2. Wire your control following the instructions on page 5. If you are using
a two-wire transmitter as an input, see the drawing and instructions on
page 6. Option wiring instructions are on Page 7. Option descriptions
and specific instructions start on page 16.
3. Most controls do not need many (if any) program changes to work on
your process. For best results when programming changes are
necessary, make all the necessary changes in the Secure Menu (page
26) before making changes to the Secondary Menu (page 19). If error
messages occur, check the Diagnostic Error Messages on page 35 for
help.
Take the example of a Model 86010 that comes from the factory pro-
grammed for type J thermocouples. Suppose for this example you wish to
change the input to type K and limit the set point range between 0° and
1000° C.
First, enter the Secure menu as instructed on page 5. Press the INDEX key
until the display shows Inp and press the DOWN ARROW until the display
shows CA. Don't forget to press the ENTER key to retain your setting.
Next, press the INDEX key to display Unit. Press the DOWN ARROW until
the display shows C. Press ENTER.
Next, press the INDEX key until SPL is displayed (pass the dPt and InPt
selections). Press the UP ARROW until the display shows 0. Press
ENTER.
Finally, press INDEX key to display SPH. Press the DOWN ARROW until
the display shows 1000. Press ENTER.
The necessary program changes are now complete. After 30 seconds the
display will switch back to the temperature reading. If you want to return
faster, press the UP ARROW and ENTER keys (at the same time) and then
press the DOWN ARROW and INDEX keys ( again at the same time). This
will 'back out' of the menu and immediately display the temperature reading.
If you want to use Self Tune®, Auto/Manual, or the Ramp/Soak Programmer features, see the special sections on these items. Page numbers for
these are in the Contents section on the previous page.
December, 1998Page 3949-1277-3
Page 4
MODEL IDENTIFICATION
Model 8 6 ———
Alarm
0 = No
1 = Yes
Output 1
1 = SSR
2 = 15 VDC
3 = Relay
5 = Current
Output 2
0 = None
1 = SSR
3 = Relay
5 = Current
2 = 15 VDC
INSTALLATION
Mount the instrument in a location that will not be subject to excessive
temperature, shock, or vibration. All models are designed for mounting in an
enclosed panel.
Select the position desired for the instrument on the panel.
Prepare the panel by cutting and deburring the required opening.
From the front of the panel, slide the instrument through the cut out. The
housing gasket should be against the housing flange before installing.
From the rear of the panel slide the mounting collar over the housing. Hold
the housing with one hand and using the other hand, push the collar evenly
against the panel until the springs are compressed. The ratchets will hold the
mounting collar and housing in place.
OPTIONS
Orientation
0 = Vertical
1 = Horizontal
PANEL CUTOUTS
Vertical
Horizontal
949-1277-3Page 4December, 1998
Page 5
It is not necessary to remove the control chassis from the
housing for installation. If the control chassis is removed
from the housing, you must follow industry standard practice for control and protection against Electro-Static Discharge (ESD). Failure to exercise good ESD practices may
cause damage to the control.
WIRING
Do not run thermocouple or other class 2 wiring in the same conduit as power
leads. Use only the type of thermocouple or RTD probe for which the control
has been programmed. Maintain separation between wiring of sensor,
auxiliary in or out, and other wiring. See the "Secure Menu" for input selection.
For thermocouple input always use extension leads of the same type designated for your thermocouple.
For supply connections use No. 16 AWG or larger wires rated for at least 75°C.
Use copper conductors only. All line voltage output circuits must have a
common disconnect and be connected to the same pole of the disconnect.
Input wiring for thermocouple, current, and RTD; and output wiring for 15 VDC
is rated CLASS 2.
Wiring to housing terminals while chassis is removed
may cause distortion of the internal connector and possible damage to the connector when the chasis is reinstalled. It is strongly recomended that the control
housing be wired with the chassis installed.
Control wiring is as shown.
+
1
21
T/C
2
V
RTD
6
NO
ALARM 1
7
8
9
OUTPUT*
C
NO
ALARM 2
OUTPUT*
C
-
3
4
+
5
6
7
8
9
10
22
23
24
+
-
24 VDC
@ 50 mA
ISOLATED
SET POINT
1 OUTPUT*
SET POINT
2 OUTPUT*
F1
15VDC
pulsed
RELAY
NC
C
+
NO
-
NC
C
+
NO
-
CURRENT
SSR
+
-
+
-
* IF SWITCHING INDUCTIVE LOADS
(RELAYS, MOTORS, SOLENOIDS,
ETC.) USE AN R/C SNUBBER
ACROSS COIL.
11
12
13
14
15
16
17
18
19
20
F1 = 3/8A 250VAC MEDIUM LAG
LINE INPUT
UNUSED TERMINALS CAN NOT BE USED
AS TIE POINTS FOR OTHER CIRCUITS.
SEE RATING LABEL
FOR DETAILS
December, 1998Page 5949-1277-3
13
14
15
16
17
18
Page 6
Wiring for Transmitter inputs
Wire power and outputs as shown on previous page. Two-wire transmitters
wire as shown below.
For three or four wire transmitters follow the wiring instructions provided
with your transmitter.
DO NOT WIRE THE 24 VOLT POWER SUPPLY ACROSS
THE INPUT OF THE CONTROL. DAMAGE TO THE CON-
TROL INPUT CIRCUITRY WILL RESULT.
Wiring for Optional Inputs and Outputs
Wire power and outputs as shown on page 5. Wiring for options is shown
opposite. All wiring shown below is Class 2. Shielded twisted pair is
recommended for Option 992.
DO NOT RUN SIGNAL WIRING IN THE SAME CONDUIT
OR CHASE AS THE POWER WIRING. ERRATIC OPERA-
TION OR DAMAGE TO THE CONTROL CIRCUITRY WILL
RESULT.
949-1277-3Page 6December, 1998
Page 7
OPTION 10 21 22
948 & 949 Truth Table
948 Sig. Ground B A
936 Not Used + 924 Not Used + 926 Not Used + 928 Not Used CCW Wiper
10
1
2
3
4
5
6
7
8
9
21
23
24
22
11
12
13
14
15
16
17
18
19
20
A to Gnd. B to Gnd. SP
OPEN OPEN 1SP1
CLOSED OPEN 2SP1
OPEN CLOSED 3SP1
CLOSED CLOSED 4SP1
SWITCH CONTACTS FOR
OPTIONS 948 AND 949 MUST
BE ISOLATED AND CAN NOT
SHARE WIRING WITH OTHER
CONTROLS.
993 Signal Ground Data In Data Out
949 Signal Ground A B
December, 1998Page 7949-1277-3
Page 8
FRONT PANEL KEY FUNCTIONS
Set Point 1 LampAlarm Lamps
Set Point 2 Lamp°F Indicator
Process Display°C Indicator
Set Point DisplayRemote Set Lamp
Manual IndicatorPer Cent Lamp
Heater Break IndicatorHold Lamp
The decimal point flashes when Self-Tune is operating.
Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next
menu item. May also be used in conjunction with other keys as noted
below.
UP ARROW: Increments a value, changes a menu item, or
selects the item to ON. The maximum value obtainable is 9999
regardless of decimal point placement.
DOWN ARROW: Decrements a value, changes a menu item, or
selects the item to OFF. The minimum value obtainable is -1999
regardless of decimal point placement.
ENTER: Pressing ENTER stores the value or the item changed. If
not pressed, the previously stored value or item will be retained. The
display will flash once when ENTER is pressed.
AUTO/MANUAL: This key toggles the control output between
Automatic mode and Manual mode. Press and hold key for three
seconds to activate. See section on AUTO/MANUAL operation on
Page 13.
RUN/HOLD: This key toggles the Ramp/Soak programmer functions
between Run mode (program runs as set up), and Hold mode (program
functions are suspended). Press and hold key for three seconds to
activ ate. See section on Programmer Functions (Page 10) for further
details.
949-1277-3Page 8December, 1998
Page 9
UP ARROW & ENTER: Pressing these keys simultaneously brings up
the secondary menu starting at the alarm, tune, or cycle item (depending
on programming). Pressing these keys for 5 seconds will bring up the
secure menu.
INDEX & DOWN ARROW: Pressing these keys simultaneously will allow
backing up one menu item, or if at the first menu item they will cause the
display to return to the primary menu. If an alarm condition has occurred,
these keys may be used to reset the alarm.
