4.1 mm) plastic panel.
•Remove the two mounting brackets provided with
the meter (back-off the two screws so that there is
¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
• Insert meter into the panel cutout.
• Install mounting brackets and tighten the screws
against the panel. To achieve a proper seal,
tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side.
DO NOT OVER TIGHTEN, as the rear of the
panel may be damaged.
Mounting Dimensions
Figure 2. Meter Dimensions - Side View
Figure 3. Meter Dimensions - Top View
DO NOT apply AC or DC power to the meter when using the
Micro USB connection.
Figure 1: 1/8 DIN Panel Cutout and Mounting
12
Page 13
Series APM Analog Panel Meter Instruction Manual
Installation Overview
We recommend the following sequence for getting the
meter into service:
1. DO NOT apply AC or DC power to the meter.
2. Connect the meter to the PC with the USB cable
provided. DO NOT use a different USB cable.
3. If Panel Meter Pro is already installed in your
computer, then the program will launch
automatically in most systems. If the program
does not start automatically, double-click on the
MVPro icon.
4. If MVPro is not installed, follow the instructions
provided below.
5. Use MVPro to configure the meter for your
application.
6. Disconnect the USB cable from the meter.
7. Apply power and signal and check operation of
the meter.
8. Install the meter and put into service.
9. Make any programming adjustments using the
front panel buttons.
2. Once the driver is installed, an AutoPlay
dialog should appear for the drive
“MAINSTAL.” Click “Open folder to view
files.”
If the computer does not display an AutoPlay
dialog for the drive “MAINSTAL,” you should
open My Computer and double-click on the
drive labeled “MAINSTAL.”
3. Double-click on the file named “MAStart.”
The program will open a few windows and
install two programs on your computer.
Simply follow the on-screen instructions until
you see one of the dialogs below. If you
receive a “User Account Control” warning,
click “Yes.”
Panel Meter Pro Software
The easiest and quickest way to program your APM
meter is to use the FREE Panel Meter Pro
programming software. This software is loaded into
the meter and connects and installs directly to your
PC with the USB cable provided. DO NOT use a
different USB cable. We recommend that the first
thing you do after taking the meter out of the box is
connect the APM to your PC with the provided USB
cable. DO NOT apply AC or DC power to the meter
while your PC is connected to the meter as it will
disrupt the USB connection. It is not necessary to
apply an input signal.
Panel Meter Pro programming software is intuitive,
and most customers can get their meter programmed
as they like without even looking in the manual.
4. If there is an update available, click the
“Update” button to install the new version.
Otherwise, click “Configure” to begin
programming your meter.
Panel Meter Pro Installation
1. Connect one end of the provided USB cable
to the meter and the other end to the
computer. The computer will automatically
install the driver software it needs to talk to
the meter. Follow the on-screen instructions
and allow sufficient time for the process to
complete. This can take a few minutes. If the
process is interrupted, then it could leave the
system in an unstable condition.
•Only one meter may be connected at a time.
Attaching multiple meters will cause a conflict
with the meter software.
•DO NOT apply AC or DC power to the meter
when using the Micro USB connection.
Note: If you decide to update your Panel Meter Pro
software, once the installation has completed, you
will be asked if you want to update the setup files
located on the meter itself. This way, you will
always have the most current version on the meter
for future installs.
•DO NOT unplug the meter while the new
installation files are being written to it. The meter
will display uwrite during the process and you
will receive an on-screen notification once the
process is complete.
13
Page 14
Series APM Analog Panel Meter Instruction Manual
Transmitter Supply Voltage
Selection (P+, P-)
All meters, including models equipped with the
12-24 VDC power option, are shipped from the
factory configured to provide 24 VDC power for
the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation,
the internal jumper J4 must be configured
accordingly.
To access the voltage selection jumper:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J4 jumper, located behind the
input signal connector, for the desired
excitation voltage as shown.
Figure 6. APM-120 & APM-220 Connectors Label
Figure 7. APM-101 & APM-201 Connectors Label
Figure 4: Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw
terminal connectors located at the rear of the
meter.
•Use copper wire with 60°C or 60/75°C insulation
for all line voltage connections. Observe all safety
regulations. Electrical wiring should be performed
in accordance with all applicable national, state,
and local codes to prevent damage to the meter
and ensure personnel safety.
Connectors Labeling
The connectors’ label, affixed to the meter, shows the
location of all connectors available with requested
configuration.
Figure 8. APM-140 & APM-240 Connectors Label
Figure 9. APM-121 & APM-221 Connectors Label
Figure 10. APM-141 & APM-241 Connectors Label
Figure 5. APM-100 & APM-200 Connectors Label
•DO NOT connect any equipment other than
Dwyer’s expansion modules, cables, or meters to
the RJ45 M LINK connector. Otherwise damage
will occur to the equipment and the meter.
14
Page 15
Series APM Analog Panel Meter Instruction Manual
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+
-
CNONO NCNCC
RELAY4RELAY3
436521
CNONO NCNCC
RELAY2RELAY1
436521
Power Connections
Power connections are made to a two-terminal
connector labeled POWER. The meter will operate
regardless of DC polarity connection. The + and symbols are only a suggested wiring convention.
The current input is protected against current
overload by a resettable fuse. The display may or
may not show a fault condition depending on the
nature of the overload.
The fuse limits the current to a safe level when it
detects a fault condition, and automatically resets
itself when the fault condition is removed.
Figure 11: Power Connections
Signal Connections
Signal connections are made to a six-terminal
connector labeled SIGNAL. The COM (common)
terminal is the return for the 4-20 mA and the ±10 V
input signals.
Current and Voltage Connections
The following figures show examples of current and
voltage connections.
There are no switches or jumpers to set up for current
and voltage inputs. Setup and programming is
performed through the front panel buttons.
Figure 12: Transmitter Powered by Internal Supply
Figure 14: Voltage Input Connections
The meter is capable of accepting any voltage from 10 VDC to +10 VDC.
Modbus RTU Serial
Communications
Serial communications connection is made to an
RJ45 connector labeled M-LINK. For interfacing to the
MPM, use the PMA-01 for RS-232 or the PMA-03 for
RS-485. The same port is used for interfacing with all
expansion modules (e.g. external relays, digital I/O).
Relay Connections
Relay connections are made to two six-terminal
connectors labeled RELAY1 – RELAY4. Each relay’s
C terminal is common only to the normally open (NO)
and normally closed (NC) contacts of the
corresponding relay. The relays’ C terminals should
not be confused with the COM (common) terminal of
the INPUT SIGNAL connector.
Figure 13: Transmitter Powered by External
Supply or Self-Powered
Figure 15: Relay Connections
15
Page 16
Series APM Analog Panel Meter Instruction Manual
C
R
C
R
Switching Inductive Loads
The use of snubbers to suppress electrical noise is
strongly recommended when switching inductive
loads to prevent disrupting the microprocessor’s
operation. The snubbers also prolong the life of the
relay contacts. Suppression can be obtained with
resistor-capacitor (RC) networks assembled by the
user or purchased as complete assemblies. Refer to
the following circuits for RC network assembly and
installation:
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This
digital input should be connected with a normally
open contact across F4 and COM, or with an active
low signal applied to F4. It can be used to reset the
total, for remote operation of front-panel buttons, to
acknowledge/reset relays, or to reset max/min values.
See Function Keys & Digital I/O Available Settings on
page 39 for a complete list of capabilities.
Figure 16: AC and DC Loads Protection
Choose R and C as follows:
R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of
solenoid loads. Check to confirm proper
operation.
3. Install the RC network at the meter's relay screw
terminals. An RC network may also be installed
across the load. Experiment for best results.
Use a diode with a reverse breakdown voltage two to three
times the circuit voltage and forward current at least as large
as the load current.
Figure 18: F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are
made to the connector terminals labeled mA OUT.
The 4-20 mA output may be powered internally or
from an external power supply.
Figure 19: 4-20 mA Output Connections
Analog Output Power Supply
The internal 24 VDC power supply powering the
analog output may be used to power other devices, if
the analog output is not used. The I+ terminal is the
+24 V and the R terminal is the return.
Figure 17: Low Voltage DC Loads Protection
RC Networks (Snubbers) Available
from Dwyer Instruments, Inc.
RC networks are available from Dwyer Instruments,
Inc. and should be applied to each relay contact
switching an inductive load. Part number: PMA-13.
Note: Relays are de-rated to 1/14th HP (50 watts)
with an inductive load.
.
Figure 20. Analog Output Supply Powering Other
Devices
16
Page 17
Series APM Analog Panel Meter Instruction Manual
12
RLY5RLY6RLY7RLY8
345678
NO C NOCNO CNO C
123456
+5I1I2I3I4O1
78
O2 O3
910
O4G
DI 1-4DO 1-4
5 VDCGND
External Relay & Digital I/O
Connections
The relay and the digital I/O expansion modules
PMA-11 & PMA-12 are connected to the meter using
a CAT5 cable provided with each module. The two
RJ45 connectors on the expansion modules are
identical and interchangeable; they are used to
connect additional modules to the system.
