Dwyer 4G, 8G, 16G Manual

Page 1
1
Love Controls – A Div. of Dwyer Instruments Inc. – Michigan City, IN 46360 – PH: 800-879-8000 – www.dwyer-inst.com
Series 4G/8G/16G
Temperature/Process Controllers
DANGER! Caution! Electric Shock! When the power is on, DO NOT touch the AC terminals in case an electric
shock may occur. Make sure the power is disconnected when you check the input power supply.
Prevent dust or metallic debris from falling into the controller and causeing malfunctions. DO NOT modify or
uninstall the controller.
Series 4G/8G/16G is an open-type device. Make sure it is installed in an enclosure free of dust and humidity to
limit the potential for electric shock.
Wait for one minute after the power is switched off to allow the capacitor to discharge. DO NOT touch the internal
wiring within this period of time.
Series / Panel size (W×H)
16: 1/16 DIN W48 × H48mm 8: 1/8 DIN W48 × H96mm 4: 1/4 DIN W96 × H96mm
Output 1 options
2: Voltage pulse, 12V ±10% 3: Relay, 250 VAC, 5A 5: DC current, 4 to 20m A 6: L: Linear voltage, 0 to 10 VDC
Output 2 options
2: Voltage pulse, 12V ±10% 3: Relay, 250 VAC, 5A 5: DC current, 4 to 20m A 6: L: Linear voltage, 0 to 10 VDC
Optional Function 1
0: None 1: Event input 2 3: Retransmission output 4: CT input 2
Optional Function 2
0: None 1: Event input 1 2: Remote setpoint input 4: CT input 1
Options
“Blank”: AC 100 to 240V LV: DC 24 V±10%
Warning
Display, LED & Keys
Ordering Information
Page 2
Series 4G/8G/16G Temperature/Process Controllers
2
Love Controls – A Div. of Dwyer Instruments Inc. – Michigan City, IN 46360 – PH: 800-879-8000 – www.dwyer-inst.com
Supply Voltage
AC 100 to 240 V -20/+8%, 50/60Hz; Optional DC 24 V ±10%
Power Consumption
5 VA
Display
Process Value: 4-digit, orange LCD Setpoint Value: 4-digit, green LCD
Input sensors Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
RTD: Pt100, JPt100, Cu50, Ni120
Analog input: 0 to 5 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA, 0 to 50 mV
Control modes
PID, PID program (ramp/soak) , Fuzzy, Manual, ON/OFF, 2PID
Tuning method
Auto-tuning, Self-tuning
Display Resolution
0 or 1 digit to the right of the decimal point
Sampling rate
Analog input: 0.1s, Thermocouple or platinum RTD: 0.1s
Ambient temperature
0 to +50°C
Ambient humidity
35 to 80% RH (non-condensing)
Model
Panel cutout ( W × H )
16G
45mm × 45mm
8G
44.5mm × 91.5mm
4G
91mm × 91mm
4G/8G Wiring Terminals
16G Wiring Terminals
Specifications
Panel Cutout
Wiring
Page 3
Series 4G/8G/16G Temperature/Process Controllers
3
Love Controls – A Div. of Dwyer Instruments Inc. – Michigan City, IN 46360 – PH: 800-879-8000 – www.dwyer-inst.com
Regulation Mode
Operation Mode
Initial Setting Mode
Auto-tuning (Set in PID control and RUN
mode) Press
Use to set up target temperature
Press
Set up input type
Press
Self-tuning switch (set when in PID
control and the TUNE parameter = ST)
Control loop RUN or STOP
Set up temperature unit (not displayed
when in analog input)
Select the nth (n = 0 ~ 5) PID. When n =
AUTO, PID is auto-selected.