INDEX & ENTER: Pressing these keys simultaneously and holding them
for 5 seconds allows recovery from the various error messages. The
following menu items will be reset:
ALiH: Alarm inhibitOPEn InP: Input error message
bAd InP: Input error message CHEC CAL: Check calibration error
Correct the problems associated with the above conditions before
using these reset keys. More than one error could be present. Caution is
advised since several items are reset at one time.
While in the Primary orSecondary Menu, if no key is pressed for a period
of 30 seconds, the display will return to the HOME position displaying the
temperature value. While in the SecureMenu, if no key is pressed for a
period of 60 seconds, the display will return to the HOME position displaying
the temperature value. Outputs are disabled (turned off) when the Secure
Menu is active.
NOTE: To move to the Primary Menu quickly from any other menu, press
the UP ARROW & ENTER keys followed by pressing the INDEX & DOWN
ARROW keys.
SECURITY LEVEL SELECTION
Four levels of security are provided. The display shows the current security
level. To change security levels change the password value using the UP &
DOWN ARROW keys and pressing the ENTER key. Refer to the password
table (following) for the correct value to enter for the security level desired.
The SECr menu item security level may be viewed or changed at any time
regardless of the present security level.
To set the access level to, for example, 2, at the SECr menu item press the
UP ARROW key until the upper display show the password, 1101. Press
the ENTER key. The display will blink, and return with the level value, 2, in
the upper display.
December, 1998Page 9949-1277-3
Page 10
The password values shown in the table cannot be altered, so retain a copy
of these pages for future reference. This is the only reference made to
password values in this instruction book.
PASSWORD TABLE
Security Level
MenuStatus
PrimaryLocked
SecondaryLocked
SecureLocked
PrimaryUnlocked
SecondaryLocked
SecureLocked
PrimaryUnlocked
SecondaryUnlocked
SecureLocked
PrimaryUnlocked
SecondaryUnlocked
SecureUnlocked
Displayed Value
When Viewed
1
2
3
4
Password Value
To Enter
1110
1101
1011
111
NOTATION CONVENTIONS FOR THE MENUS
Because of the number of features available in this control, information is
included that may not apply to your specific control. All usable features are
included in this book, but may not be used in your process. To increase
clarity the following conventions are used:
1. Certain features or functions shown in this book are contextual. This
means that Menu Items may or may not appear, depending on other Menu
Item selections. Whenever this occurs, a notation is made in the Menu Item
that "controls" or "directs" other menu items. If you are looking for a
particular menu item and can't find it, check the menu item that is its
"control" for proper setting.
2. The "#" symbol is used in two ways. It is used inside a group of
characters to indicate which set point function (SP1 or SP2) is being
affected. It is also used before a group of characters of a menu item to
indicate that there may be more than one selection or value for that menu
item. This is used for certain repeated items such as in the Ramp/Soak
Program section.
949-1277-3Page 10December, 1998
Page 11
THE HOME DISPLAY
The home display is the normal display while the control is operating. If no
errors or functions are active, the HOME display will indicate the Process
Variable (the temperature, pressure, flow, RH, etc., that is being measured)
on the top display and the Set Variable (Set Point 1) on the bottom.
Items that can change the HOME display are the Auto/Manual function, the
Run/Hold function, the Prog function, the PCtO function, and any error
message. Description of these special displays follow.
If the Auto/Manual key is pressed, the Manual indicator lights, and the home
display is changed. The upper display continues to show the Process
Variable (PV), but the lower display changes to show the percentage of
output in tenths of a percent to 99.9% (0.0 to 99.9), or 100 if 100%. The
display digit to the right of the number shows a flashing letter o to indicate
that the value displayed is no longer the SV, but percent output. The SP2
output is indicated by the use of an overline on the letter õ. Access to the
SP2 value is done by the INDEX key. See Auto/Manual Operation on Page
13 for further information.
If Prog is turned On, the HOME display changes the SV display from SP1
to the Present Set Variable as calculated by the Ramp/Soak Programmer
function. See Programming and Operation for Ramp/Soak Feature below
for more information.
If PCtO (Secondary Menu) is turned On, the lower display changes to show
the active percentage of output as required to maintain SP1. The display
is similar to the Auto/Manual display above, except that the letter indicators
do not flash, and the output is displayed in whole percentages of output, not
in tenths of a percent. If the control has both SP1 and SP2, the lower display
will alternate between the SP1 percent output and the SP2 percent output.
Error messages are listed on Page 35.
PROGRAMMING AND OPERATION FOR RAMP / SOAK
FEATURE
The ramp / soak feature offers a great deal of flexibility by allowing changes
in the set point to be made over a predetermined period of time. Dwell times
can be programmed, and the alarm output relays can be programmed to
open or close during any of the segments.
Theory of Operation
The 8600 Series controls offer a very simple approach to programming a
ramp. Rather than requiring the operator to calculate an approach rate
(usually in degrees per minute), the 8600 does the calculation internally.
December, 1998Page 11949-1277-3
Page 12
Thus, the operator only needs to program the target set point and the time
desired to reach that point. When the ramp segment is executed by the
control, it calculates the ramp required to move the process from the
starting value (current PV) to the desired value (programmed SP) in the
time allowed.
Soaks (or dwells) are ramp segments where the target set point is the same
as the beginning process value. This allows for multistage ramps without
wasting intermediate soak steps. Care must be taken, however, that the
process does actually reach the soak value before the soak time starts. If
not, the next segment will calculate a slope from the starting PV to the target
SP. Depending on your process requirements, this difference may be
important. Make sure to test any program for desired results before running
production material.
Do not operate Self Tune while a ramp function is operating. The
ramp function will prevent the Self Tune from operating properly.
Make sure that all tuning is set up before operating Ramp / Soak.
Program Setup
All of the programming for the Ramp / Soak function is done in the
Secondary Menu. You may wish to work out your program on paper before
going into the programmer menu sequence.
In the Secondary Menu INDEX to Prog and make sure that Prog is set to
OFF.
INDEX to PSEt and turn On.
Skip the StAt setting (this is discussed later) and press INDEX to 1ti.
The following items repeat in the following order: 1ti, 1SP, 1A1 (if alarm 1
is programmed as an event), 1A2 (if alarm 2 is programmed as an event),
2ti, 2SP, 2A1, 2A2, . . . , 16ti, 16SP, 16A1, 16A2. To avoid repetition each
item will only be described once.
Set 1ti to the amount of time you want for the first ramp. This value is in
time units (determined by the tbAS menu item) from 0 to 9999. Press
INDEX
Set 1SP to the target value desired for the first ramp. This value is in actual
units just like SP1. If the control is programmed for temperature, then the
SP displays are in temperature. If the control is programmed for some other
engineering unit, the SP is set in that unit.
949-1277-3Page 12December, 1998
Page 13
Press INDEX to continue. If Alarm 1 is programmed as an event, then 1A1
will appear. If you wish the Alarm 1 contact to function for this segment, set
1A1 for On. If not, set for OFF. Press INDEX. If Alarm 1 is not programmed
as an event, then 1A1 will not appear. If 1A1 is set to On, the Alarm 1
function will be active for the entire period as set in 1ti above.
If Alarm 2 is programmed as an event, then 1A2 will appear. If you wish the
Alarm 2 contact to function for this segment, set 1A2 for On. If not, set for
OFF. Press INDEX. If Alarm 2 is not programmed as an event, then 1A2
will not appear. If Alarm 2 is not programmed as an event, then 1A2 will
not appear. If 1A2 is set to On, the Alarm 2 function will be active for the
entire period as set in 1ti above.
Complete setting the segment times (2ti ... 16ti), segment set points (2SP... 16SP), and event alarms (2A1 ... 16A1 and / or 2A2 ... 16A2) if they exist.
For Unneeded or unused segments set the segment times (2ti ... 16ti) to0, and set the segment set points (2SP ... 16SP) to the same value as the
last active set point. Event alarms may be set to indicate "end of run" as
you feel necessary.
The last menu item for the ramp / soak function is PEnd. PEnd determines
what the control does when the program has ended. You may choose to
have the program repeat (LooP), Hold the last set point (16SP), revert to
the local SP1, or turn the outputs off (OoFF).
It is important to remember that if you want the program to repeat, you must
allow the process to return to the same condition that existed when the
program first started. Remember that the ramp function calculates the
slope by drawing a line from the beginning PV to the ramp target set point.