Note: The jumper located between the RJ45
connectors of the PMA-12 must be removed on
the second digital I/O module in order for the
system to recognize it as module #2.
•DO NOT connect or disconnect the expansion
modules with the power on! More detailed
instructions are provided with each optional
expansion module.
Interlock Relay Feature
As the name implies, the interlock relay feature
reassigns one, or more, alarm/control relays for use
as interlock relay(s). Interlock contact(s) are wired to
digital input(s) and activate the interlock relay. This
feature is enabled by configuring the relay, and the
corresponding digital input(s), see Setting Up the Interlock Relay (Force On) Feature on page 32.
In the example below, an Interlock Contact switch is
connected to a digital input, which will be used to
force on (energize) the Interlock Relay. The Interlock
Relay and the Control Relay are connected in series
with the load.
• When the Interlock Contact is closed (safe), the
Interlock Relay energizes, allowing power to flow
to the Control Relay; the corresponding front
panel LED is on.
• When the Interlock Contact is open, the
corresponding front panel LED flashes (locked
out), the Interlock Relay is de-energized,
preventing power from flowing to the Control
Relay and the load.
.
Figure 21. Expansion Module &
DIN Rail Mounting Kit
Figure 22. External Relays Module Connections
Figure 23. Digital I/O Module Connections
Figure 24. Interlock Connection
17
Page 18
Series APM Analog Panel Meter Instruction Manual
There is no need to recalibrate the meter
Button
Description
LED
Status
Flashing:
Total
Note:
Grand Total
Total
Note:
Setup and Programming
Front Panel Buttons and Status
LED Indicators
when first received from the factory.
The meter is factory calibrated prior to
shipment for milliamps and volts with
calibration equipment that is certified to NIST
standards.
Overview
There are no jumpers to set for the meter input
selection.
Setup and programming is done using Panel Meter
Pro or through the front panel buttons.
After power and input signal connections have been
completed and verified, apply power to the meter.
Menu 1-8
Alarm 1 – 8
indicators
Right
arrow/F1
Up arrow/F2 R
Enter/F3 T
F4 is a digital input. Alarms
5-8 are enabled when relay
expansion module is
installed.
LEDs for relays in manual mode flash with the “M” LED
every 10 seconds. “M” flashing by itself indicates Aout –
manual control is used.
G T
▲
1-8
M
Relay in
manual
control mode
Rate
indicator
indicator or
Flashing:
Tare
indicator
overflow
indicator
•Press the Menu button to enter or exit the
Programming Mode at any time.
•Press the Right arrow button to move to the next
digit during digit
or decimal point programming.
•Press or hold the Up arrow button to scroll
through the menus, decimal point, or to
increment the value of a digit.
•Press the Enter button to access a menu or to
accept a setting.
•Press and hold the Menu button for three
seconds to access the advanced features of the
meter.
18
Page 19
Series APM Analog Panel Meter Instruction Manual
Display Functions & Messages
Description
(relays assigned to rate)
Display Functions & Messages
The meter displays various functions and messages
during setup, programming, and operation. The
following table shows the main menu functions and
messages in the order they appear in the menu.
Display Functions & Messages
Display Parameter
setup
Input
nmA
volt
Total
d-SCAL
units
rate
total
Gtotal
Dec pt
prog
InCAL
sCalE
Cal
Inp 1
Dis 1
Inp 2
Dis 2
Error
T tb
T CF
T rst
GT tb
Setup Enter Setup menu
Input
4-20 mA
0-10 VDC
Total
Dual-scale
Units
Rate
Total
Grand Total
Decimal
point
Program Enter the Program menu
Input
Calibration
Scale Enter the Scale menu
Calibrate Enter the Calibrate menu
Input 1
Display 1 Program display 1 value
Input 2
Display 2
Error
Total time
base
Total
conversion
factor
Total reset
Grand total
time base
Action/Setting
Description
Enter Input selection
menu
Set meter for 4-20 mA
input
Set meter for ±10 VDC
input
Enable or disable
totalizer features
Enter d-SCAL menu and
select Yes for dual- scale
or No for single scale
display
Select the display
units/tags
Select the display units
for rate
Select the display units
for total
Select the display units
for grand total
Set decimal point for rate,
total, grand total
Enter the Input Calibration menu
Calibrate input 1 signal or
program input 1 value
Calibrate input 2 signal or
program input 2 value
(up to 32 points)
Program display 2 value
(up to 32 points)
Error, calibration not
successful, check signal
or programmed value
Program total time base
Program total conversion
factor
Program total rest mode:
auto or manual
Program grand total time
base
Display Parameter
GT CF
GT rst
Auto
T dly
nmAn
dsplay
Line 1
Line 2
d-Inty
RELaY
Assign
Asign1
totAL
G total
nm bus
rate
RLY 1
Act 1
Auto
A-nman
LatCH
Lt-CLr
Altern
Sanmpl
Grand total
conversion
factor
Grand total
reset
Automatic Press Enter to set
Time delay Program time delay for
Manual Press Enter to reset total
Display Enter the Display menu
Line 1 Press Enter to assign the
Line 2
Display
intensity
Relay Enter the Relay menu
Assignment Assign relays to rate,
Assign 1 Relay 1 assignment
Total Assign relay to total
Grand total Assign relay to grand
Modbus Select to display Modbus
Rate Assign relay to rate
Relay 1 Relay 1 setup
Action 1 Set relay 1 action
Automatic Set relay for automatic
Auto-manual
Latching
Latchingcleared
Alternate
Sampling
Action/Setting
Program grand total
conversion factor
Program grand total rest
mode: auto or manual
automatic total reset
total auto reset
manually
Main display parameter
(default: PV or rate)
Press Enter to assign the
small display parameter
(default: total)
Set display intensity level
from 1 to 8
total, or grand total
total
input or to assign
Modbus input as the
analog output source
reset
Set relay for automatic &
manual reset
any time
Set relay for latching
operation (relays
assigned to rate)
Set relay for latching
operation with manual
reset only after alarm
condition has cleared
Set relay for pump
alternation control (relays
assigned to rate)
Set relay for sampling
operation
19
Page 20
Series APM Analog Panel Meter Instruction Manual
Display Functions & Messages
Description
Interlock feature)
Display Functions & Messages
Description
Display Parameter
OFF
Set 1
RSt 1
RLY 2
FaiLSF
FLS 1
on
off
DeLAY
DLY 1
On 1
OFF 1
break
iGnorE
On
OFF
Aout
Dis 1
Out 1
Dis 2
Out 2
reset
Rst Gt
Rst Hi
Rst Lo
Rst HL
Rst t
Off
Set 1 Program set point 1
Reset 1 Program reset point 1
Relay 2
Fail-safe Enter Fail-safe menu
Fail-safe 1
On Enable fail-safe operation
Fail-safe off
Delay
Delay 1
On Set relay 1 On time delay
Off Set relay 1 Off time delay
Loop break Set relay condition if loop
Ignore Ignore loop break
On
Off
Analog
output
Display 1 Program display 1 value
Output 1 Program output 1 value
Display 2 Program display 2 value
Output 2
Reset Press Enter to access the
Reset
grand total
Reset high Press Enter to reset max
Reset low
Reset
high & low
Reset total Press Enter to reset total
Action/Setting
Disable relay and front
panel status LED
(Select Off to enable
Relays 2-8 setup
Note: Relays 5-8 are
shown, only if expansion
relay module is installed.
Set relay 1 fail-safe
operation
Disable fail-safe
operation
Enter relay Time Delay
menu
Enter relay 1 time delay
setup
break detected
(For mA input only)
condition
(Processed as a low
signal condition)
Relay goes to alarm
condition when loop
break is detected
Relay goes to non-alarm
condition when loop
break is detected
Enter the Analog output
scaling menu
(e.g. 4.000 mA)
Program output 2 value
(e.g. 20.000 mA)
Reset menu
Press Enter to reset
grand total
display
Press Enter to reset min
display
Press Enter to reset max
& min displays
Display Parameter
Rst tr
Contrl
Auto
nmAn
pass
Pass 1
Pass 2
Pass 3
Total
Gtotal
nonrst
unloc
locd
999999
-99999
Reset tare Reset tare (Used when
Control Enter Control menu
Automatic Press Enter to set relays
Manual
Password Enter the Password
Password 1 Set or enter Password 1
Password 2 Set or enter Password 2
Password 3 Set or enter Password 3
Total
password
Grand total
password
Nonresettable
Unlocked Program password to
Locked Enter password to unlock
Flashing
display
Action/Setting
Total is no only)
and analog output for
automatic operation
Press Enter to manually
control relays or analog
output operation
menu
Set or enter password for
manual reset
Set or enter password for
manual reset
Non-resettable grand
total set after entering
“050873” for Gtotal
password
lock meter
meter
Overrange condition
Underrange condition
20
Page 21
Series APM Analog Panel Meter Instruction Manual
Main Menu
The main menu consists of the most commonly used
functions: Reset, Control, Setup, and Password.