Set up start pattern (when in PID
programmable control and )
Set up upper temperature limit
Set up PID control offset
Set up start step (when in programmable
control)
Set up lower temperature limit Set up Fuzzy gain value
Set up the position of decimal point
Select control modes
Set up Fuzzy Deadband
Lock the keys
Select SV control modes
Adjust Output 1 hysteresis (when in
ON/OFF control)
Set up upper limit of Alarm 1
Set up waiting temperature (when in
programmable control)
Adjust Output 2 hysteresis (when in
ON/OFF control)
Set up lower limit of Alarm 1
Set up waiting time (when in
programmable control)
Control cycle for Output 1 (except in
ON/OFF control)
Set up upper limit of Alarm 2
Set up start slope (when in programmable
control)
Control cycle for Output 2
(except in ON/OFF control)
Set up lower limit of Alarm 2
Select pattern to be edited
Ratio of Output 1 against Output 2 when in dual output control (set when in PID and dual output control)
Set up upper limit of Alarm 3
Select AT or ST
Set up deadband (when in dual output)
Set up lower limit of Alarm 3
Select heating, cooling or dual output heating and cooling
Set up input filter factor
Record highest temperature of Alarm 1
Set up Alarm 1 mode
Set up input filter range
Record lowest temperature of Alarm 1
Set up Alarm 1 options
Adjust input compensation
Record highest temperature of Alarm 2
Set up Alarm 1 delay
Adjust input gain
Record lowest temperature of Alarm 2
PV color change
Set up rising slope (when CRTS = SLOP)
Record highest temperature of Alarm 3
2PID Switch temperature
Adjust upper limit compensation for
analog Output 1*
Record lowest temperature of Alarm 3
2PID Return temperature
Adjust lower limit compensation for analog Output 1*
Display and adjust Output 1 volume
Set up Remote type
Adjust upper limit compensation for analog Output 2*
Display and adjust Output 2 volume
Select auxiliary function
Adjust lower limit compensation for analog Output 2*
Set up percentage of upper limit for Output 1
Select auxiliary function 2
Adjust upper limit compensation for Retransmission*
Set up percentage of lower limit for Output 1
Enable/disable communication write-in
Adjust lower limit compensation for Retransmission*
Set up percentage of upper limit for Output 2
Select ASCII or RTU format
Adjust Remote gain
Set up percentage of lower limit for Output 2
Set up communication address
Adjust Remote compensation
Display current measured at CT1
Set up baudrate
Set up EVENT1 function
Display current measured at CT2 Press to return to set up target temperature
Set up data length
Set up EVENT2 function
Set up stop bit
Set up EVENT3 function Press to return to auto-tuning
Set up parity bit Press to return to set up input type
Select the nth PID (n = 0 ~ 5)
Press 0 ~ 5th PID
Set up the 0th PID temperature value Press
Set up the 5th PID temperature value Press
Set up the 0th proportional band value
Set up the 5th proportional band value
Set up the 0th Ti value
Set up the 5th Ti value
Set up the 0th Td value
Set up the 5th Td value
Set up the 0th PID integral deviation
Press to return to PID deviation
Set up the 5th PID integral deviation
Press to return to PID deviation
Parameters Operation
*1 scale = 2μA; 1scale = 1mV
PID mode: Any of the 6 PID groups can be selected. When n = AUTO, the program will automatically select the PID group that
is the closest to the target temperature.
Page 4
Series 4G/8G/16G Temperature/Process Controllers
4
Love Controls – A Div. of Dwyer Instruments Inc. – Michigan City, IN 46360 – PH: 800-879-8000 – www.dwyer-inst.com
Select the pattern number to be edited Select number
Press to select OFF
Edit temperature for Step 0
Press
Select actual number of steps when the program is executing
Press
Exit pattern and step editing and switch to to continue the setup process.
Edit time for Step 0 (time unit: hr, min)
Set up additional cycles (0 ~ 99) for the pattern execution
Set up Step 0 ~ 15 in order
Set up link pattern. OFF refers to the program end.
Press to return to select the pattern number
to be edited
Edit temperature for Step 15
Edit time for Step 15
Press to set up actual step numbers
Address
Content
Definition
1000H
Present value (PV)
Measuring unit: 0.1 scale. The following values read mean error occurs. 8002H: Temperature not yet acquired 8003H: Not connected to sensor 8004H: Incorrect sensor
1001H
Set value (SV)
Measuring unit: 0.1 scale.
1002H
Upper limit of temp. range
Cannot exceed the default value
1003H
Lower limit of temp. range
Cannot fall below the default value
1005H
Control mode
0: PID, 1: ON/OFF, 2: Manual, 3: FUZZY
1006H
Heating/cooling control
0: Heating/ Heating, 1: Cooling/ Heating, 2: Heating/cooling, 3: Cooling/ Cooling
1007H
1st heating/cooling control cycle
0.1 ~ 99.0 sec.