If the PV at the end of the program is different than the PV at the initial start,
the ramp will calculate differently.
Ramp / Soak Operation
When you wish to start the program, enter the Secondary Menu and set the
Prog menu item to On. Return to the HOME position by waiting for the
display to time out or by pressing the UP ARROW / ENTER keys and then
the DOWN ARROW / INDEX keys.
The home display will read as it normally does. The HOLD indicator over
the RUN / HOLD key will be lit. To start the program press the RUN / HOLD
key. The HOLD indicator will go out, and the program will start.
December, 1998Page 13949-1277-3
Page 14
To suspend the program at any time, press the RUN / HOLD key. Press
the key again to resume.
Pressing the AUTO / MANUAL key will also suspend the program operation. The difference is that AUTO / MANUAL also puts the control into
manual mode. See Auto / Manual Operation on page 13.
The function of the Primary Menu will change depending on the setting of the
StAt menu item in the Secondary Menu. If StAt is OFF then the Primary Menu
is not changed.
If the StAt menu item is set to On, then the Primary Menu has three
additional information items added before SP1 appears. The first INDEX
item, ####/ ti, displays the time remaining in the current segment. The next
INDEX item, ####/##ti, displays the total time for the active segment
(1ti...16ti). The third INDEX item, ####/##SP, displays the segment set
value (1SP...16SP). The next INDEX press resumes the normal Primary
Menu
AUTO / MANUAL OPERATION
The AUTO / MANUAL function allows you to manually adjust the output of
the control. This is normally used during process setup or start up. It can
also be used for troubleshooting. To switch from AUTO to MANUAL press
the AUTO / MANUAL key. The MANual indicator will light and the lower
display will change from normal to showing the actual output in percent. The
value will be the actual percentage of output that was active when the key
was pressed. This is usually known as "bumpless transfer".
If you wish to change the output while in manual, press the UP ARROW or
DOWN ARROW keys to change the value, and press ENTER to retain it. It
is important to remember that the value of the display is read as 0 to 100%
of the full control output, NOT the range between S1OL and S1OH or S2OL
and S2OH. For example, if the set point one output is programmed for 4 to
20 mA (S1OL=20, S1OH=100), a reading of 50% in MANUAL represents
10 mA, not 12mA. This allows the operator to go above and below the output
range to allow for improperly function equipment that may be connected to
the control output.
To return to AUTOmatic control, press the AUTO / MANUAL key again. The
MANual indicator will go out, and the set point will take over. If you want
bumpless transfer back to AUTO, slowly change the percentage of output
until the process variable matches (or at least is close) to the set point. The
further away the PV is from the set point, the greater the "bump" or upset
there will be in the output.
949-1277-3Page 14December, 1998
Page 15
OPERATION OF SELF TUNE® FUNCTION
Self Tune® allows automatic selection of the necessary parameters to
achieve best control operation from your 8600 Series control. If you are
using the control output as a simple on-off function (Out1 set for OnOF),
none of the following will apply.
Theory of Operation
The Self Tune function calculates the Pb1, rES, and rtE parameters under
the PID tunE selection, and the Fbnd and FrtE parameters, as shown in the
Secondary Menu . These values are determined by measuring the response
of the process connected to the control. When Self Tune is started, the
control temporarily acts as an on-off control. While in this mode the control
measures the overshoot and undershoot of the process, and the period of
the process (the time from peak value to the next peak value). These
measurements are collected over a period that lasts three periods of
overshoot and undershoot. The data collected over this time is then
compared and calculated into final PID and Fuzzy Logic values. The effect
of Fuzzy Logic on the process is still controlled by the Fint (fuzzy intensity)
setting. If Fint is 0, the Fbnd and FrtE will be calculated, but will have no
effect. The calculations for the PID values are the same as used in the
standard Ziegler - Nichols equations that have been recognized as standard
for decades.
The only modification to the application of the Ziegler - Nichols equations is
controlled by the dFAC menu item. This menu item controls the amount of
rate (derivative) that is applied. A dFAC setting of 3 (factory default) or less
allows for less damping. A dFAC setting of 4 allows for critical damping as
set forth in Ziegler - Nichols. A dFAC setting of 5 or more allows over
damping of the process.
Program Setup and Operation
In the secondary menu set tunE to SELF. Skip LErn and check to make
sure that dFAC is set to the desired value. Back up to LErn and set to YES.
The control will begin the Self Tune function. While the Self Tune function
is active, the right hand decimal point on the lower display will blink. When
Self Tune is complete, the blinking will stop.
After Self Tune is complete, the tunE setting automatically switches to PID.
This allows examination and / or modification of the values calculated. We
recommend that you do not change the calculated values unless you have
a firm understanding of the parameters involved and their function. For more
information on PID tuning, please contact your supplier.
December, 1998Page 15949-1277-3
Page 16
OPERATION AND PROGRAMMING OF OPTIONS
Options 924, 926, 928, Analog Remote Set Point
The analog remote set point allows the control set point to be determined by
an outside analog signal. The signal may be 0 to 10 VDC (Option 924), 0
(or 4) to 20 mADC (Option 926), or 0 to 10,000 Ohms (Option 928).
Wire the input as shown on page 7.
To set up the analog remote set point, first determine the scale range that
the analog signal will represent. The maximum span is 11,998 degrees or
counts. In the Secure Menu set rSCL for the scale value that will be
represented by the low end of the analog signal (0 Volts, 0 mA, 0 Ohms). Set
rSCH for the scale value that will be represented by the high end of the
analog signal (10 Volts, 20 mA, 10,000 Ohms).
If you require a suppressed scale or input, you may use the following
equations to determine the proper settings for rSCL and rSCH.
K = (Highest desired scale reading - Lowest desired scale reading) /
(Maximum desired analog signal - Minimum desired analog signal).
rSCH = ((Maximum possible analog signal- Maximum desired analog signal)
* K) + Highest desired analog reading.
rSCL = Lowest desired scale reading - ((Minimum desired analog signal) * K).
Operation is simple. Make sure that a valid analog signal is available to the
control. In the Secondary Menu set the rSPt to On. The REM indicator on the
front of the control will turn on. When the control returns to the HOME position,
the displayed SV will be the value supplied from the analog remote signal. If
the analog remote signal fails or goes out of range of the SPL or SPH settings,
the control will revert to the internal SP1 (or #SP1), and flash the error messageCHEC rSPt. If SPL or SPH are set outside of rSCL or rSCH then the error will
be suppressed, and the control will attempt to work with the remote value.
To clear the error message, change rSPt to OFF.
Option 934, 936, Analog Retransmission.
The analog retransmission option allows the Process Variable or the Set
Variable to be sent as an analog signal to an external device. The signal may
be either 0 to 10 VDC (Option 936) or 0 (or 4) to 20 mADC (Option 934). The
output may be changed in the field from one to the other by the toggle switch
located on the top printed circuit board.
Wire the output as shown on page 7.
949-1277-3Page 16December, 1998
Page 17
To set up the analog retransmission, first determine the scale range that the
analog signal will represent. The maximum scale is 9999°F, 5530°C, or
9999 counts. In the Secondary Menu set POL for the scale value that will
be represented by the low end of the analog signal (0 Volts or 0 mA). Set
POH for the scale value that will be represented by the high end of the analog
signal (10 Volts or 20 mA).
If you require a suppressed scale or output, you may use the following
equations to determine the proper settings for POL and POH.
K = (Highest desired scale reading - Lowest desired scale reading) /
(Maximum desired analog signal - Minimum desired analog signal).
POH = ((Maximum possible analog output - Maximum desired analog signal)
* K) + Highest desired analog reading.
POL = Lowest desired scale reading - ((Minimum desired analog output) * K).
Next select whether you want the retransmission signal to follow the Process
Variable or the Set Variable. Usually the Process Variable is sent to recorders
or other data acquisition devices. Usually the Set Variable is sent to other
controls to be used as an analog remote set point. If you want the analog
retransmission signal to follow the PV, in the Secondary Menu set POSr to InP.
If you want the analog retransmission signal to follow the SV, set POSr to SPt.
Operation is automatic. There are no further programming steps required.
Option 948, 4-Stage Set Point.
