PUSH BUTTON
PT100
TEMPERATURE
TRANSMITTER
Power
Supply
U
-
+
Load
Pt 100
White
Red
Red
Every effort has been taken to ensure the accuracy of this
specification, however we do not accept responsibility for damage,
injury, loss or expense resulting from errors and omissions, and we
reserve the right of amendment without notice
MODEL 659RTD-1
DWYER INSTRUMENTS, INC.
MICHIGAN CITY, IN 46360 USA
1.0 DESCRIPTION
The head mounted 659RTD-1 connects to any standard Pt100 resistance sensor and
converts the linearised temperature to a 4 to 20 mA signal. The transmitter is a two wire
device, and is fully configurable by the user, over a wide temperature range, with the aid
of a simple push button. This new design incorporates additional configuration menus,
allowing the user to push button trim the transmitter output at both zero and span, ideal
for trimming out sensor errors. The transmitters advanced circuitry guaranties high
stability over the wide operating ambient temperature ranges experienced by head
mounted devices.
The 659RTD-1 features an LED which provides visual indication of sensor fault when in
normal operation and is also used to guide the operator through the simple menus during
configuration.
659RTD-1 User Guide
2.0 RECEIVING AND UNPACKING
Please inspect the packaging and instrument thoroughly for any signs of transit damage.
If the instrument has been damaged, please notify your supplier immediately.
3.0 SPECIFICATION @ 20 °C
INPUT
Sensor Type PT100 100 R @ 0°C 2 or 3 Wire
Sensor Range (-200 to +850) ° C (18 to 390) Ω
Sensor Connection Screw terminal
Minimum span (see note 1) 25 °C
Linearisation BS EN 60751(IEC 751) standard / JISC1604
Accuracy (see note 2) ±0.1 ° C±0.05% of Reading
Thermal Drift 0.0025 % / °C
Excitation current < 200 uA
Lead Resistance effect 0.002 ° C/ Ω
Maximum lead Resistance 20 Ω per leg
Note 1 Any span may be selected, full accuracy is only guaranteed
Note 2 Basic measurement accuracy includes the effects of
OUTPUT
Type Two wire 4 to 20 mA sink
Limits Low >3.9 mA ; high 21.5 mA
Accuracy ±(mA out / 2000) or ±5 uA which ever greater
Loop Effect ± 0.2 uA / V measured @ 50 Hz 1 V (peak to peak)
Thermal Drift ± 1 uA / °C typical ; ±1.5 uA Max
Max Load [ (Vsupply – 10)/21 ] KΩ
GENERAL
Update Time 0.5 Seconds
Response Time 1 Second to reach 90% of final value
Start up time From power up typically 5 Seconds
Filter Factor Adaptive
Ambient Temperature (-40 to 85) °C
Connection Screw Terminal
Approvals BS EN 61326 ; 1998 – Electrical equipment for measurement
Factory Default (0 to 100) °C upscale burnout (0.0 °C user trim)
4.0 INSTALLATION AND WIRING
Mounting holes : two holes 5.5 mm diameter, 33 mm centers
Center Hole sensor wire entry : 4 mm
for spans greater than the minimum recommended span.
calibration, linearisation and repeatability
and control ANNEX A ; ANNEX F
Figure 1
4.1 Mechanical
The transmitter has been specifically designed to fit inside a DIN standard probe head
enclosure, which provides adequate protection from moisture, dust, corrosive
atmosphere etc. All cable entries must be sealed using the correct size gland. Likewise
any probe assembly fitted must be sealed.
Care must be taken when locating the transmitter to ensure the working ambient
temperature range of (-40 to 85) °C is not exceeded. The enclosure has a hole allowing
the sensor wire to enter through the transmitter. This is applicable when the sensor is
mounted directly below the transmitter.
4.2 Electrical
Electrical connections to the transmitter are made to the screw terminal provided on the
top face. The sensor wires must be equal length and type for the lead compensation to
work correctly. The screw terminals allow for wires to enter either inner or outer direction.
The transmitter is protected against reverse connection and over voltage. If no sensor
(input) connection is made the transmitter will go into either up or down scale output
current, depending on configuration.
Figure 2 gives connection details, the output is shown connected to a 24 V supply. The
load symbol represent any other device connected in the loop, such as monitoring
equipment , panel indicators and loop isolators. The load value can range from 0 ohms to
the max loop load for given supply, refer to section 3 “Max load” for more information.
The transmitter conforms with EC directive BS EN 61326 : 1998 when correctly installed
in a termination head providing at least IP20 protection and with sensor wires less than 3
metres. Screened or twisted pair wires are recommended for output wires. Always ensure
the 4 to 20 mA loop is grounded at one point, this would normally be at the monitoring
equipment or loop power supply.
In normal operation the program LED acts as over-range LED.
Figure 2
Adjustment
both move
Low High
Fig
4
Adjustment
Low
fixed
High
Moves
Fig
5
5.0 USER CONFIGURATION
Power Supply
(10 to 30) VDC
-
+
Current Meter
(Optional)
-
+
Program
Button
Burnout /
Program LED
Calibrator precision
resistance source
READ COMPLETE SECTION BEFORE ATTEMPTING CONFIGURATION
PARTICULAR CARE SHOULD BE TAKEN REGARDING TIMEOUTS IN MENU 2 & 3
User Configuration
User configuration uses three menus, each menu sets a different parameter:Menu 1 Set range
Menu 2 Set direction of output on sensor burnout
Menu 3 User trim at 4 mA and 20 mA.