1008H
2nd heating/cooling control cycle
0.1 ~ 99.0 sec.
1009H
Proportional band (PB)
0.1 ~ 999.9
100AH
Ti value
0 ~ 9,999
100BH
Td value
0 ~ 9,999
1012H
Read/write Output 1 volume
Unit: 0.1%, only valid in manual control mode
1013H
Read/write Output 2 volume
Unit: 0.1%, only valid in manual control mode
1016H
Regulated temp. value
-99.9 ~ +99.9, Unit: 0.1
102AH
Read/write LED status
b0: ALM3, b1: ALM2, b2: °F, b3: °C, b4: ALM1, b5: OUT2, b6: OUT1, b7: AT
102BH
Read/write key status
b0: Set, b1: Select, b2: Up, b3: Down, 0: Press it
102CH
Panel lockup status
0: Normal, 1: Fully locked, 2: SV adjustable
102DH
CT value
Unit: 0.1A
103BH
AT setting
0OFF(default), 1ON
103CH
Control RUN/STOP setting
0 : STOP, 1RUN (default), 2 : END (program), 3 : HOLD (program)
Patterns and steps: Edit in parameter. Take editing pattern 0 for example:
SPxx & TMxx parameters save must be after Press in parameter.
RS-485 Communication
Series 4G/8G/16G Controllers support baudrate 2,400 to 38,400 bps, Modbus ASCII/RTU protocol, function code
03H and reads maximum 8 words from the register.
Page 5
Series 4G/8G/16G Temperature/Process Controllers
5
Love Controls – A Div. of Dwyer Instruments Inc. – Michigan City, IN 46360 – PH: 800-879-8000 – www.dwyer-inst.com
SV
Alarm mode
Alarm output operation
0
No alarm
1
Alarm output will be enabled when the temperature reaches upper or lower limit: The alarm will be enable when the PV exceeds SV + AL-H or falls below SV – AL-L.
2
Alarm output will be enabled when the temperature reaches the upper limit: The alarm will be enabled when the PV exceeds SV + AL-H.
3
Alarm output will be enabled when the temperature reaches the lower limit: The alarm will be enabled when the PV falls below SV – AL-L.
4
Alarm output will be enabled when the temperature reaches the absolute value of the upper or lower limit: The alarm will be enabled when the PV exceeds AL-H or falls below AL-L.
5
Alarm output will be enabled when the temperature reaches the absolute value of the upper limit: The alarm will be enabled when the PV exceeds AL-H.
6
Alarm output will be enabled when the temperature reaches the absolute value of the lower limit: The alarm will be enabled when the PV falls below AL-L.
7
Upper limit hysteresis alarm: The alarm will be enabled when the PV exceeds SV + AL-H. The alarm will be disabled when the PV falls below SV + AL-L.
8
Lower limit hysteresis alarm: The alarm will be enabled when the PV falls below SV – AL-H. The alarm will be disabled when the PV exceeds SV – AL-L.
9
Offline alarm: The alarm will be enabled when the input sensor is not correct or offline.
10
Timing alarm
11
CT1 alarm: The alarm will be enabled when the CT1 value falls below AL-L or exceeds AL-H.
12
CT2 alarm: The alarm will be enabled when the CT2 value falls below AL-L or exceeds AL-H.
13
When SOAK status (temperature hold) happens to PID program control, alarm output is ON.
14
When RAMP UP status happens to PID program control, alarm output is ON.
15
When RAMP DOWN status happens to PID program control, alarm output is ON.
16
When RUN status happens to PID program control, alarm output is ON.
17
When HOLD status happens to PID program control, alarm output is ON.
18
When STOP status happens to PID program control, alarm output is ON.
19
When END status happens to PID program control, alarm output is ON.
ON
OFF
SV-(AL-L) SV SV+(AL-H)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
SV SV+(AL-H)
SV-(AL-H) SV-(AL-L) SV
SV SV+(AL-L) SV+(AL-H)
AL-L
AL-H
AL-L AL-H
SV-(AL-L) SV
AL-L AL-H
ON
OFF
Alarm Outputs
Series 4G/8G/16G controllers offer 3 alarm outputs, and each alarm output has 20 alarm modes to choose from in
the initial setting mode.
Loading...