The 4-stage set point option allows four different values to be used for SP1 and
all of the values associated with the tunE menu items. The control will switch
to a given stage when an external contact or contacts are made or opened
across the appropriate terminals at the rear of the control (when SPSA, Set
Point Switch Action, is set for remote, rE), or when the stage is selected from
the Secondary Menu, SP (when SPSA is set for Int). When the state of a
contact changes (or the stage number is changed in the Secondary Menu), the
values in use are stored and the previously stored values for the new stage are
used.
Wire the input as shown on page 7.
Usually the control is configured for external switching of the stages. In this
case, the operation is usually automatic, selected by the external switches
driven by the machine logic. If it is necessary to program the stages in advance,
you may select the stage to modify with the SP menu item. When SP is
changed while the SPSA is set for rE, the selected stage is displayed for
modification, but only used when the appropriate contact is made.
December, 1998Page 17949-1277-3
Page 18
Option 992, 993, Serial Communication.
The serial communications options allow the control to be written to and read
from a remote computer or other similay digital device. Communication is
allowed either through a RS-485 (Option 992) port, or a RS-232 (Option 993)
port.
Wire the communication lines as shown on Page 7. Wiring for the RS-485 is
run from control to control in a daisy chain fashion with a termination resistor
(120 ohms) across the transmit and receive terminals of the last control in the
chain.
Select the control address and communication baud rate with the Addr and
bAUd menu items in the Secure Menu. THE BAUD RATE AND ADDRESS
MENU ITEMS WILL TAKE EFFECT ON THE NEXT POWER UP OF THE
CONTROL. BE SURE TO POWER CYCLE THE CONTROL BEFORE
USING THE NEW BAUD RATE AND ADDRESS.
In operation, you have the option of preventing a write command from the host
computer. To prevent the host from writing to the control change the LOrE
menu item in the Secondary Menu to LOC. To allow the host to write
commands to the control set LOrE to rE. (The host does have the ability to
change the LOrE state, but it is not automatic.)
If your system depends on constant reading or writing to and from the host, you
may wish to set the No Activity Timer (nAt) to monitor the addressing of the
control. When the LOrE is set to rE and the nAt is set to any value other than
Off, the control will expect to be addressed on a regular basis. If the control
is not addressed in the time set by the value of nAt, then the control will display
the error message CHEC LOrE. To clear the message set LOrE to LOC.
MENU SELECTIONS
PRIMARY MENU
Press INDEX to advance to the next menu item. Press UP ARROW or
DOWN ARROW to change the value in the display. Press ENTER to retain
the value. If StAt (Secondary Menu) is On, the three program status menu
items will precede the following.
#SP1(Option 948, 4-Stage Set Point) or
SP1Set Point 1 Adjust, Control Point 1.
SP2Set Point 2 Adjust (if equipped), Control Point 2.
949-1277-3Page 18December, 1998
Page 19
SECONDARY MENU
Hold UP ARROW & ENTER. Press INDEX to advance to the next menu
item. Press UP ARROW or DOWN ARROW to change the value in the
display. Press ENTER to retain the value.
A1LoAlarm 1 Low: The Low Alarm point is usually set below the Set
Point. May not appear depending on AL1 setting in Secure Menu.
A1HiAlarm High: The High Alarm Point is usually set above the Set
Point. May not appear depending on AL1 setting in Secure Menu.
A2LoAlarm 2 Low: The Low Alarm point is usually set below the Set
Point. May not appear depending on AL2 setting in Secure Menu.
A2HiAlarm 2 High: The High Alarm Point is usually set above the Set
Point. May not appear depending on AL2 setting in Secure Menu.
Out1Output selection: Select OnOf, 1tP, 1PuL, or ProP.
ONOFA setting of ONOF allows the control to operate as a
simple on/off mode. This setting forces the control to
turn off at set point, and on at the set point plus the
differential (SP_d). When selected, the Out1/OnOF
menu item is followed by ####/SP1d, and the tunE, Pb,rES, OFS, rtE, and ArUP selections in the Secondary
menu and the S1OL and S1OH selections in the Secure
menu are suppressed.
SP_dSet Point On-Off Differential (hysteresis). Se-
lect 1 to 9999 (direct acting), or -1 to -9999
(reverse acting). This value will be negative for
reverse acting set points, and positive for direct
acting outputs. Set the value for the amount of
difference between the turn off point (set point)
and the turn on point. The following drawing
shows output behavior for reverse and direct
action.
##tPTime Proportioning Cycle Time. Select 1tP to 80tP.
1tPA setting of 1tP is recommended for solid state
outputs (SSR or 15VDC).
2tP to 80tP Time Proportioning Control is adjustable in
1 second steps. Recommended for mechanical
outputs (relays, solenoids, etc.). For best contact life, a time should be selected as long as
possible without causing the process to wander.
#PuLPulsed Time Proportioning Output: Select 1PuL
December, 1998Page 19949-1277-3
Page 20
to 7PuL. 1PuL = Linear and 7PuL = most
nonlinear. Changes output linearity for use in
cooling applications or for an extremely fast
response processes. At the center of the proportional band, a pulse value of 1 provides an output
of one second on and one second off (50%
output). A pulse value of 2 provides an output of
one second on and two seconds off (33% output).
Output at center of band equals one second on,
(pulse value-1)
2
seconds off.
ProPFor Current (Code 5) outputs only.
The following menu items apply only if your control is equipped with
a second set point (last digit of model number is not zero). If your
control does not have a second set point, jump to the "tunE" menu on
the next page.
Out2Output selection: Select OnOf, 2tP, 2PuL, or ProP.
ONOFA setting of ONOF allows the control to operate as a
simple on/off mode. This setting forces the control to
turn off at set point, and on at the set point plus the
differential (SP2d). When selected, the Out2/OnOF
menu item is followed by ####/SP2d, and the Pb2
selection in the Secondary menu and the S2OL and
S2OH selections in the Secure menu are suppressed.
SP2dSet Point On-Off Differential (hysteresis). Se-
lect 1 to 9999 (direct acting), or -1 to -9999
(reverse acting). This value will be negative for
reverse acting set points, and positive for direct
acting outputs. Set the value for the amount of
difference between the turn off point (set point)
and the turn on point. The drawing opposite
shows output behavior for reverse and direct
action.
##tPTime Proportioning Cycle Time. Select 1tP to 80tP.
1tPA setting of 1tP is recommended for solid state
outputs (SSR or 15VDC).
949-1277-3Page 20December, 1998
Page 21
2tP to 80tP Time Proportioning Control is adjustable in
1 second steps. Recommended for mechanical
outputs (relays, solenoids, etc.). For best contact life, a time should be selected as long as
possible without causing the process to wander.
#PuLPulsed Time Proportioning Output: Select 1PuL
to 7PuL. 1PuL = Linear and 7PuL = most
nonlinear. Changes output linearity for use in
cooling applications or for an extremely fast
response processes. At the center of the proportional band, a pulse value of 1 provides an output
of one second on and one second off (50%
output). A pulse value of 2 provides an output of
one second on and two seconds off (33% output).
Output at center of band equals one second on,
(pulse value-1)
2
seconds off.
ProPFor Current (Code 5) outputs only.
SP(Option 948, 4-Stage Set Point) Active Set Point Stage. Select
1SP1, 2SP1, 3SP1, 4SP1 .
1SP1Set Menu Items to display Stage 1 for view and change
access. If SPSA is set for Int, 1SP1 is made active.
2SP1Set Menu Items to display Stage 2 for view and change
access. If SPSA is set for Int, 2SP1 is made active.
3SP1Set Menu Items to display Stage 3 for view and change
access. If SPSA is set for Int, 3SP1 is made active.
4SP1Set Menu Items to display Stage 4 for view and change
access. If SPSA is set for Int, 4SP1 is made active.
#SP1(Option 948, 4-Stage Set Point) Adjust Control Point 1 for Stage
selected above.
Note: The menu items for tunE (below) are modified when Option 948 is in
use. When Option 948 is active the menu items are preceeded with the stage
number selected in SP above. The stage number is noted here with the # sign.
When the 4 Stage Set Point option (948) is active, each stage has its own set
of tunE parameters.
#tun(Option 948, 4-Stage Set Point) or
tunETuning Choice: Select SELF, Pid, SLO, nor, or FASt.
SELFThe Controller will evaluate the Process and select the PID
values to maintain good control. Active for SP1 only.