•Press Menu button to enter Programming Mode,
then press the Up arrow button to scroll main
menu.
•Press Menu, at any time, to exit and return to
Run Mode. Changes made to settings prior to
pressing Enter are not saved.
•Changes to the settings are saved to memory
only after pressing Enter/F3.
•The display moves to the next menu every time a
setting is accepted by pressing Enter/F3.
Setting Numeric Values
The numeric values are set using the Right and Up
arrow buttons. Press Right arrow to select next digit
and Up arrow to increment digit value. The digit being
changed is displayed brighter than the rest. Press and
hold Up to auto-increment the display value. If
negative numbers are allowed, the first digit position
will include a negative symbol (-) after the 9.
Press the Enter button, at any time, to accept a
setting or Menu button to exit without saving changes.
Setting Up the Rate/Totalizer
Meter (
The Setup menu is used to select:
Press the Enter button to access any menu or press
Up arrow button to scroll through choices. Press the
Menu button to exit at any time.
setup)
1. Input signal the meter will accept and enable
totalizer features
2. Select the display units/tags
3. Select the decimal point position
4. Meter programming & input calibration
5. Display parameter and intensity
6. Relay operation
7. 4-20 mA analog output scaling
21
Page 22
Series APM Analog Panel Meter Instruction Manual
Display
Character
Display
Character
0
1
2
3
4
O
5
o
6
7
8
9
c
w
d
X
-
]
[
J
Space
Setting the Input Signal (Input)
Enter the Input menu to set up the meter to display
current (nmA) or voltage (Volt) inputs.
The current input is capable of accepting any signal
from 0 to 20 mA. Select current input to accept
0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal
from -10 to +10 VDC. Select voltage input to accept
0-5, 1-5, 0-10, or ±10 VDC signals.
Setting the Totalizer Features
(total)
To simply not display the total, select alternative
display parameters in the display (dsplay) menu.
Enable or disable the totalizer features by selecting
“Yes” or “no” after the input type has been set up. If
the totalizer features are disabled, all the totalizer
features and functions are hidden from the menus.
Level and process meter features and functions are
added to the menus.
If disabling the total parameter by selecting no,
please refer to the MPM Panel Meter manual
available at www.dwyer-inst.com
setting up the meter parameters.
Notes:
1. The totalizer continues working in the background.
2. When selecting "no" for Total, the meter now
functions as a MPM Process Meter. We strongly
suggest that you download and use the MPM
instruction manual from our website www.dwyer-
inst.com while in this mode of operation.
for instructions on
Setting the Display Units or
Custom Tags (units)
Use this menu to enter the unit or custom tag that will
be displayed if:
1. Alternating rate, total, or grand total and
units is selected in the units menu, or
2. d unit is selected as the line 2 parameter.
See the Setting the Display Parameter & Intensity
(dsplay) flow chart on page 24 to access the display
menu to show the unit or tag on line 2. The
engineering units or custom legends can be set using
the following 7-segment character set:
0
1
2
3
4
5
6
7
8
9
A
b
C
A
b
C
c
d
e
f
g
9
H
h
I
I
E
F
G
g
H
h
I
i
j
Notes:
Degree symbol represented by (<) if programming with
Panel Meter Pro.
The letters “m” and “w” use two 7-segment LEDs each;
when selected the characters to the right are shifted one
position.
Press and hold up arrow to auto-scroll the characters in
the display.
k
l
n m
n O
o
p
q r
s
t
u v
uw
x
y
z
-
/
[
] =
!
K
L
m
n
P
q
r
S
t
u
V
Y
Z
/
=
Degree(<)
22
Page 23
Series APM Analog Panel Meter Instruction Manual
Setting the Decimal Point (dEc.pt)
The decimal point may be set with up to five decimal
places or with no decimal point at all. The rate, total,
and grand total decimal points are independent.
The decimal point selection should be made prior to
scaling, calibrating or programming the meter.
Pressing the Right arrow moves the decimal point one
place to the right until no decimal point is displayed
then it moves to the leftmost position. Pressing the Up
arrow moves the decimal point one place to the left.
Programming the Rate/Totalizer
(prog)
The meter may either be scaled (SCALE) without
applying an input or calibrated (Cal) by applying an
input. The meter comes factory calibrated to NIST
standards, so for initial setup, it is recommended to
use the (SCALE) function.
The Program menu contains the following menus:
1. Scale without a signal source
2. Calibrate with a calibrated signal source
3. Total time base & conversion factor
4. Grand total time base & conversion factor
5. Total reset mode for total & grand total
Process inputs may be scaled or calibrated to any
display within the range of the meter.
Note: The Scale and Calibrate functions are
exclusive of each other. The meter uses the last
function programmed. Only one of these methods
can be employed at a time. The Scale and Calibrate
functions can use up to 32 points (default is 2). The
number of points should be set in the Advanced
menu prior to scaling and calibration of the meter.
See Multi-Point Linearization (Linear) menu on page
37 for details.
The process input may be calibrated or scaled to any
display value within the range of the meter.
Multi-Point Calibration & Scaling
The meter is set up at the factory for 2-point linear
calibration. The number of points for multi-point
calibration/scaling is set up in the AdvancedFeatures
menu. Up to 32 linearization points may be selected.
See Multi-Point Linearization (Linear) menu on page 37 for details.
Input Calibration Method (InCAL)
There are two methods of calibrating (or scaling) the
display to show the correct engineering units.
•Use the Scale menu to enter the scaling without a
signal source.
•Use the Calibrate menu to apply a signal from a
signal source.
Note: The Scale and Calibrate functions are exclusive
of each other. The meter uses the last function
programmed. Only one of these methods can be
employed at a time. The Scale and Calibrate
functions can use up to 32 points (default is 2). The
number of points should be set in the Advanced menu
prior to scaling and calibration of the meter. See
Multi-Point Linearization (Linear) on page 37 for
details.
Scaling the Meter (SCALE)
The process inputs (4-20 mA and ±10 VDC) can be
scaled to display the process variable in engineering
units.
A signal source is not needed to scale the meter;
simply program the inputs and corresponding display
values.
Additional parameters, not needed for most applications,
are programmed in the Advanced Features menu; see
Advanced Features Menu on page 35.
23
Page 24
Series APM Analog Panel Meter Instruction Manual
Input range
Input 1 & input 2 span
4-20 mA
0.15 mA
±10 VDC
0.10 VDC
Error Message (Error)
An error message indicates that the calibration or
scaling process was not successful.
After the error message is displayed, the meter
reverts to the input prior to the failure during
calibration or scaling and to input 1 during internal
calibration, allowing the appropriate input signal to be
applied or programmed.
The error message might be caused by any of the
following conditions:
1. Input signal is not connected to the proper
terminals or it is connected backwards*.
2. Wrong signal selection in Setup menu*.
3. Minimum input span requirements not
maintained.
4. Input 1 signal inadvertently applied to calibrate
input 2*.
*Not relevant when scaling the meter.
For instructions on how to program numeric values
see Setting Numeric Values on page 21.
Minimum Input Span
The minimum input span is the minimum difference
between input 1 and input 2 signals required to
complete the calibration or scaling of the meter.
Calibrating the Meter with External
Source (
The meter can be calibrated to display the process
variable in engineering units by applying the
appropriate input signal and following the calibration
procedure.
The use of a calibrated signal source is strongly
recommended to calibrate the meter.
Cal)
Time Base, Total Conversion Factor
& Total Reset
The time base, total conversion factor, and total reset
menus are located in the Program menu.
The total and grand total have their own independent
settings. This means that one can be displaying the
value in gallons while the other displays in million
gallons, liters, m
3
, etc.
Time Base
The time base is the amount of time over which the
rate parameter should accrue. For example, if the rate
was ten and the time base was in minutes, then the
total would increase by ten every one minute.
Total & Grand Total Conversion
Factor
The total & grand total conversion factor is the
amount by which the rate is multiplied before it is
added to the total or grand total. For Example, if the
rate was ten per second and the total conversion
factor was 100, the total would increase by 1000
every second. This is useful, for instance, if you want
to show rate in gallons and total in thousands of
gallons.
Total & Grand Total Reset
The totals can be programmed for automatic or
manual reset. In the automatic reset mode, a
programmable time delay is available to reset the total
or grand total after the assigned preset is reached.
The totals can also be reset via the front panel button,
via a switch across the on-board F4 terminal, the
PMA-12 digital I/O expansion module, or via a
Modbus command.
