Dwyer 644 User Manual

Series 644 - Industrial Pressure Transmitter
Specifications - Installation and Operating Instructions
The Series 644 Industrial Pressure Transmitter is a robust transmitter designed
for high accuracy pressure applications. Boasting an accuracy of ±0.05% FS RSS (<±0.25% TEB), the 644 is intended for precise measurements in the critical applications of calibration technology, hydraulic/pneumatic controls, and many more laboratory and industrial settings. The Series 644 offers multiple measurement options with two output choices (VDC or mA) and ten psig pressure ranges (optional 0 to 15 psia). The robust and compact all stainless steel Series 644 is available with either a 1/4˝ male NPT, or 7/16˝-20 male SAE process connections. Each transmitter is provided with an 11 point NIST traceable calibration certificate.
Range
Range
Number
0 to -14.7 psig
00
0 to 15 psig
01
0 to 25 psig
02
0 to 50 psig
03
0 to 100 psig
04
0 to 150 psig
05
0 to 200 psig
06
0 to 300 psig
07
0 to 500 psig
08
0 to 750 psig
09
0 to 1000 psig
10
0 to 15 psia
11
INSTALLATION
1. Environment
The operating temperature limits of the 644 are -40 to 185°F (-40 to 85°C). The compensated temperature range is -4 to 140°F (-20 to 60°C).
Proof Pressure
30 psig 30 psig 50 psig 100 psig 200 psig 300 psig 400 psig 600 psig 800 psig 1200 psig 1500 psig 30 psia
Burst Pressure
3000 psig 3000 psig 3000 psig 8000 psig 10000 psig 10000 psig 10000 psig 10000 psig 10000 psig 10000 psig 10000 psig 3000 psia
4-3/4
[120.42]
Bulletin P-644
3 FT CABLE
CONNECTION (-L)
Ø1-5/16
[Ø33.02]
3-5/16
[83.44]
1 [25.63]
SPECIFICATIONS Service: Compatible gases and liquids. Wetted Materials: 17- 4 PH SS. Accuracy: ±0.05% FS RSS. Total Error Band (Includes all thermal effects): <±0.25% FS over entire
temperature compensated range.
Stability: < 0.15% FS/year. Operating Temperature Limits: -40 to 185°F (-40 to 85°C). Pressure Limits: Proof pressure and burst pressure: See pressure limits table
below.
Compensated Temperature Range: -4 to 140°F (-20 to 60°C). Power Requirements:
9 to 30 VDC for current output; 15 to 30 VDC for voltage output.
Minimum Supply Voltage:
Min. supply voltage (VDC) for current output = 9 + 0.02 x loop resistance Ω (loop resistance Ω = line resistance + receiver resistance).
Output Signal:
0 to 10 VDC (4-wire); 4 to 20 mA (2-wire).
Response Time: < 10 ms (voltage output), < 80 ms (current output). Max Current Consumption:
4 to 20 mA: 22 mA; 0 to 10 VDC: 20 mA.
Electrical Connections: 3 ft cable or 6-pin male bayonet connector. Process Connection: 1/4˝ male NPT or 7/16˝-20 male SAE with O-ring. Enclosure Rating: NEMA 4X (IP65). Mounting Orientation: Vertical. Weight: 9 oz (254 g). Agency Approvals: CE.
BAYONET CONNECTOR
6-PIN (-B)
1/4-NPT (-P)
7/16˝-20 SAE MALE (-S)
2. Pressure Fittings
Available pressure fittings are given in table below:
Pressure Port Code
-P
-S
3. Installation of Pressure Fittings
Your transmitter is designed for most accurate operation when subjected to pressures within the designated pressure range. Refer to the catalog bulletin specifications for proof pressure limits.
For the most sensitive pressure ranges, excessive high torquing of a metal pressure fitting may cause slight zero shift which may be trimmed out using the zero adjustment. Use of a plastic fitting often shows no noticeable zero shift. The torquing effect does not appreciably affect linearity or sensitivity. The wrench flat on the Series 644 must be used when installing the positive pressure fitting.
DWYER INSTRUMENTS, INC.
Fitting Description
1/4˝-18 male NPT 7/16˝- 20 male SAE
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
4. Position: The transmitter is not position sensitive. However, all standard models
are originally calibrated with the unit in a position with the pressure connection downward. Although they can be used at other angles, for best accuracy it is recommended that units be installed in the position calibrated at the factory.
ELECTRICAL INSTALLATION
1. Electrical Connections: The 644 is available with cable version or bayonet
connector options having different connector pin outs shown in table below:
Wiring Codes Electrical Connection
+ EXC
- EXC + Sig Out
- Sig Out
2. Voltage Output Units
The Series 644 voltage units are four-wire type circuit with 0 to 10 VDC analog output.
3. Current Output Units
The Series 644 current units are two-wire loop-powered 4 to 20 mA current output and delivers rated current into any external load of 0 to 800 ohms.
The current flows into the + terminal and returns back to the power supply through the
- terminal (see Diagram 1). The power supply must be a DC voltage source with a voltage range between 9 and 30 measured between the + and - terminals. The unit is calibrated at the factory with a 24 VDC loop supply voltage and a 250 ohm load.
Cable Wire Color
Red Black Green White
Code-B Bayonet Connector Pinout
A D B C
Diagram 1
MAINTENANCE
After final installation of the pressure transmitter and its companion receiver, no routine maintenance is required. A periodic check of system calibration is suggested. The Series 644 transmitter is not field repairable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.