LErnSelect YES or no
December, 1998Page 21949-1277-3
Page 22
YESStart Learning the Process. After the
process has been learned the menu
item will revert to no.
noLearning will stay in present mode.
dFAC Damping factor, Select OFF, 1 to 7. Sets the ratio
of Rate to Reset for the SELF tunE mode. 7 =
most Rate. Factory set to 3. For a fast response
process the value should be lowered (less Rate).
For a slower process the value should be increased (more Rate).
PidManually adjust the PID values. PID control consists of
three basic parameters, Proportional Band (Gain), Reset
Time (Integral), and Rate Time (Derivative).
#Pb1(Option 948, 4-Stage Set Point) or
Pb1Proportional Band (Bandwidth). Select 1 to 9999
°F, °C, or counts.
Pb2Proportional Band (Bandwidth). Select 1 to 9999
°F, °C, or counts. Appears only if control is
equipped with second set point and Out2 is NOT
selected as ONOF.
#rES(Option 948, 4-Stage Set Point) or
rESAutomatic Reset Time. Select OFF, 0.1 to 99.9
minutes. Select OFF to switch to OFS.
#OFS(Option 948, 4-Stage Set Point) or
OFS Manual Offset Correction Select OFF, 0.1 to 99.9%.
Select OFF to switch to rES.
#rtE(Option 948, 4-Stage Set Point) or
rtERate Time. Select OFF, 0.01 to 99.99 minutes,
Derivative.
SLOPID values are preset for a slow response process.
norPID values are preset for a normal response process.
FAStPID values are preset for a fast response process.
Pid2Linkage of PID parameters between SP1 and SP2: Select On or
OFF.
OnApplies SP1 rEs, rtE, Fbnd, and FrtE terms to SP2 for
heat/cool applications.
OFFSP2 functions without rEs, rtE, Fbnd and FrtE.
ArUPAnti- Reset Windup Feature: Select On or OFF.
OnWhen ArUP is On the accumulated Reset Offset value
will be cleared to 0% when the process input is not within
the Proportional Band.
OFFWhen ArUP is OFF, the accumulated Reset Offset
Value is retained in memory when the process input is
949-1277-3Page 22December, 1998
Page 23
not within the Proportional Band.
ArtEApproach Rate Time: Select OFF, 0.01 to 99.99 minutes. The
function defines the amount of Rate applied when the input is
outside of the Proportional Band. The ArtE time and the rtE time
are independent and have no effect on each other. To increase
damping effect and reduce overshoot set the approach rate time
for a value greater than the natural rise time of the process (natural
rise time = process value time to set point).
FintFuzzy Logic Intensity: Select 0 to 100%. 0% is OFF (disables Fuzzy
Logic). The function defines the amount of impact Fuzzy Logic will
have on the output.
FbndFuzzy Logic Error Band: Select 0 to 4000 °F, °C, or counts. Sets the
bandwidth of the Fuzzy Logic. Set Fbnd equal to PID proportional
band (Pb1) for best results.
FrtEFuzzy Logic Rate of Change: Select 0.00 to 99.99 counts/second.
For best initial setting, find the count/second change of process value
near set point 1 with output ON 100%. Multiply this value by 3. Set
FrtE to this calculated value.
PEAThe Peak feature stores the highest input the control has measured
since the last reset or Power On. At Power On PEA is reset to the
present input. To manually reset the value PEA must be in the lower
display. Press the ENTER key to reset. PEA will be reset and display
the present input value.
UALThe Valley feature stores the lowest input the Instrument has
measured since the last reset or Power On. At Power On UAL is reset
to the present input. To manually reset the value UAL must be in the
lower display. Press the ENTER key. UAL will be reset and display
the present input value.
PctOPercent Output Feature: Select On or OFF.
OnWhen selected On, the HOME lower display will indicate
the output of the controller in percent. An “o” will appear
in the right hand side of the lower display to indicate percent
output for SP1. An "õ" will appear on the right hand corner
of the lower display to represent percent output for SP2, if
the control is so equipped. The display will alternate
between these values.
OFFPercent Output display is disabled.
December, 1998Page 23949-1277-3
Page 24
ProgRamp/Soak Feature: Select On or OFF
OnAllows Programmed Ramp/Soak function to be started
by the Run/Hold key on the control front panel.
OFFTurns Ramp/Soak function OFF and resets program to
beginning.
PSEtProgrammer function set. Select On or OFF.
OffSkip Ramp/Soak Programming. Go to next Secondary
Menu Item, InPC on the next page.
OnEnable Ramp/Soak Programming.
StAtProgrammer Status Display in the Primary Menu when Prog (above)
is On: Select On or OFF.
OFFThe Primary Menu operates as normal.
OnThe Primary Menu is altered to have the following items
inserted before the SP1 menu item: ####/ti (time
remaining in segment), ####/##ti (total time in active
segment), and ####/##SP (segment target set point).
tbASRamp/Soak Time Base. Select 1_S or 60_S.
1_SRamp/Soak time base is in 1 second increments. Pro-
gram time 1ti...16ti is measured in seconds.
60_SRamp/Soak time base is in 60 second increments (min-
utes). Program time 1ti...16ti is measured in minutes.
The following items repeat in the following order: 1ti, 1SP, 1A1 (if
alarm 1 is programmed as an event), 1A2 (if alarm 2 is programmed as
an event), 2ti, 2SP, 2A1, 2A2, . . . , 16ti, 16SP, 16A1, 16A2. To avoid
repetition each item will only be described once.
1tiSegment Time: Select 0 to 9999 units (minutes if tbaS is set to
60_S, seconds if tbaS is set to 1_S.
1SPSegment Set Point: Select value as desired.
1A1Segment Alarm 1 Event: Select On or OFF .
OnAlarm 1 is active during segment 1 time (1ti).
OFFAlarm 1 is inactive during segment 1 time (1ti).
1A2Segment Alarm 2 Event: Select On or OFF.
OnAlarm 2 is active during segment 1 time (1ti).
OFFAlarm 2 is inactive during segment time (1ti).
949-1277-3Page 24December, 1998
Page 25
PEndProgram End action: Select Hold or OoFF.
HoldStay at the Present Set Point (16SP).
OoFFTurn Off SP1 and SP2 Outputs at the end of the program.
LooPRepeat program starting at 1ti.
SP1Revert to SP1 value.
InPCInput Correction: Select ±500 °F, °C, or counts. This feature allows
the input value to be changed to agree with an external reference
or to compensate for sensor error. Note: InPC is reset to zero
when the input type is changed, or when decimal position is
changed.
FiLtDigital Filter: Select OFF, 1 to 99. In some cases the time constant
of the sensor, or noise could cause the display to jump enough to
be unreadable. A setting of 2 is usually sufficient to provide enough
filtering for most cases, (2 represents approximately a 1 second
time constant). When the 0.1 degree resolution is selected this
should be increased to 4. If this value is set too high, controllability
will suffer.
LPbrLoop Break Protection: Select OFF, 1 to 9999 seconds. If, during
operation, the output is minimum (0%) or maximum (100%), and the
input moves less than 5°F (3°C) or 5 counts over the time set for LPbr,
the LOOP bAd message will appear. This condition can also be
routed to an Alarm Condition if alarms are present and turned On (see
ALbr in the secure menu). The loop break error can be reset by
pressing the ENTER key when at the LPbr menu item. The INDEX
& ENTER keys may also be used.
POL(Option 934, 936, Analog Retransmission Output) Process Output
Low: Select -450°F, -260°C, or -1999 counts to any value less than
POH.
POH(Option 934, 936, Analog Retransmission Output) Process Output
High: Select from any value greater than POL to +9999°F, +5530°C,
or 9999 counts.
POSr(Option 934, 936, Analog Retransmission Output) Process Output
Source: Select InP or SPt.
InPProcess output follows the Process Variable (input).
SPtProcess Output follows the Set Variable (SP1).
December, 1998Page 25949-1277-3
Page 26
rSPt(Option 924, 926, 928, Analog Remote Set Point) Remote Set Point:
Select On or OFF.
OFFThe control uses the value set for SP1.
OnThe control uses the value set by the analog remote set
point signal as established by the Secure Menu items
rSCL and rSCH. If the analog signal fails, the control will
display the error message CHEC/ LorE and revert to the
SP1 local value.
LOrE(Option 992, 993, Serial Communications) Local / Remote Status:
Select LOC or rE.