Warm up the meter for at least 15 minutes before
performing calibration to ensure specified
accuracy.
Non-Resettable Totalizer
The total and grand total can be password-protected
to prevent unauthorized resets. The grand total can
be programmed as a non-resettable total. See Total Reset Password & Non-Resettable Total on page 34
for details.
24
Page 25
Series APM Analog Panel Meter Instruction Manual
Setting the Display Parameter &
Intensity (dsplay)
Display line 1 can be programmed to display:
1. Rate value
2. Total or grand total
3. Toggle rate/total
4. Toggle rate/G-total
5. Relay set points
6. Toggle rate and units
7. Toggle total and units
8. Toggle grand total and units
9. Max, min, or max & min values
10. Modbus input
Display line 2 can be programmed to display:
1. Engineering units or custom legends
for line 1
2. Rate value
3. Total or grand total
4. Toggle rate/total
5. Toggle rate/G-total
6. Relay set points
7. Toggle rate and units
8. Toggle total and units
9. Toggle grand total and units
10. Max, min, or max & min values
11. Modbus input
12. Off (no display)
Selecting engineering units or custom legends as
display line 2 (d unit) will display the unit or tag
selected for the rate, total, or grand total displayed on
line 1.
For example, if line 1 is set to total, selecting
d unit to display on line 2 will have the total appear
on line 1, and the total unit appear on line 2.
After setting up the input and the display, press the
Menu button to exit programming and skip the rest of
the setup menu. Press the Menu button again and the
Up arrow to reach the Program menu and complete
the scaling or calibration of the meter.
Display Flow Rate, Total or Grand
Total
Line 1 can be programmed to display flow rate, total,
or grand total, and line 2 can be programmed to
display flow rate, total, grand total, engineering units,
custom legends, or be turned off. Both lines can also
display relay set points, or max and min values.
Display Toggling Between Reading
& Units
The APM meter can be programmed so that line 1
and line 2 toggle between the reading and their
engineering units. For instance, line 1 displays flow
rate, line 2 displays total, and the display toggles to
show their units.
Display Intensity (d-Inty)
The meter has eight display intensity levels to give the
best performance under various lighting conditions.
Select intensity 8 for outdoor applications. The default
intensity setting is 6.
25
Page 26
Series APM Analog Panel Meter Instruction Manual
Setting the Relay Operation
(relay)
This menu is used to set up the operation of the
relays.
•During setup, the relays do not follow the input
and they will remain in the state found prior to
entering the Relay menu.
1. Relay assignment
a. Rate for low and high alarm
b. Total
c. Grand total
d. Modbus input process variable
2. Relay action
a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time
(non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only
after alarm condition has cleared)
e. Pump alternation control (automatic
reset only)
f. Sampling (the relay is activated for a
user-specified time)
g. Off (relay state controlled by Interlock
feature)
3. Set and reset points
4. Fail-safe operation
a. On (enabled)
b. Off (disabled)
5. Time delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
6. Relay action for loss (break) of 4-20 mA input
(ignore, on, off)
Relay Assignment (Assign)
The relays can be assigned to any of the following
parameters:
1. Rate for low or high alarm indication
2. Total for alarm indication
3. Grand total for alarm indication
4. Modbus input process variable
Setting the Relay Action
Operation of the relays is programmed in the Action
menu. The relays may be set up for any of the
following modes of operation:
1. Automatic reset (non-latching)
2. Automatic + manual reset at any time
(non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after
alarm condition has cleared)
5. Pump alternation control (automatic reset only)
6. Sampling (the relay is activated for a userspecified time)
7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup;
relay 2-8 are set up in a similar fashion.
26
Page 27
Series APM Analog Panel Meter Instruction Manual
Programming Set and Reset
Points
High alarm indication: program set point above reset
point.
Low alarm indication: program set point below reset
point.
The deadband is determined by the difference
between set and reset points. Minimum deadband is
one display count. If the set and reset points are
programmed with the same value, the relay will reset
one count below the set point.
Note: Changes are not saved until the reset point has
been accepted.
Relay Action for Loss of 4-20 mA
Input (Loop Break)
A loop break condition is triggered when the 4-20 mA
input signal drops below 0.005 mA. Each relay may
be programmed to go to one of the following
conditions when the meter detects the loss of the
input signal (i.e. < 0.005 mA):
1. Turn On (Go to alarm condition)
2. Turn Off (Go to non-alarm condition)
3. Ignore (Process as a low signal condition)
The following graph shows the loop break relay
operation for a high alarm relay.
Setting Fail-Safe Operation
In fail-safe mode of operation, the relay coil is
energized when the process variable is within safe
limits and the relay coil is de-energized when the alarm
condition exists. The fail-safe operation is set
independently for each relay. Select on to enable or
select off to disable fail-safe operation.
Programming Time Delay
The On and Off time delays may be programmed for
each relay between 0 and 999.9 seconds. The relays
will transfer only after the condition has been
maintained for the corresponding time delay.
The On time delay is associated with the set point.
The Off time delay is associated with the reset point.
27
Page 28
Series APM Analog Panel Meter Instruction Manual
Relay and Alarm Operation
Diagrams
The following graphs illustrate the operation of the
relays, status LEDs, and ACK button.
High Alarm Operation (Set > Reset)
High Alarm with Fail-Safe
Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To
detect a new alarm condition, the signal must go below the set point, and then go
above it.
Low Alarm Operation (Set < Reset)
Note: Relay coil is energized in non-alarm condition. In case of power failure,
relay will go to alarm state.
Low Alarm with Fail-Safe
Operation (Set < Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To
detect a new alarm condition, the signal must go below the set point, and then go
above it.
Note: Relay coil is energized in non-alarm condition. In case of power failure,
relay will go to alarm state.
28
Page 29
Series APM Analog Panel Meter Instruction Manual
Preset = 100
100
Relay
LED
Total
200
300
Sample
Time
Sample
Time
Sample
Time
Time Delay Operation
The following graphs show the operation of the time
delay function.
When the signal crosses the set point, the On time delay
timer starts and the relay trips when the time delay has
elapsed. If the signal drops below the set point (high
alarm) before the time delay has elapsed, the On time
delay timer resets and the relay does not change state.
The same principle applies to the Off time delay.
Note: If “Automatic or Manual (A-nmAn)” reset mode is
selected, the LED follows the reset point and
not the relay state when the relay is
acknowledged.
Rate Relay Sampling Operation
When the signal crosses the set point, the relay trips
and the sample time starts. After the sample time has
elapsed, the relay resets. The cycle repeats every
time the set point is crossed, going up for high alarms
and going down for low alarms.
The sample time can be programmed between 0.1
and 5999.9 seconds
.
Total Relay Sampling Operation
When the total reaches the preset, the relay trips and
the sample time starts. After the sample time has
elapsed, the relay resets. The cycle repeats every
time the preset value is added to the total.
29
Page 30
Series APM Analog Panel Meter Instruction Manual
Fail-Safe
Non-Alarm State
Alarm State
Power
NO
NC
NO
NC
Off
Open
Closed
Closed
Open
Relays
On
Closed
Open
Open
Closed
Relays
LED
Status
LED
Status
1
Alarm 1
5
Alarm 5
2
Alarm 2
6
Alarm 6
3
Alarm 3
7
Alarm 7
4
Alarm 4
8
Alarm 8
Power-
1
HI
1000
500
499
Off 2 LO
700
900
499
On 3 LO
250
400
499
Off 4 HI
450
200
499
On
Relay terminology for following tables
Terminology
Relay Condition
On
Alarm (Tripped)
Off
Normal (Reset)
Ack
Acknowledged
Relay Operation Details
Overview
The relay capabilities of the meter expand its
usefulness beyond simple indication to provide users
with alarm and control functions. These capabilities
include front panel alarm status LEDs as well as
either 2 or 4 optional internal relays and/or 4 external
relays expansion module. Typical applications include
high or low temperature, level, pressure or flow
alarms, control applications such as simple on/off
pump control, pump alternation control for up to 8
pumps, and basic batch control. There are four basic
ways the relays can be used:
1. High or Low Alarms with Latching or NonLatching Relays
2. Simple On/Off Control with 100% Adjustable
Deadband
3. Sampling (Based on Time)
4. Pump Alternation Control for up to 8 Pumps
Relays Auto Initialization
When power is applied to the meter, the front panel
LEDs and alarm relays will reflect the state of the
input to the meter. The following table indicates how
the alarm LEDs and relays will react on power-up
based on the set and reset points:
Alarm #
HI or LO
Alarm
Fail-Safe Operation
The following table indicates how the relays behave
based on the fail-safe selection for each relay:
Selection
Set
Point
Reset
Point
Up
Reading
Relay &
LED
Failure
Front Panel LEDs
The LEDs on the front panel provide status indication
for the following:
The meter is supplied with four alarm points that
include front panel LEDs to indicate alarm conditions.
