Dwyer A-435-A User Manual

Model A-435-A Remote Display Tool
Specifications - Installation and Operating Instructions
Bulletin P-A-435-A
n option for Magnesense
A
ave a display would be to use a Model A-435-A remote display tool which can plug
h
nto the connector shown in Figure 1. The remote display tool has two buttons that
CALIBRATION
NOTICE
calibration takes place. This delay is used to prevent stress related offsets on the lower ranges.
NOTICE
adjusted by the user.
Zero Calibration
The zero calibration can be set by applying zero pressure to both the pressure ports and pressing the zero button for 3 seconds. The display will read ZEro and then sequence back to the home display. If the current reading is not close enough to zero (±2%), the operation will fail and FAIL will be displayed.
®
I Differential Pressure Transmitter models that do not
I
Figure 1
There is a 5 second delay from the time the zero or span calibration buttons is released until the time that the change in
The security level that is set in the Programming Menu Section of the manual will determine which calibrations, if any, may be
PAN Calibration
S
he span calibration can be adjusted only after setting the zero adjustment. It must
T
e completed within 5 minutes of the last zero calibration. The span calibration
b button will be ignored until the zero calibration is completed. Apply pressure to the ports of the transmitter that is associated with the maximum output of the transmitter (20 mA, 5 V, or 10 V depending on output being used). Press and hold the span button for 3 seconds. The display will read SPAn and then sequence back
o the home display. If the span calibration is attempted before adjusting the zero
t calibration, the FAIL error message will flash on the display. For bi-directional ranges, separate spans can be performed for positive and negative sides of the range. A failure will also occur if the span operation is performed too closely to the
ero point pressure.
z
isplay Error Messages
D
ovEr = The applied pressure is greater than the maximum span value causing an Over Range Error. UndEr = The applied pressure is less than the minimum span value causing an Under Range Error. FAiL = When the span or zero buttons are pressed, the pressure value is out of the range to allow a correct setting. This may be due to a sensor failure or incorrect pressure being applied.
Err1 = The sensor is damaged.
-rErr = Negative display value too low to display.
PROGRAMMING MENUS
Home Menu
During normal operation, the display will be in the Home Menu and will display the current measured pressure and the engineering units.
Menu Access Security
While in the Home Menu, press and hold the Zero and Span buttons simultaneously until SECUr appears on the display in order to access the other programming menus. Upon releasing the buttons, the display will indicate the current security level.
If the current security level is the security level desired (i.e. Security Level 0), press and hold the span button for three seconds to enter the Pressure, Velocity, or Air Flow Menu.
If the security level is not the desired level, the security level can be changed temporarily to a lower security level or permanently to a higher level of security by pressing the zero button. A security code will be shown on the display and it can be changed to one of the codes listed in the below table. The span button chooses which digit and the zero button increments the value of that digit. Pressing and holding the span button will store the value.
Access
Yes Yes
No No
Edit
Menu
Yes
No No No
Span
Yes
No No No
Zero
Yes Yes Yes
No
Security
The level of access to the programming menus and the calibration is limited based on the security level. The above table details the level of access for each security level.
Level
0 1 2 3
Setting
View
Menu
000 111 222 333
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyermail.com
ode Selection / Digital Dampening Menu
M
rom the home display, pressing the span and zero button simultaneously for 3
F
econds will access the Menu Security Level. If the level is set to 0 or 1, pressing and
s
olding the span button for 3 seconds a second time will access the Mode Selection
h Menu. The display will default to Pressure when first powered up. Pressing the zero button will cycle to Velocity and Flow.
nce the desired Mode is displayed, pressing and holding the span button for three
O
econds will save the selected mode and display the digital dampening or averaging
s
arameter. This parameter stabilizes the output and the display by averaging the
p
eadings. There are 2.5 readings taken each second and the user can select the
r number of seconds that they would like to average up to 240 seconds. The display and the output will continue to update at a rate of 2.5 updates per second, but the moving average is used for these updates.