LOCThe host computer is advised not to send remote
commands. Any write commands sent to the controls
will be rejected.
rEThe host computer is allowed to send write commands.If
the control is not addressed within the time set in the nAt
(No Activity Timer, see Secure Menu) the CHEC LorE
error message will be displayed.
Addr(Option 992, Serial Communications) Control Address: Set from 1
to 3FF. This number (hexadecimal, base 16) must match the
address number used by the host computer. Viewed only in this
menu. To change this parameter, see Addr in the Secure Menu.
SECURE MENU
Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to advance to the
next menu item. Press UP ARROW or DOWN ARROW to change the value
in the display. Press ENTER to retain the value.
OUTPUTS ARE DISABLED (TURNED OFF) WHILE CONTROL IS IN
SECURE MENU.
SECrSecurity Code: See the Security Level Selection and the Password
Table in this manual, in order to enter the correct password.
InPInput Type: Select one of the following. Refer to the Input wiring
C-Type “C” Thermocouple
P392100 ohm Platinum (NIST 0.00392 Ω/Ω/°C)
n120120 ohm Nickel
P385100 ohm Platinum (DIN 0.00385 Ω/Ω/°C)
1P381000 ohm Platinum (DIN 0.00385 Ω/Ω/°C)
CurrDC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.
VoLtDC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.
diFFDC Voltage Input -10 to +10 mV.
----Reserved
OSUPZero Suppression: Select On or OFF. Only with Current and Voltage
input types.
OFFThe input range will start at 0 (zero) Input.
OnThe input range will start at 4.00 mA or 2.00 V.
UnitF, C or None.
F°F descriptor is On and temperature inputs will be dis-
played in actual degrees Fahrenheit.
C°C descriptor is On and temperature inputs will be dis-
played in actual degrees Celsius.
nonE°F and °C descriptors will be Off. This is only available with
Current and Voltage Inputs.
dPtDecimal Point Positioning: Select 0, 0.0, 0.00, or 0.000. On tempera-
ture type inputs this will only effect the Process Value, SP1, SP2,
ALLo, ALHi, and InPC. For Current and Voltage Inputs all Menu
Items related to the Input will be affected.
0No decimal Point is selected. This is available for all Input
Types.
0.0One decimal place is available for Type J, K, E, T, L,
RTD’s, Current and Voltage Inputs.
0.00Two decimal places is only available for Current and
Voltage Inputs.
0.000Three decimal places is only available for Current and
Voltage inputs.
InPtInput Fault Timer: Select OFF, 0.1 to 540.0 minutes. Whenever an
Input is out of range (UFL or OFL displayed), shorted, or open the
timer will start. When the time has elapsed, the controller will revert
to a safe condition (Output Off, Flashing Display). If OFF is
selected, the Input Fault Timer will not be recognized (time =
infinite).
SEnCSensor Rate of Change: Select OFF, 1 to 4000 °F, °C, or counts
per 1 second period. This value is usually set to be slightly greater
December, 1998Page 27949-1277-3
Page 28
than the fastest process response expected during a 1 second
period, but measured for at least 2 seconds. If the process is faster
than this setting, the SEnC bAd error message will appear. The
outputs will then be turned off. This function can be used to detect
a runaway condition, or speed up detection of an open thermocouple. Use the INDEX & ENTER keys to reset.
SCALScale Low: Select 100 to 9999 counts below SCAH. The total span
between SCAL and SCAH must be within 11998 counts. Maximum
setting range is -1999 to +9999 counts. For Current and Voltage
inputs, this will set the low range end. Viewable only for Thermocouple and RTD ranges.
SCAHScale High: Select 100 to 9999 counts above SCAL. The total span
between SCAL and SCAH must be within 11998 counts. Maximum
setting range is -1999 to +9999 counts. For Current and Voltage
inputs, this will set the high range end. Viewable only for Thermocouple and RTD ranges.
SPLSet Point Low: Select from the lowest input range value to SPH
value. This will set the minimum SP1 or SP2 value that can be
entered. The value for SP1 or SP2 will not stop moving when this
value is reached.
SPHSet Point High: Select from the highest input range value to SPL
value. This will set the maximum SP1 or SP2 value that can be
entered. The value for SP1 or SP2 will not stop moving when this
value is reached.
S1StSet Point 1 State: Select dir or rE.
dirDirect Action. As the input increases the output will
increase. Most commonly used in cooling processes.
rEReverse Action. As the input increases the output will
decrease. Most commonly used in heating processes.
If Out1 is set for ##tP, #PUL, or ProP,then S1OL and S1OH (following)
appear. If Out1 is set for ONOF, then skip to S1rE.
S1OLSet Point Output Low Limit: Select 0 to 100% but not greater than
S1OH. This item limits the lowest output value. This is useful for
adding a bias to the process when needed. Factory set to 0 for
output codes 1,2, and 3. Factory set to 20 for output code 5 (20%
output equals 4 mA output).
949-1277-3Page 28December, 1998
Page 29
S1OHSet Point 1 Output High Limit: Select 0 to 100% but not less than
S1OL for output codes 1, 2, or 3. Select 0 to 102% but not less than
S1OL for output code 5. This item allows setting the maximum
output limit. This is useful with processes that are over powered.
Adjustment to 102% allows setting current output to force a full on
condition for output devices which do not have bias adjustments.
Factory set to 100 for all output codes.
If Out1 is set for ##tP, #PUL, or ProP,then skip to S1LP below.
S1rESet Point 1 Reset. Select OnOF or Hold.
OnOFControl will automatically reset when process passes
back through SP1d.
HoLdManual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5
seconds.
S1PiSet Point 1 Power Interrupt. Select On or OFF.
OnAlarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFFAlarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S1iHSet Point 1 Inhibit: Select On or OFF.
OnAlarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFFAlarm Inhibit is OFF.
S1LPSet Point Lamp: Select O on or OoFF.
O onLamp ON when Output is ON.
OoFFLamp OFF when Output is ON.
If your control is not equipped with Set Point 2, then proceed to the
alarm section (next page).
S2tSet Point 2 type: Select Abs or dE.
AbSAbsolute SP2 . SP2 is independent of SP1, and may be set
anywhere between the limits of SPL and SPH.
dEDeviation SP2. SP2 is set as a deviation from SP1, and
allows SP2 to retain its relationship with SP1 when SP1 is
changed (tracking SP2).
S2StSet Point 2 State: Select dir or rE.
dirDirect Action. As the input increases the output will
December, 1998Page 29949-1277-3
Page 30
increase. Most commonly used in cooling processes.
rEReverse Action. As the input increases the output will
decrease. Most commonly used in heating processes.
If Out2 is set for ##tP, #PUL, or ProP,then S2OL and S2OH (following)
appear. If Out2 is set for ONOF, then skip to S2rE.
S2OLSet Point Output Low Limit: Select 0 to 100% but not greater than
S2OH. This item limits the lowest output value. This is useful for
adding a bias to the process when needed. Factory set to 0 for
output codes 1,2, and 3. Factory set to 20 for output code 5 (20%
output equals 4 mA output).
S2OHSet Point 1 Output High Limit: Select 0 to 100% but not less than
S2OL for output codes 1, 2, or 3. Select 0 to 102% but not less than
S2OL for output code 5. This item allows setting the maximum
output limit. This is useful with processes that are over powered.
Adjustment to 102% allows setting current output to force a full on
condition for output devices which do not have bias adjustments.
Factory set to 100 for all output codes.
S2rESet Point 2 Reset. Select OnOF or Hold.
OnOFControl will automatically reset when process passes
back through SP2d.
HoLdManual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5
seconds.
S2PiSet Point 2 Power Interrupt. Select On or OFF.
OnAlarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFFAlarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S2iHSet Point 2 Inhibit: Select On or OFF.
OnAlarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFFAlarm Inhibit is OFF.
S2LPSet Point 2 Lamp: Select O on or OoFF.
O onLamp ON when Output is ON.
OoFFLamp OFF when Output is ON.
949-1277-3Page 30December, 1998
Page 31
ALARM TYPE AND ACTION (if present)
Caution: In any critical application where failure could
cause expensive product loss or endanger personal
safety, a redundant limit controller is required.
When setting an alarm value for an absolute alarm (A#t = AbS), simply set
the value at which the alarm is to occur.