This standard feature is particularly useful for alarm
applications that require visual-only indication. The
LEDs are controlled by the set and reset points
programmed by the user. When the display reaches a
set point for a high or low alarm, the corresponding
alarm LED will turn on. When the display returns to
the reset point the LED will go off. The front panel
LEDs respond differently for latching and non-latching
relays.
For non-latching relays, the LED is always off during
normal condition and always on during alarm
condition, regardless of the state of the relay (e.g.
Relay acknowledged after alarm condition).
For latching relays, the alarm LEDs reflect the status
of the relays, regardless of the alarm condition. The
following tables illustrate how the alarm LEDs function
in relation to the relays and the acknowledge button
(Default: F3 key assigned to ACK).
Latching and Non-Latching Relay
Operation
The relays can be set up for latching (manual reset)
or non-latching (automatic reset) operation.
Note: NO = Normally Open, NC = Normally Closed.
This refers to the condition of the relay contacts when
the power to the meter is off.
go to
nonalarm
state
go to
alarm
state
The On and Off terminology does not refer to the
status of the relay’s coil, which depends on the failsafe mode selected.
•In latching relay mode, if Fail-Safe is off, latched
relays will reset (unlatch) when power is cycled.
30
Page 31
Series APM Analog Panel Meter Instruction Manual
Automatic reset only
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack (No effect)
On
On
Normal
Off
Off
Automatic + manual reset at any time
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Normal
Off
Off
Next Alarm
On
On
Ack
On
Off
Normal
Off
Off
Manual reset any time
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack
Off
Off
Manual reset only after alarm condition has
cleared
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack (No effect)
On
On
Normal
On
On
Ack
Off
Off
Non-Latching Relay (Auto)
In this application, the meter is set up for automatic
reset (non-latching relay). Acknowledging the alarm
while it is still present has no effect on either the LED
or the relay. When the alarm finally goes away, the
relay automatically resets and the LED also goes off.
Non-Latching Relay with Manual
Reset (A-nman)
In this application, the meter is set up for automatic
and manual reset at any time (non-latching relay).
The LED and the relay automatically reset when the
meter returns to the normal condition.
In addition, the relay can be manually reset while the
alarm condition still exists, but the LED will stay on
until the meter returns to the normal condition.
Latching Relay with Clear (LatcH)
In this application, the meter is set up for manual
reset at any time. Acknowledging the alarm even if
the alarm condition is still present resets the relay and
turns off the LED.
Latching Relay (Lt-Clr)
In this application, the meter is set up for manual reset
only after the signal passes the reset point (alarm
condition has cleared). Acknowledging the alarm while it
is still present has no effect on either the LED or the
relay. When the alarm is acknowledged after it returns to
the normal state, the LED and the relay go off. Notice
that the LED remains on, even after the meter returns to
the normal condition. This is because, for latching relays,
the alarm LED reflects the status of the relay, regardless
of the alarm condition.
31
Page 32
Series APM Analog Panel Meter Instruction Manual
123456
+5I1I2I3I4O1
78
O2 O3
910
O4G
DI 1-4DO 1-4
5 VDC
GND
SW2
SW1
Acknowledging Relays
There are three ways to acknowledge relays
programmed for manual reset:
1. Via the programmable front panel function keys
F1-F3 (Example: F3 assigned to ACK).
Setting Up the Interlock Relay
(Force On) Feature
Relays 1-4 can be set up as interlock relays. To set
up the relays for the interlock feature:
1. Access the Setup – Relay – Action menu and set
the action to off.
2. Remotely via a normally open pushbutton wired
to the F4 terminal at the rear of the instrument.
3. One of the digital inputs and the +5 V terminals
on the digital I/O expansion module.
When the ACK button or the assigned digital input is
closed, all relays programmed for manual reset are
acknowledged.
2. In the Advanced features – User menu program
any of the digital inputs to Force On any of the
internal relays (1-4).
3. Connect a switch or dry contact between the +5V
terminal and the corresponding digital input (dI-1
to dI-4) terminal.
Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front
panel LEDs are steady on) when SW1 & SW2
switches (above) are closed. If the contacts to these
digital inputs are opened, the corresponding front
panel LEDs flash indicating this condition. The
processes being controlled by the interlock relay will
stop, and will re-start only after the interlock relay is
re-activated by the digital inputs (switches).
Note: If multiple digital inputs are assigned to the
same relay, then the corresponding logic is (AND) –
i.e. both switches must be closed to activate the relay.
32
Page 33
Series APM Analog Panel Meter Instruction Manual
Scaling the 4-20 mA Analog
Output (
The 4-20 mA analog output can be scaled to provide
a 4-20 mA signal for any display range selected.
No equipment is needed to scale the analog output;
simply program the display values to the
corresponding mA output signal.
The Analog Output menu is used to program the 4-20
mA output based on display values.
For further details, see Setting Numeric Values,
page 21, Relay Action for Loss of 4-20 mA Input (Loop Break), page 27.
Aout)
Reset Menu (reset)
The Reset menu is used to reset the totals and maximum
or minimum reading (peak or valley) reached by the
process; both may be reset at the same time by selecting
“reset high & low” (rst HL). If total is set to no, the tare
value used to zero the display may be reset by selecting
“reset tare” (rst tr).
Manual Control Menu (Contrl)
The Manual Control menu is used to control the
4-20 mA analog output and the relays manually,
ignoring the input. Each relay and analog output can
be programmed independently for manual control.
Selecting automatic control sets all relays and analog
output for automatic operation.
33
Page 34
Series APM Analog Panel Meter Instruction Manual
Setting Up the Password (pass)
The Password menu is used for programming three
levels of security to prevent unauthorized changes to
the programmed parameter settings and to program
the non-resettable totalizer.
Pass 1: Allows use of function keys and digital
inputs
Pass 2: Allows use of function keys, digital inputs
and editing set/reset points
Pass 3: Restricts all programming, function keys,
and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total manually
Protecting or Locking the Meter
Enter the Password menu and program a six-digit
password.
For instructions on how to program numeric values
see Setting Numeric Values on page 21.
Making Changes to a Password
Protected Meter
If the meter is password protected, the meter will
display the message Locd (Locked) when the Menu
button is pressed. Press the Enter button while the
message is being displayed and enter the correct
password to gain access the menu. After exiting the
programming mode, the meter returns to its password
protected condition.
Disabling Password Protection
To disable the password protection, access the
Password menu and enter the correct password
twice, as shown below. The meter is now unprotected
until a new password is entered.
Total Reset Password & NonResettable Total
The total and the grand total can be passwordprotected to prevent unauthorized total resets.
The grand total can be programmed as a nonresettable total by entering the password “050873”.
•Once the Grand Total has been programmed as
“non-resettable” the feature CANNOT be
disabled.
If the correct six-digit password is entered, the meter
displays the message unLoc (unlocked) and the
protection is disabled until a new password is
programmed.
If the password entered is incorrect, the meter
displays the message Locd (Locked) for about two
seconds, and then it returns to Run Mode. To try
again, press Enter while the Locked message is
displayed.
Did you forget the password?
The password may be disabled by entering a
master password once. If you are authorized to
make changes, enter the master password 508655
to unlock the meter.
34
Page 35
Series APM Analog Panel Meter Instruction Manual
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
Filter
Set noise filter value
Bypass
Set filter bypass value
for display variables
parameters
address
Baud rate
Select baud rate
serial communication
with 1 or 2 stop bits
timeout
(function, cutoff, out)
horizontal tank function
points
points
32-point linearization
root extraction
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
exponent value
calculation
(cm)
gallons or meters
diameter in inches
in inches
Cutoff
Set low-flow cutoff
total count direction
down
Count
up or down
grand total countdown
programming
parameters
4-20 mA output
display overrange
display underrange
loop break detected
value for loop break
condition
output allowed
output allowed
for scaling the output)
resolution
resolution
and digital I/O
key
key
key
Advanced Features Menu
To simplify the setup process, functions not needed
for most applications are located in the Advanced Features menu.
Press and hold the Menu button for three seconds to
access the advanced features of the meter.