The configuration menus are navigated using the push button and program LED, The
push button is located under the hole in the keyhole shaped wiring label. To press the
button use a 3 mm screw driver (flat blade) inserted into the hole. The button has a slight
click action.
Three types of button press are used:-
Single button press = Advance
Double press within 0.5 seconds = Escape or change direction
Press and hold button > two seconds = Enter
When a menu is selected the Program LED will flash in bursts of one to three flashes, the
number of flashes represents the menu number.
Navigating the menus
To access menus, press and hold button > 2 second, then program LED will start
to flash, one flash every burst. This Indicates “menu 1” is selected.
Use single button press to advance selection to “menu 2”, the program LED will
now show two flashes per burst. The Next single presses will advance the
selected menu to menu 3 and the next single press will advance selected menu
back to menu 1. Repeated single presses will cycle the selected menu back
around menus 1 to 3, in the above sequence.
Double press button to escape from menus, and return to normal. Normal
operation can also be selected by turning transmitter power off and on. Note the
transmitter will not time out and automatically escape from menus.
659RTD-1 User Guide
IMPORTANT
Figure 3 Configuration circuit
Using Menus
Menu 1 Range configuration (No Timeout)
Configuration will require the following tools and equipment :
DC Supply (12 to 30) V @ 30 mA
Precision resistance decade box to simulate PT100 sensor. (Do not use
electronic calibrator)
Screw driver flat blade 3mm wide
PT100 resistance tables
Current meter (user trim)
To re-range the temperature scale follow the following instructions: Refer to figure 3, connect resistance box to the input terminals using three wire
connection. Connect output to a DC supply, observe polarity. Turn power on and
allow 1 minute warm up period.
Set calibrator to the equivalent resistance of the Pt100 sensor, at required low
range temperature. If the program LED is on at this stage the input is out of range,
check resistance and connection.
Press and hold button > 2 seconds to enter menus, menu 1 will then be selected,
indicated by one flash every burst.
Whilst menu 1 is selected, press and hold button > 2 seconds to enter menu 1, at
which stage the program LED toggle on and off at a slow rate.
Allow twenty seconds then single press button to store low range setting, the
program LED will now flash at a fast rate.
Set calibrator to the equivalent resistance of the Pt100 sensor, at required high
range temperature and allow twenty seconds.
Press button to store high range setting, the program LED will flicker for one
second before the transmitter returns to normal operation. The transmitter is now
re-ranged.
Menu 2 Burnout Selection (Timeout is 3 Seconds)
Refer to figure 3, Connect output to a DC supply, observe polarity. For this menu
the input can be connected or open circuit. Turn power on.
Press and hold button > 2 seconds to enter menus, menu 1 will then be selected,
indicated by one flash every burst.
Single press button to advance selection to menu 2, indicated by two flashes of
the program LED every burst.
Whilst menu 2 is selected, press and hold button > 2 seconds to enter menu 2, at
which stage the program LED will either toggle on and off at a slow indicating low
scale burnout or fast rate indicating upscale burnout.
To change burnout direction single press button. The Program LED toggle rate will
change to the other setting. Repeated single presses will toggle between up and
down scale.
To store setting allow 3 seconds with no button action, the program will then
timeout, store new setting then return to normal operation.
Menu 3 User trim (Timeout is 20 Seconds)
This menu allows the user to trim the output current at 4 mA and 20 mA points,
(similar function to trim potentiometers) and is very useful for trimming out sensor
errors.
The input of the transmitter must be connected to either a calibrator or a
temperature sensor held at a known temperature. The 4 to 20 mA loop current will
also need to be monitored with a current meter.
Refer to figure 3, connect sensor or resistance box to the input terminals using
three wire connection. Connect output to a DC supply, observe polarity, connect
current meter in series with loop. Turn power on and allow 1 minute warm up
period.
Set calibrator to the equivalent resistance of the Pt100 sensor, at required trim
point. Alternatively ensure sensor temperature is at the required calibration point.
The transmitter will automatically trim the 4 mA end if the output is within the active
band of 3.8 to 6 mA, and trim the 20 mA end if the output is within the active
band of 18 to 21.5 mA . No setting adjustment is performed if the output current is
not within these two bands. Ensure your calibration points are within these bands.
Press and hold button > 2 seconds to enter menus, menu 1 will then be selected,
indicated by one flash every burst.
Single press button to advance selection to menu 2, and single press again to
select menu 3 indicated by three flashes of the program LED every burst.
Whilst menu 3 is selected, press and hold button > 2 seconds to enter menu 3, at
which stage the program LED toggle on and off at either a slow rate indicating
downward trim direction or fast rate indicating upwards trim direction.
To change trim direction double press button. The Program LED toggle rate will
toggle to the opposite direction. Repeated double presses will toggle between up
and down trim direction
To trim output current, single press button to advance current 2 uA in set direction,
or press and hold button to auto advance in set direction release button to stop
advance. Note after approximately 20 seconds of continuous button press, the
auto trim rate will speed up. Monitor the current change on the current meter.
To store new setting allow 20 seconds with no button action, the program will then
timeout, store new setting then return to normal operation.
Aid to User trim
1) Trim the 4 mA end first. The 4 mA trim is an offset adjustment and
2) Trimming the 20 mA end will not affect the 4 mA end. It will stretch or
Reset to factory default settings
If required the unit can be reset to factory default setting, this procedure also removes
any user trim adjustment. Factory default settings are :
Range (0 to 100) °C
Burnout up-scale
User trim All user adjustment cleared
To reset to factory setting, hold the button down whilst the 659RTD-1 is powered up.
will affect both low and high ends, they will trim by the same amount
(Fig 4)
contract the „span‟ between them. (Fig 5)