When setting the alarm value for a deviation alarm (A#t = dE), set the
difference in value from the Set Point (SP) desired. For example if a low
alarm is required to be 5 degrees below the SP, then set A#Lo to -5. If a high
alarm is required 20 degrees above the SP, then set A#Hi to +20. If SP is
changed, the alarm will continue to hold the same relationship as originally
set.
The following diagram (below) shows the action and reset functions for both
absolute and deviation alarms.
When Alarm Power Interrupt, A#Pi, is programmed ON and Alarm Reset,
A#rE, is programmed for Hold, the alarm will automatically reset upon a
power failure and subsequent restoration if no alarm condition is present.
If Alarm Inhibit, A#iH, is selected ON, an alarm condition is suspended upon
power up until the process value passes through the alarm set point once.
Alarm inhibit can be restored as if a power up took place by pressing both
the INDEX and ENTER keys for 5 seconds.
December, 1998Page 31949-1277-3
Page 32
Warning: If inhibit is on and a power failure occurs
during a high alarm, restoration of power will not cause
the alarm to occur if the process value does not first
drop below the high alarm setting. Do not use the Alarm
Inhibit feature if a hazard is created by this action. Be
sure to test all combinations of high and low alarm
inhibit actions before placing control into operation.
The following menu items apply only to the alarm.
AL1Alarm 1 function: Select OFF, Lo, Hi, HiLo, or Evnt.
OFFAlarm 1 is disabled. No Alarm 1 menu items appear in
the Secondary or Secure menus.
LoLow Alarm Only. A1Lo appears in the Secondary Menu.
HiHigh Alarm Only. A1Hi appears in the Secondary Menu.
HiLoHigh and Low Alarms. Both A1Lo and A1Hi appear in
the Secondary Menu, and share the same Alarm 1 Relay
output.
EvntAlarm 1 is controlled by the Ramp/Soak program func-
tion. See pages 10-13, and 20 (#A1) for further information.
If AL1 is set to OFF, go to AL2 below. If AL1 is set to Evnt, go to A1St below.
A1tAlarm 1 Type: Select AbS or dE
AbSAbsolute Alarm that may be set anywhere within the
values of SCAL and SCAH and is independent of SP1.
dEDeviation Alarm that may be set as an offset from SP1.
As SP1 is changed the Alarm Point will track with SP1.
A deviation alarm will also track any active ramp or soak
set point.
A1rEAlarm 1 Reset: Select OnOF or Hold.
OnOFAutomatic Reset.
HoldManual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5
seconds.
A1PiAlarm 1 Power Interrupt: Select On or OFF.
OnAlarm Power Interrupt is On.
OFFAlarm Power Interrupt is OFF.
A1iHAlarm 1 Inhibit: Select On or OFF.
OnAlarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFFAlarm Inhibit is OFF.
949-1277-3Page 32December, 1998
A1StAlarm 1 Output State: Select CLOS or OPEn.
Page 33
CLOSCloses Contacts at Alarm Set Point.
OPEnOpens Contacts at Alarm Set Point.
A1LPAlarm 1 Lamp: Select O on or OoFF.
O onAlarm Lamp is ON when alarm contact is closed.
OoFFAlarm Lamp is OFF when alarm contact is closed.
A1LbAlarm 1 Loop Break. Select On or OFF.
OnLoop Break Condition will cause an Alarm Condition.
OFFLoop Break will not affect the Alarm Condition.
AL2Alarm 2 function: Select OFF, Lo, Hi, HiLo, or Evnt.
OFFAlarm 2 is disabled. No Alarm 2 menu items appear in
the Secondary or Secure menus.
LoLow Alarm Only. A2Lo appears in the Secondary Menu.
HiHigh Alarm Only. A2Hi appears in the Secondary Menu.
HiLoHigh and Low Alarms. Both A2Lo and A2Hi appear in
the Secondary Menu, and share the same Alarm 2 Relay
output.
EvntAlarm 2 is controlled by the Ramp/Soak program func-
tion. See pages 10-13, and 20 (#A2) for further information.
If AL2 is set to OFF, the Secure Menu ends. If AL2 is set to Evnt, go to A2St
below.
A2tAlarm 2 Type: Select AbS or dE
AbSAbsolute Alarm that may be set anywhere within the
values of SCAL and SCAH and is independent of SP1.
dEDeviation Alarm that may be set as an offset from SP1.
As SP1 is changed the Alarm Point will track with SP1.
A deviation alarm will also track any active ramp or soak
set point.
A2rEAlarm 2 Reset: Select OnOF or Hold.
OnOFAutomatic Reset.
HoldManual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5
seconds.
A2PiAlarm 2 Power Interrupt: Select On or OFF.
OnAlarm Power Interrupt is On.
OFFAlarm Power Interrupt is OFF.
December, 1998Page 33949-1277-3
Page 34
A2iHAlarm 2 Inhibit: Select On or OFF.
OnAlarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFFAlarm Inhibit is OFF.
A2StAlarm 2 Output State: Select CLOS or OPEn.
CLOSCloses Contacts at Alarm Set Point.
OPEnOpens Contacts at Alarm Set Point.
A2LPAlarm 2 Lamp: Select O on or OoFF.
O onAlarm Lamp is ON when alarm contact is closed.
OoFFAlarm Lamp is OFF when alarm contact is closed.
A2LbAlarm 2 Loop Break. Select On or OFF.
OnLoop Break Condition will cause an Alarm Condition.
OFFLoop Break will not affect the Alarm Condition.
SPSA(Option 948, 4-Stage Set Point) Switch Action: Select rE or Int.
rESet Point Stage selected by external contact closures.
IntSet Point Stage selected by internal menu selection. See
SP menu item in Secondary Menu.
Addr(Option 992, 993, Serial Communications) Control Address: Set
from 1 to 3FF. This number (hexadecimal, base 16) must match the
address number used by the host computer.
bAUd(Option 992, 993, Serial Communications) Communication Baud
Rate: Select 300, 1200, 2400, 4800, 9600, or 19200. This number
must match the baud rate used by the host computer.
nAt(Option 992, 993, Serial Communications) No Activity Timer: Set
from OFF or 1 to 99 minutes.1 - 99Maximum time between host computer accesses. If timer
counts to 0, CHEC/LorE will be displayed.
OFFNo Activity Timer function is disabled.
rSCL(Option 924, 926, 928, Analog Remote Set Point) Remote Scale
Low: Select 100 to 9999 counts below rSCH. The total span between
rSCL and rSCH must be within 11998 counts. Maximum setting
range is -1999 to +9999 counts.
rSCH(Option 924, 926, 928, Analog Remote Set Point) Remote Scale
High: Select 100 to 9999 counts above rSCL. The total span between
rSCL and rSCH must be within 11998 counts. Maximum setting
range is -1999 to +9999 counts.
949-1277-3Page 34December, 1998
Page 35
DISPLAY
DIAGNOSTIC ERROR MESSAGES
MEANING
SP OUTPUTS
ACTION REQUIRED
UFL
or
OFL
bAd
InP
OPEn
InP
LOOP
bAd
SEnC
bAd
Underflow or Overflow: Process value
has exceeded input
range ends.
UFL or OFL will sequence to display
one of these messages if the InPt is
set for a time value.
For RTD inputs RTD
is open or shorted.
For THERMOCOUPLE inputs thermocouple is open.
The sensor may be
defective, heater
fuse open, heater
open, or the final
power output device
is bad.
Sensor Rate of
Change exceeded
the programmed limits set for SEnC.
Set point
outputs active
Alarms active
Set point
outputs
inactive
Alarms active
Set point
outputs
inactive.
Alarms active.
Set point
outputs
inactive.
Alarms Active
Input signals may normally go
above or below range ends. If
not, check input and correct.
To reset use the INDEX &
ENTER keys. When InPt (in-
put fault timer) has been set
for a time, the outputs will be
turned off after the set time.
Setting the time to OFF causes the outputs to remain active, however UFL or OFL will
still be displayed.
Correct or replace sensor. To
reset use the INDEX & EN-TER keys.
Correct or replace sensor, or
any element in the control loop
that may have failed. Correct
the problem, and reset the
control by pressing the INDEX
and ENTER keys, or index to
LPbr and press ENTER.
Check for the cause of the
error. The value setting may
be too slow for the process, or
the sensor is intermittent.
Correct the problem and press
INDEX and ENTER to reset.