Prog E
rht
Programmable
exponent
Round
horizontal tank
Set meter for
programmable
exponent and enter
Set meter for round
horizontal tank volume
Advanced Features Menu &
Display Messages
The following table shows the functions and
messages of the Advanced Features menu in the
order they appear in the menu.
filter
bypASs
Round
seriAl
SlaV Id
baud
Tr dLY
Round
Serial
Slave ID
Transmit delay
Set the rounding value
Set serial
communication
Set slave ID or meter
Set transmit delay for
Inch
dianmr
Length
CutofF
Count
Tot C
Gtot C
C Strt
AoutPr
Source
O-rang
u-rang
Break
Force
Ignore
nmAx
nmin
Dimension
Diameter
Length
Count
Total Count
Grand Total
Count Start
Analog output
Source
Overrange
Underrange
Loop Break
Force
Ignore
Maximum
Minimum
Calculate volume in
Enter the tank’s
Enter the tank’s length
Set total and grand
Set total to count up or
Set grand total to count
Set start for total or
Program analog output
Select source for the
Program mA output for
Program mA output for
Set relay condition if
Force analog output
Ignore loop break
Program maximum mA
Program minimum mA
Parity
t-byt
SelEct
Functn
Linear
No PtS
Square
Parity
Time byte
Select
Input signal
conditioning
Linear
Number of
Square root
Select parity
Even, Odd, or None
Set byte-to-byte
Enter the Select menu
Select linear, square
root, programmable
exponent, or round
Set meter for linear
function and select
number of linearization
Set meter for 2 to
Set meter for square
35
Calib
4 nmA
20 nmA
user
F1
F2
F3
Calibrate
4 mA output
20 mA output
User I/O
F1 function
F2 function
F3 function
Calibrate 4-20 mA
output (internal
reference source used
Enter mA output value
read by milliamp meter
with at least 0.001 mA
Enter mA output value
read by milliamp meter
with at least 0.001 mA
Assign function keys
Assign F1 function key
Assign F2 function key
Assign F3 function key
Page 36
Series APM Analog Panel Meter Instruction Manual
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
(digital input)
modules connected
modules connected
without a signal source
for scaling the input)
input (e.g. 4 mA)
input (e.g. 20 mA)
calibration
input
input (e.g. 0 V)
input (e.g. 10 V)
settings
test)
number and version
meter’s memory
Rounding Feature (round)
The rounding feature is used to give the user a
F4
dI I
dO 1
ICal
C CAL
C lo
C Hi
v CAL
v Lo
v Hi
F4 function
Digital input 1
Digital output 1
Internal source
calibration
Current
calibration
Current low
Current high
Voltage
Voltage low
Voltage high
Assign F4 function
Assign digital input
1 – 8, if expansion
Assign digital output
1 – 8, if expansion
Enter internal source
calibration (used for
scaling the meter
Calibrating 4-20 mA
current input (internal
reference source used
Calibrate low current
Calibrate high current
Calibrating voltage
Calibrate low voltage
Calibrate high voltage
steadier display with fluctuating signals. Rounding is
used in addition to the filter function.
Rounding causes the display to round to the nearest
value according the rounding selected. See examples
below:
Rounding
Selection
1 12.022 12.022 12.023 12.023
5 12.022 12.020 12.023 12.025
10 12.024 12.020 12.025 12.030
Actual
Value
Display
Value
Actual
Value
Display
Value
Modbus RTU Serial
Communications (serial)
The meter is equipped with serial communications
capability as a standard feature using Modbus RTU
Serial Communication Protocol.
The meter may be connected to a PC for initial
configuration via the on-board micro USB connection.
For ongoing digital communications with a computer
or other data terminal equipment, an RS-232, or RS485 option is required; see Ordering Information on
page 6 for details.
Diag
LED t
Info
Erase
Diagnostics
LED test
Information
Erase
Display parameter
Test all LEDs
(press menu to exit
Display software
Erase Panel Meter Pro
software stored in
Noise Filter (filter)
The noise filter is available for unusually noisy signals
that cause an unstable process variable display. The
noise filter averages the input signal over a certain
period. The filter level determines the length of time
over which the signal is averaged. The filter level can
be set between 2 and 199. The higher the filter level,
the longer the averaging time and so the longer it
takes the display to settle to its final value. Setting the
filter level to zero disables the filter function.
Noise Filter Bypass (bypass)
The noise filter bypass changes the behavior of the
meter so that small variations in the signal are filtered
out but large abrupt changes in the input signal are
displayed immediately. The bypass value determines
the minimum amount of signal change to be displayed
immediately. All signal changes smaller than the
bypass value are filtered or averaged by the meter.
The noise filter bypass may be set between 0.1 and
99.9% of full scale.
•DO NOT connect any equipment other than
Dwyer’s expansion modules, cables, or meters to
the RJ45 M LINK connector. Otherwise damage
will occur to the equipment and the meter.
Note: More detailed instructions are provided with
each optional serial communications adapter.
Note: Refer to the APM Modbus Register Tables
located at www.dwyer-inst.com for details.
When using more than one meter in a multi-drop mode,
each meter must be provided with its own unique
address. The meter address (Slave ID) may be
programmed between 1 and 247. The transmit delay
may be set between 0 and 199 ms. The parity can be set
to even, odd, or none with 1 or 2 stop bits.
36
Page 37
Series APM Analog Panel Meter Instruction Manual
Table 13-3
Head (Feet)
CFS
GPM
MGD
Function
Desire
Programming
Select Menu (SElEct)
The Select menu is used to select the input signal
conditioner applied to the input (linear, square root,
programmable exponent, or round horizontal tank),
low-flow cutoff, and analog output programming. The
multi-point linearization is part of the linear function
selection.
Input Signal Conditioning (Functn)
The Function menu is used to select the input signal
conditioner applied to the input: linear, square root,
programmable exponent, or round horizontal tank
volume calculation. The multi-point linearization is
part of the linear function selection.
Meters are set up at the factory for linear function with
2-point linearization. The linear function provides a
display that is linear with respect to the input signal.
Multi-Point Linearization (Linear)
Meters are set up at the factory for linear function with
2-point linearization. Up to 32 linearization points can
be selected under the linear function. The multi-point
linearization can be used to linearize the display for
non-linear signals such as those from level
transmitters used to measure volume in odd-shaped
tanks or to convert level to flow using weirs and
flumes with complex exponent.
The programmable exponent can be used to linearize
the signal from level transmitters in open-channel flow
applications using weirs and flumes.
The APM meter, in combination with an ultrasonic
level transmitter, makes for an economical way to
measure and display open channel flow rate and total
in most weirs and flumes. A guide such as the ISCO
Open Channel Flow Measurement Handbook can
provide the user with all the information needed: the
exponent used in the flow equation for the desired
flow units and the flow rate for any given head height.
For example, to display the open channel flow rate
from a 3" Parshall flume, the ISCO handbook advises
the exponent is 1.547 and at the maximum head
height of 3.0 feet, the flow rate is 3.508 MGD.
3" Parshall Flume Discharge Table with Head in
Feet
Formula: CFS = 0.9920 H
MGD = 0.6411 H
Where: H = head in feet
3.00 5.428 2436 3.508
ISCO Open Channel Flow Measurement Handbook, 3rd edition
With this information the APM should be programmed
in the following fashion. This setup assumes the level
transmitter is programmed to output 20 mA at the
maximum head height of 1.10 feet; but any mA value
at a head height with a known flow rate may be used.
Programmable Exponent
Linearization (
Prog E)
Application: Open Channel Flow
1.547
GPM = 445.2 H
1.547
1.547
Square Root Linearization
(
Square)
The square root function can be used to linearize the
signal from a differential pressure transmitter and
display flow rate in engineering units.
37
Open Channel
Flow
Flow Rate
Total
Non-Resettable
Grand Total
Display
3" Parshall flume
Millions of
Gallons per Day
(MGD)
Millions of
Gallons
Program meter
so grand total can
never be reset
Display Flow
Rate, Total, and
Grand Total
Set Programmable Exponent to
1.547
Set 4 mA = 0
20 mA = 3.508
Time base = Day
Set Totalizer Conversion Factor = 1
(password protect “total” to avoid
accidental reset)
Set non-resettable grand total
password
Set upper display for Grand Total
and lower display to toggle
between rate and total.
Page 38
Series APM Analog Panel Meter Instruction Manual
Round Horizontal Tank
Linearization (
This function automatically calculates the volume in a
round horizontal tank with flat ends. This function is
only used when Total is set to no.
Set the display for the desired decimal point and
engineering units before entering the round horizontal
tank function. Select units, inches or cm for the tank
dimension. Enter the diameter and the length in
inches and the results are given in US gallons. Enter
the diameter and length in cm and the results are
calculated automatically in liters.
The meter can be scaled to display the volume in any
engineering unit.
Note: After Scale is displayed continue pressing the
Enter button until the meter completes the
scaling of the input and display values.
Changing the Volume from Gallons to Liters
In the above graphic, entering the 48" for the diameter
and 120" for the length of the round horizontal tank,
the meter automatically calculates that the volume of
the tank is 940.02 gallons.
1. Convert gallons to liters
1 US gallon = 3.7854 L
940.02 gal = 3558.4 L
2. Go to the Setup menu and change the decimal
point to 1 decimal.
3. Go to the Program – Scale menu and press Enter
until dis 2 is shown on the main display.
4. Press Enter and change the display 2 value to
3558.4.
5. The meter is now displaying the volume in liters.
Note: The display can be scaled to display the volume
in any engineering units.