RESSURE MODE
P
aximum Output Adjustment
M
If the Pressure Mode was selected, pressing and holding the span after adjusting the digital dampening will enter the Pressure Mode. In this menu, the maximum output pressure (POH) can be adjusted to any pressure between the lowest dip switch range to the highest dip switch range. If the dip switch settings are preferred over manually
etting the range, the POH parameter can be set to off.
s
ELOCITY MODE
V K-Factor Adjustment
If the Velocity Mode was selected, pressing and holding the span after adjusting the digital dampening will enter the Velocity Mode and the transmitter will display the engineering unit that has been selected by the dip switch. Pressing and holding the
pan button for three seconds will enter the K – Factor adjustment. The K – Factor
s
an be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing
c
he span button to select the digit and pressing the zero button to increment the value
t of the digit. Pressing and holding the span button for three seconds will enter the Maximum Output Adjustment parameter.
Maximum Output Adjustment
The maximum output can be equivalent to a velocity or a pressure. After adjusting the K-Factor, the display will indicate if the adjustment is set for pressure or velocity. Pressing the zero button will toggle between the selections. Pressing and holding the span button for three seconds will enter the maximum output adjustment. The maximum output can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for three seconds will save this value and go to the Security Update Menu.
FLOW MODE K-Factor Adjustment
If the Flow Mode was selected, pressing and holding the span after adjusting the digital dampening will enter the Flow Mode and the transmitter will display the engineering unit that has been selected by the dip switch. Pressing and holding the span button for three seconds will enter the K – Factor adjustment. The K – Factor can be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for three seconds will enter the Area Adjustment parameter.
ressing the zero button will toggle between yes and no. Yes will save the changes
P
ade to all menu items and no will discard all the changes made to all menu items.
m
f the display is set to yes, pressing and holding the span will save the menu items
I
nd return the display to the Home Position.
a
FACTORY DEFAULT PROCEDURE
n order to reset all of the menu settings back to their factory programmed values,
I
ress and hold both the span and zero buttons simultaneously for 10 seconds until
p
ACt is displayed on the LCD. Upon releasing the buttons, the unit will be factory
F
efaulted. Since resetting the transmitter will wipe out all changes, it is necessary to
d zero (and possibly span) the transmitter before taking measurements.
MAINTENANCE/REPAIR
pon final installation of the A-435-A, no routine maintenance is required. The A-435-
U
is not field serviceable and it is not possible to repair the unit. Field repair should
A
ot be attempted and may void warranty.
n
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the
roduct back for repair. Be sure to include a brief description of the problem plus any
p
dditional application notes.
a
APPENDIX I Air Velocity / Air Flow Calculations
Velocity is calculated using the below equation:
elocity(fpm) = K-Factor x 4004.4 x √(Diff. Press. (in of w.c.)
V
Velocity in m/s is then calculated from the equation:
Velocity(m/s) = Velocity(fpm) x 0.00508
Flow is calculated using the below equation:
Flow(cfm) = Area(Ft
3
/h) = Flow (cfm) x 1.6992
Flow (m
2
) x K-Factor x 4004.4 x √(Diff. Press. (in of w.c.)
APPENDIX II Maximum Flow
Max Displayed Flow
Range in w.c.
0.5
5885000
5
5885000
28
5885000
CFM
9999000 9999000 9999000
Max (K Factor x Area)
3
M
CFM Mode
/H
2037.2
644.2
272.2
3
M
/H Mode
154.5
59.9
25.3
Area Adjustment
For Flow applications, the area is multiplied by the velocity to determine the volumetric air flow. The area will be listed in either feet or meters depending on the dip switch settings. The units will be indicated on the display at the time of adjustment.The area can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for three seconds will enter the Maximum Output Adjustment parameter.
Maximum Output Adjustment
The maximum output can be equivalent to a flow or a pressure. After adjusting the Area parameter, the display will indicate if the adjustment is set for pressure or flow. Pressing the zero button will toggle between the selections. Pressing and holding the span button for three seconds will enter the maximum output adjustment. The maximum output can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for three seconds will save this value and go to the Security Update Menu.
Security Update / Save Changes Menu
The Security Update Menu allows the security level to be set either higher or lower than the current security level setting. This security level will be displayed the next time the Menus are accessed from the home screen. Pressing the zero button cycles through the security levels. Pressing and holding the span button for three seconds accepts the new security level and gives the option to save all the menu changes.