CHEC
CAL
Check calibration appears as an alternating message if the
instrument calibration nears tolerance
edges.
Check calibration appears as a flashing
message if the instrument calibration exceeds specification.
Set point
outputs active
Alarms active
Set point
outputs
inactive
Alarms active
Remove the instrument for
service and / or recalibration.
To reset use the INDEX &
ENTER keys.
Remove the instrument for
service and / or recalibration.
To reset use the INDEX &
ENTER keys.
December, 1998Page 35949-1277-3
Page 36
DISPLAY
DIAGNOSTIC ERROR MESSAGES
MEANING
SP OUTPUTS
ACTION REQUIRED
No
display
lighted
FAIL
tESt
CHEC
SP1,
CHEC
SP2,
CHEC
1SP, ...,
CHEC
16SP,
Display is blank. Instrument is not getting power, or the
supply voltage is too
low.
Fail test appears
upon power up if the
internal diagnostics
detect a failure. This
message may occur during operation
if a failure is detected. Displays flash.
This message will
appear upon power
up if SP1, SP2,
#SP1, or ##SP is
set outside of the
SPL or SPH values.
Set point
outputs inactive
Alarms inactive
Set point
outputs inactive
Alarms inactive
Set point
outputs inactive
Alarms active
Check that the power supply is
on, or that the external fuses
are good.
The display alternate between
FAIL tESt and one of the following messages: FACt dFLt:
Memory may be corrupted.
Press the ENTER key and the
DOWN ARROW key to start
the factory default procedure.
Recheck controller programming. rEt FACt: Unrecoverable error, return to factory for
service.
Correct the SP1, etc. or adjust
the SPL or SPH values by
programming new values.
CHEC
SPL
or
CHEC
SPH
CHEC
rSpt
CHEC
LorE
This message appears at power up if
SPL or SPH values
are programmed
outside the input
range ends.
This message appears if the analog
remote set point signal is out of range.
This message appears if the Serial
Communications
has timed out.
Set point
outputs inactive
Alarms inactive
Set point
outputs active
Alarms inactive
Set point
outputs active
Alarms inactive
Correct the SPL or SPH values by programming new values.
The control will revert to SP1.
Correction of the analog signal allows the control to return
to the remote
Restore the communications
line and switch the LorE to
LOC.
949-1277-3Page 36December, 1998
Page 37
DIAGNOSTIC ERROR MESSAGES
DISPLAY
ArEA
(Alter-
nates
with PV)
ArEA
MEANING
This message appears if the ambient
temperature of the
control approaches
the ends of tolerence.
This message appears if the ambiient temperature of
the control is out of
range or RJC sensor is broken.
SP OUTPUTS
Set point
outputs active
Alarm active
Set point
outputs active
Alarms active
ACTION REQUIRED
Correct the ambient temperature conditions. Ventilate the
area of the cabinet or check
for clogged filters. If RJC broken, return to factory for service.
Correct the ambient temperature conditions. Ventilate the
area of the cabinet or check
for clogged filters. If RJC broken, return to factory for service.
SPECIFICATIONS
Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current
selectable.
Input Impedance:
Thermocouple = 3 megohms minimum.RTD current = 200 µA.
Current = 10 ohms.Voltage = 5000 ohms.
Sensor Break Protection: De-energizes control output to protect system
after customer set time. (See InPt in Secondary Menu.)
Set Point Range: Selectable (See Range Chart Page 39).
Display: Two 4 digit, 7 segment; vertical 7.62mm (0.3") high LEDs;
horizontal 10mm (0.4") high LEDs.
Control Action: Reverse (usually heating), Direct (usually cooling) select-
able.
Proportional Band: 1 to 9999 °F, °C, or counts.
Reset Time (Integral): Off or 0.1 to 99.9 minutes.
Rate Time (Derivative): Off or 0.01 to 99.99 minutes.
Cycle Rate: 1 to 80 seconds.
On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F,
1° C, or 1 count steps.
Alarm On - Off Differential: 1° F, 1° C, or 1 count.
Fuzzy Percent: 0 to 100%.
Fuzzy Rate: Off or 0.01 to 99.99 minutes.
Fuzzy Band: Off or 1 to 4000 °F, °C, or counts.
Accuracy: ±0.25% of span, ±1 least significant digit.
December, 1998Page 37949-1277-3
Page 38
Resolution: 1 degree or 0.1 degree, selectable.
Line Voltage Stability: ±0.05% over the supply voltage range.
Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F)
maximum (100 ppm / °C typical, 200 ppm / °C maximum).
Common Mode Rejection: 140 db minimum at 60 Hz.
Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
Isolation:
Relay and SSR outputs: 1500 VAC to all other inputs and outputs.
SP1 and SP2 Current outputs: 500 VAC to all other inputs and
outputs, but not isolated from each other,
SP1 and SP2 Switched Voltage outputs: 500 VAC to all other inputs
and outputs, but not isolated from each other.
24 VDC Loop Power: 500 VAC to all inputs and outputs.
Process Output: 500 VAC to all other inputs and outputs.
Supply Voltage: 100 to 240 VAC, nominal., +10 -15%, 50 to 400 Hz. single
phase; 132 to 240 VDC, nominal., +10 -20%.
Power Consumption: 5VA maximum.
Operating Temperature: -10 to +55 °C (+14 to 131 °F).
Storage Temperature: -40 to +80 °C (-40 to 176 °F).
Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at
55 °C non-condensing.
Memory Backup: Nonvolatile memory. No batteries required.
Control Output Ratings:
SSR: 2.5 A @ 240 VAC at 25 °C (77°F). Derates to 1.25 A @ 55° C
(130°F).
Relay: SPDT, 10 A @ 240 VAC resistive; 1/4 hp @ 120 VAC, 1/3 hp
@ 240 VAC.
Alarm Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC
inductive; Pilot Duty Rating: 240 VA, 2 A @ 125 VAC or 1 A @ 240
VAC.
Current (isolated): 0 to 20 mA across 600 ohms maximum.
Switched Voltage (isolated): 15 VDC @ 20 mA.
Loop Power Supply (isolated): 24VDC @ 50mA, regulated.
Panel Cutout: 92 mm x 45 mm (3.625" x 1.775").
Depth Behind Mounting Surface: 103 mm (4.0").
Weight: 369 g (13 oz).
Agency Approvals: CE, UL E87325
Front Panel Rating: Type 4X, (IP66).
949-1277-3Page 38December, 1998
Page 39
Input Ranges (Field Selectable)
Thermocouple T ypes
Input
Type
Range
1°F
1°C
Input
Type
Range
1°F
1°C
Input
Type
Range
1°F
1°C
Type J or L*
-100 to +1600
-73 to +871
Type R
0 to 3200
-17 to +1760
Type N*
-100 to +2372
-73 to +1300
Type K*
-200 to +2500
-129 to +1371
Type S
0 to 3200
-17 to +1760
* These Input Types can be set for 0.1° display.
If temperature goes above 999.9° or less than
-199.9° the display will return to whole degree
resolution.
Type T*
-350 to +750
-212 to +398
Type B
-100 to +2372
-73 to +1300
Type E*
-100 to +1800
-73 to +982
Type C
-100 to +2372
-73 to +1300
RTD Types
Input
Type
Range
1°F
1°C
100 Ohm
Platinum
0.00385 DIN
Curve*
-328 to +1607
-200 to +875
100 Ohm
Platinum
0.00392 Nist
Curve*
-328 to +1607
-200 to +875
120 Ohm
Nickel
0.00628 US
Ind. Curve*
-112 to +608
-80 to +320
1000 Ohm
Platinum
0.00385 Nist
Curve*
-328 to +1607
-200 to +875
Process Input Types
The 0 to 20 mADC, 4 to 20 mADC, 0 to 10 VDC, 2 to 10 VDC, and -10 to
+10 mVDC inputs are fully scalable from a minimum of 100 counts span
placed anywhere within the within the range of -1999 to +9999. Decimal
point position is adjustable from the zero place (9999), tenths (999.9),
hundredths (99.99), thousandths (9.999), or ten thousandths (.9999).
December, 1998Page 39949-1277-3
Page 40
DIMENSIONS
LOVE CONTROLS DIVISION
Dwyer Instruments, Incorporated
®
949-1277-3Page 40December, 1998
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
m
m
www.love-controls.com
m
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.