Another way to display the volume in liters is to enter
the dimensions in cm. The meter automatically
calculates the volume in liters.
rHt)
Totalizer Count Up/Down (Count)
The totalizer count up/down menu may be used to
program the total and grand total to either count up
from 0 when reset or count down from a programmed
value when reset. Total and grand total may have
their countdown numbers programmed individually
from 0 to 999999.
Analog Output Programming
(AoutPr)
The Analog Output Programming menu is used to
program the behavior of the 4-20 mA output. The
following parameters and functions are programmed
in this menu:
1. Source: Source for generating the 4-20 mA
output (e.g. PV)
2. Overrange: Analog output value with display in
overrange condition
3. Underrange: Analog output value with display in
underrange condition
4. Break: Analog output value when loop break is
detected
5. Max: Maximum analog output value allowed
regardless of input
6. Min: Minimum analog output value allowed
regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source
reference used to scale the 4-20 mA output
Analog Output Source
The source for generating the 4-20 mA output may be
assigned to the rate/process variable, total, grand
total, maximum or minimum value reached by the
rate/process, or one of the set points, or the Modbus
PV input.
Low-Flow Cutoff (CutofF)
The low-flow cutoff feature allows the meter to be
programmed so that the often-unsteady output from a
differential pressure transmitter, at low flow rates,
always displays zero on the meter.
The cutoff value may be programmed from 0 to
999999. The meter will display zero below the cutoff
value. Programming the cutoff value to zero disables
the cutoff feature.
Analog Output Calibration
To perform the analog output calibration, it’s
recommended to use a milliamp meter with a
resolution of at least 0.1 µA to measure the output
current. The values saved internally during this
procedure are used for scaling the 4-20 mA output in
the Setup menu.
38
Page 39
Series APM Analog Panel Meter Instruction Manual
Function Keys & Digital I/O Available Settings
Display
Description
Directly access the relay menu
Directly access the set point menu for
relay 1 (*through 8)
Disable all relays until a button
Rly E
pressed
Enable all relays to function as they
have been programmed
Rly E
pressed
to be calculated in the background.
Display maximum display value on line 1
Display minimum display value on line 1
Display maximum & minimum display
values on line 1
Display maximum display value on line 2
Display minimum display value on line 2
Display maximum & minimum display
values on line 2
Display the grand total on line 2
Function Keys & Digital I/O Available Settings
Display
Description
Force relay 1 (*through 4) into the on
page 32 for details.
Directly access the control menu
Disable the selected function key or
digital I/O
Acknowledge all active relays that are in
manual or latching
Directly access the reset menu
Reset the total
Reset the grand total
Reset the stored maximum display
value
Reset the stored minimum display value
Reset the stored maximum & minimum
display values
Mimic the menu button functionality
(digital inputs only)
Mimic the right arrow/F1 button
functionality (digital inputs only)
Mimic the up arrow/F2 button
functionality (digital inputs only)
Mimic the enter/F3 button functionality
(digital inputs only)
Provide indication when alarm 1
outputs only)
*If installed
Programmable Function Keys
User Menu (user)
The User menu allows the user to assign the front
panel function keys F1, F2, and F3, the digital input
F4 (a digital input located on the input signal
connector), and up to eight additional digital inputs to
access most of the menus or to activate certain
functions immediately (e.g. reset total, reset grand
total, reset max & min, hold relay states, etc.). This
allows the meter to be greatly customized for use in
specialized applications.
Up to eight digital outputs can be assigned to a
number of actions and functions executed by the
meter (i.e. reset total, reset grand total, alarms, relay
acknowledgement, reset or display max, min). The
digital outputs can be used to trigger external alarms
or lights to indicate these specific events.
F On 1*
Contrl
disabl
AcH
Reset
Rst t
Rst gt
Rst Hi
Rst Lo
Rst HL
state. This function is used in
conjunction with a digital input
expansion module to achieve interlock
functionality. See
Interlock Relay (Force On) Feature
a manual operation mode such as auto-
Setting Up the
on
Function Keys & Digital I/O
Available Settings
Refer to the following table for descriptions of each
available function key or digital I/O setting.
relay
Set 1*
Rly d
Rly E
O Hold
d Hold
assigned to enable relays (
Hold current relay states and analog
output as they are until a button
assigned to enable relays (
Hold the current display value, relay
states, and analog output momentarily
while the function key or digital input is
active. The process value will continue
) is
) is
nmenu
rigHt
up
Enter
Alnm 1*
(*through 8) has been triggered (digital
Ln1 Hi
Ln1 Lo
Ln1 HL
Ln2 Hi
Ln2 Lo
Ln2 HL
Ln2 gt
39
Page 40
Series APM Analog Panel Meter Instruction Manual
The meter is factory calibrated prior to shipment
Notes:
1. If meter is in operation and it is intended to
Input range
Input 1 & input 2 span
4-20 mA
0.15 mA
±10 VDC
0.10 VDC
Internal Source Calibration (ICAL)
for milliamps and volts with calibration equipment
that is certified to NIST standards.
The use of calibrated signal sources is necessary to
calibrate the internal source of the meter. The
meter’s internal source is what allows the user to
scale the meter without applying a signal.
Check calibration of the meter at least every
12 months. Each input must be recalibrated
separately.
accept only one input type (e.g. 4-20 mA),
recalibration of other input is not necessary.
2. Allow the meter to warm up for at least
15 minutes before performing the internal
source calibration procedure.
The Internal calibration menu is part of the Advanced
Features menu.
1. Press and hold the Menu button for three
seconds to access the advanced features of the
meter.
2. Press the Up arrow button to scroll to the Internal calibration menu (ICAL) and press Enter.
3. The meter displays either current calibration
(C CAL) or voltage calibration (V CAL), according
to the input setup. Press Enter to start the
calibration process.
Example of Internal Calibration for current
input:
4. The meter displays low input current message
(C lo). Apply the low input signal and press
Enter. The display flashes for a moment while the
meter is accepting the low input signal.
5. After the display stops flashing, a number is
displayed with the leftmost digit brighter than the
rest. The bright digit is the active digit that can be
changed by pressing the Up arrow button. Press
the Right arrow button to move to the next digit.
6. Set the display value to correspond to the input
signal being calibrated, typically
4.000 mA.
7. The display moves to the high input calibration
(C Hi). Apply the high input signal and press
Enter.
8. Set the display for the high input calibration, in
the same way as it was set for the low input
calibration, typically 20.000 mA.
The graphic shows the calibration of the current input.
The voltage input is calibrated in a similar way.
Tips:
•Low and high input signals can be any valid
values within the range of the meter.
•Observe minimum input span requirements
between input 1 and input 2.
•Low input should be less than high input signal.
However, the low display can be higher than the
high display (i.e. 4-20 mA = 100.0 to 0.0).
Error Message (Error)
An error message indicates that the calibration or
scaling process was not successful.
After the error message is displayed, the meter
reverts to the input prior to the failure during
calibration or scaling and to input 1 during internal
calibration, allowing the appropriate input signal to be
applied or programmed.
The error message might be caused by any of the
following conditions:
5. Input signal is not connected to the proper
terminals or it is connected backwards*.
6. Wrong signal selection in Setup menu*.
7. Minimum input span requirements not
maintained.
8. Input 1 signal inadvertently applied to calibrate
input 2*.
*Not relevant when scaling the meter.
Minimum Input Span
The minimum input span is the minimum difference
between input 1 and input 2 signals required to complete
the calibration or scaling of the meter.
40
Page 41
Series APM Analog Panel Meter Instruction Manual
Button
Symbol
Description
Meter Operation
The meter is capable of accepting current (0-20 mA,
4-20 mA) and voltage signals (0-5 V, 1-5 V, 0-10 V,
±10 V) and displaying these signals in engineering
units from -99999 to 999999 (e.g. a 4-20 mA signal
could be displayed as -50.000 to 50.000).
The dual-line display can be customized by the user
to operate in such a way as to satisfy a specific
application. Typically, the main display is used for the
process variable; while the second display is used for
engineering units, custom legend, total, grand total, or
set point indication.
The meter can be set up to display the analog input
on the main display and the Modbus input on the
second display. The relays and analog output can be
programmed to operate from the Modbus PV input.
Front Panel Buttons Operation
Press to enter or exit Programming
Mode, view settings, or exit max/min
readings
Press to reset max/min readings or
other parameter/function assigned
through the User menu
Press to display max/min readings or
other parameter/function assigned
through the User menu
Press to acknowledge relays or other
parameters/function assigned through
the User menu
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by
the process can be displayed either continuously or
momentary:
1. Display briefly by assigning to the F1-F3 function
keys or to the digital inputs in the User menu.
2. Display continuously by assigning either display
to max/min through the Display menu.
Any of the F1-F3 function keys (buttons) and the
digital inputs can be programmed to reset the max &
min readings. The meters are set at the factory to
display the max reading by pressing the Up arrow/F2
button and to use the Right arrow/F1 button to access
the Reset menu.
To display max reading using function key with
factory defaults:
1. Press Up arrow/F2 button to display maximum
reading since the last reset/power-up.
2. To reset max/min press Right arrow/F1 button to
access the Reset menu. The max & min displays
are reset to actual values.
3. Press Menu to exit max/min display reading.
To display max/min readings continuously:
Assign either display to Max (d Hi), Min (d Lo), or
toggle between Max and Min (d HL) every 10
seconds.
Function Keys Operation
During operation, the programmable function keys
operate according to the way they have been
programmed in the Advanced Features – User menu.
See Programmable Function Keys User Menu (user)
on page 39 for details.
The table above shows the factory default settings for
F1, F2, and F3.
F4 Operation
A digital input, F4, is standard on the meter. This
digital input is programmed identically to function keys
F1, F2, and F3. The input is triggered with a contact
closure to COM, or with an active low signal. During
operation, F4 operates according to the way it has
been programmed in the Advanced Features – User
menu. See Programmable Function Keys User Menu
(user) on page 39 for details.
Totalizer Overflow Displays
Total to 9 Digits
These flow rate/totalizers can display up to nine digits
of total flow with the total overflow feature.
In the diagrams above, the flow totalizer is displaying
532,831,470 by toggling between a display of
“oF 532” and “831470”. Notice the T with arrow ▲
symbol is lit up indicating the display is in overflow
mode.
41
Page 42
Series APM Analog Panel Meter Instruction Manual
Troubleshooting
Due to the many features and functions of the meter,
it’s possible that the setup of the meter does not
agree with what an operator expects to see.
If the meter is not working as expected, refer to the
Diagnostics menu and recommendations below.
Diagnostics Menu (diag)
The Diagnostics menu is located in the Advanced
Features menu, to access Diagnostics menu see
Advanced Features Menu on page 34.
This menu allows the user to test the functionality of
all the meter LEDs, check the meter’s software and
version information, and erase the Panel Meter Pro
software installation files from the meter. Press the
Enter button to view the settings and the Menu button
to exit at any time.
For a description of the diagnostic messages, see Advanced Features Menu & Display Messages on
page 35.
Determining Software Version
To determine the software version of a meter:
1. Go to the Diagnostics menu (diAG) and
press Enter button.
2. Press Up arrow button and scroll to
Information menu (Info).
3. Press Enter to access the software number
(SFT) and version (UER) information. Write
down the information as it is displayed.
Continue pressing Enter until all the
information is displayed.
4. The meter returns to Run Mode after
displaying all the settings.
Reset Meter to Factory Defaults
When the parameters have been changed in a way
that is difficult to determine what’s happening, it might
be better to start the setup process from the factory
defaults.
Instructions to load factory defaults:
1. Enter the Advanced Features menu. See
Advanced Features Menu on page 34.
2. Press Up arrow to go to Diagnostics (diAG) menu
3. Press and hold Right arrow for three seconds,
press Enter when display flashes reset.
Note: If Enter is not pressed within three
seconds, the display returns to the Diagnostics
menu.
4. The meter goes through an initialization
sequence (similar as on power-up), and loads the
factory default settings.
42
Page 43
Series APM Analog Panel Meter Instruction Manual
Factory Defaults & User Settings
The following table shows the factory setting for
most parameters.
Parameter Display Default Setting
Input type
Total
Units
Filter
Bypass
Function
Number of points
Programming
Input 1
Display 1
Input 2
Display 2
Decimal point
Cutoff value
Display line 1
Display line 2
Display intensity
Total time base
Total conversion
factor
Total reset
Grand total time
base
Grand total
conversion factor
Grand total reset
Total count
up/down
Grand tot count
Relay 1
assignment
Relay 2
assignment
Relay 3
assignment
Relay 4
assignment
Input
total
units
filter
bypass
Functn
No Pts
prog
InP 1
Dis 1
InP 2
Dis 2
ddd.ddd
CutofF
Line 1
Line 2
d-Inty
T tb
T CF
T rst
GT tb
gT CF
gT rst
Tot C
Gtot C
Asign1
Asign2
Asign3
Asign4
4-20 mA
Yes
Rate / total / gr. total
mA / mA / mA
70
0.2
Linear
2
Scale
4.000 mA
4.000
20.000 mA
20.000
3 places
0.000 (disabled)
Rate/Process
Total value
6
Second
1.000
Manual
Second
1.000
Manual
Up
Up
Total
Total
Rate
Rate
Parameter Display Default Setting
Relay 1 action
Relay 1 set point
Relay 1 reset point
Relay 2 action
Relay 2 set point
Relay 2 reset point
Relay 3 action
Relay 3 set point
Relay 3 reset point
Relay 4 action
Relay 4 set point
Relay 4 reset point
Fail-safe relay 1
Fail-safe relay 2
Fail-safe relay 3
Fail-safe relay 4
Display 1 analog
out
Output 1 value
Display 2 analog
out
Output 2 value
Source analog
output
Overrange output
Underrange output
Loop break output
Maximum output
Minimum output
F1 function key
Password 1
Password 2
Password 3
Total password
Grand total
password
Act 1
Set 1
RSt 1
Act 2
Set 2
RSt 2
Act 3
Set 3
RSt 3
Act 4
Set 4
RSt 4
Fls 1
Fls 2
Fls 3
Fls 4
Dis 1
Out 1
Dis 2
Out 2
Source
O-rang
u-rang
break
nmAx
nmin
F1
Pass 1
Pass 2
Pass 3
Total
Gtotal
Automatic
1.000
0.000
Automatic
2.000
0.000
Automatic
3.000
2.500
Automatic
4.000
3.500
Off
Off
Off
Off
4.000
4.000 mA
20.000
20.000 mA
Rate/process
21.000 mA
3.000 mA
1.000 mA
23.000 mA
1.000 mA
Reset max & min
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
43
Page 44
Series APM Analog Panel Meter Instruction Manual
Symptom
Check/Action
No display at all
Check power at power connector
Not able to change setup or programming,
is displayed
Meter is password-protected, enter correct six-digit password to
unlock
If a Low-Flow Cutoff Value has been programmed, the meter will
cutoff value.
Check:
3. Minimum input span requirements
Meter displays
2.
2. Corresponding signal at Signal connector
Check:
3. Filter and bypass values (increase)
Display response is too slow
Check filter and bypass values
Check:
2. Scaling or calibration
Display does not respond to input changes,
reading a fixed number
Check:
Display assignment, it might be displaying max, min, or set point.
Display alternates between
2. Lo and a number
Check:
2. Wiring of relay contacts
Check:
2. Set and reset points
Flashing relay status LEDs
Relays in manual control mode or relay interlock switches opened.
Check:
3. Meter address and baud rate
If the display locks up or the meter does not
respond at all
Other symptoms not described above
Call Technical Support for assistance.
Troubleshooting Tips
This meter is a highly sophisticated instrument with an extensive list of features and capabilities. If the front panel
buttons are used to program the meter, it may be a difficult task to keep everything straight. That is why we strongly
recommend the use of the free Panel Meter Pro software for all programming activities. A cable is provided with the
meter for programming with Panel Meter Pro software.
If you have programmed the meter with the front panel buttons and it is not working as intended, try re-programming
the meter using Panel Meter Pro software.
Locd
display zero below that point, regardless of the input – which can
Meter does not respond to input change
appear like the meter is not responding to an input change. Check to
make sure the problem is not being caused by an undesired low-flow
Meter displays error message during
calibration (Error)
1. 999999
-99999
Display is unstable
Display reading is not accurate
1. Hi and a number
Relay operation is reversed
Relay and status LED do not respond to
signal
1. Signal connections
2. Input selected in Setup menu
Check:
1. Input selected in Setup menu
1. Input signal stability and value
2. Display scaling vs. input signal
1. Input signal conditioner selected: Linear, square root, etc.
Press Menu to exit max/min display readings.
1. Fail-safe in Setup menu
1. Relay action in Setup menu
Meter not communicating with application
programs
Note: Certain sequences of events can cause unexpected results. To solve these issues, it is best to start fresh from
factory defaults and use the manual as a step by step programming guide, rather than a random approach to
programming. To reset the meter to factory defaults, see Reset Meter to Factory Defaults on page 42. In addition, for
best results, we recommend using the free Panel Meter Pro software for all programming needs.
1. Serial adapter and cable
2. Serial settings
Cycle the power to reboot the microprocessor.
44
Page 45
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, IN 46360, U.S.A.
Fax: 219/872-9057
e-mail: info@dwyermail.com
07/20
Phone: 219/879-8000 dwyer-inst.com
LIM6200DW_H
SFT039 Ver 4.010 & up
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.