Dwyer 616W User Manual

Bulletin E-43-W
3-1/8
[79.38]
1-1/4
[31.75]
1-3/16
[30.18]
3-3/4
[95.25]
4-1/2
[114.30]
5-1/8
[130.18]
Ø3/16 [4.76]
MOUNTING HOLES
TYP 4 PLACES
1-5/16
[33.32] TYP
2-1/8
[53.98]
3/4 [19.05] TYP
7/16 OR 5/8
[11.13 OR 15.88] TYP
1/8 AND 3/16
[3.18 AND 4.76]
I.D. TUBING
3-1/8
[79.38]
4-17/32
[115.09]
Series 616W Differential Pressure Transmitter
Specifications - Installation and Operating Instructions
Fig. A
The Series 616W Differential Pressure Transmitter senses the
pressure of air and non-combustible, compatible gases and sends a standard 4-20 mA output signal.
All models, including those featuring LCD digital read-out, are factory calibrated to specific ranges, as listed in the chart on the next page.
Positive, negative and differential pressures can be measured within a full span accuracy of ±0.25%. This weatherproof unit is enclosed in a polycarbonate case, rated (IP66/NEMA 4X).
SPECIFICATIONS Service: Air and non-combustible, compatible gases. Wetted Materials: Consult factory. Accuracy: ±0.25% F.S., display accuracy ±0.5%. Stability: ±1% F.S./yr. Temperature Limits: 0 to 140°F (-17.8 to 60°C). Compensated Temperature Limits: 20 to 120°F (-6.67 to 48.9°C). Pressure Limits: See chart. Thermal Effect: ±0.02% F.S./°F (0.0012% F.S./°C). Power Requirements: 10-35 VDC (2-wire). Output Signal: 4 to 20 mA. Zero and Span Adjustments: Potentiometers for zero and span. Loop Resistance: DC; 0-1250 ohms maximum. Current Consumption: DC; 38 mA maximum. Electrical Connections: Screw-type terminal block. Process Connections: Barbed, dual size to fit 1/8˝ and 3/16˝
(3.12 and 4.76 mm) I.D. rubber or vinyl tubing.
Enclosure Rating: NEMA 4X (IP66). Mounting Orientation: Vertical, consult factory for other position
orientations.
Weight: Without LCD 8.8 oz (249 g); with LCD 9.6 oz (272 g). Agency Approvals: CE.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Phone: 219/879-8000 www.dwyer-inst.com
Series 616W Transmitter Models & Ranges
616W
PRESSURE
TRANSMITTER
1
2
3
4
JUMPER WIRE
RECEIVER
mA
POWER SUPPLY 10-35 VDC
Model
616W-00 616W-0 616W-1 616W-2 616W-3 616W-4 616W-5 616W-6 616W-7 616W-8 616W-9 616W-10 616W-11 616W-12 616W-3B 616W-6B 616W-10B 616W-20B 616W-0M 616W-1M 616W-2M 616W-3M 616W-4M 616W-5M
Pressure Range
0-1 in.w.c. 0-2 in.w.c. 0-3 in.w.c. 0-6 in.w.c. 0-10 in.w.c. 0-20 in.w.c. 0-40 in.w.c. 0-100 in.w.c. 0-200 in.w.c. 0-10 psid 0-20 psid 0-30 psid 0-50 psid 0-100 psid
1.5-0-1.5 in.w.c. 3-0-3 in.w.c. 5-0-5 in.w.c. 10-0-10 in.w.c. 0-500 Pa 0-750 Pa 0-1.5 kPa 0-2.5 kPa 0-5 kPa 0-25 kPa
Maximum Pressure
2 psig 2 psig 2 psig 5 psig 5 psig 11 psig 11 psig 29 psig 29 psig 29 psig 58 psig 58 psig 150 psig 150 psig 2 psig 5 psig 5 psig 11 psi
13.8 kPa
13.8 kPa
34.5 kPa
34.5 kPa
75.8 kPa 200 kPa
Digital Display
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Model
616W-00-LCD 616W-0-LCD 616W-1-LCD 616W-2-LCD 616W-3-LCD 616W-4-LCD 616W-5-LCD 616W-6-LCD 616W-7-LCD 616W-8-LCD 616W-9-LCD 616W-10-LCD 616W-11-LCD 616W-12-LCD 616W-3B-LCD 616W-6B-LCD 616W-10B-LCD 616W-20B-LCD 616W-0M-LCD 616W-1M-LCD 616W-2M-LCD 616W-3M-LCD 616W-4M-LCD 616W-5M-LCD
INSTALLATION
1. Location: Select a clean, dry mounting location free from excess
vibration where the temperature will remain between 20 and 120˚F (-6.7 and 49˚C). Distance from the receiver is limited only by total loop resistance. See Electrical Connections below. The tubing supplying pressure to the instrument can be practically any length required, but long lengths will increase response time slightly.
Pressure Range
0-1 in.w.c. 0-2 in.w.c. 0-3 in.w.c. 0-6 in.w.c. 0-10 in.w.c. 0-20 in.w.c. 0-40 in.w.c. 0-100 in.w.c. 0-200 in.w.c. 0-10 psid 0-20 psid 0-30 psid 0-50 psid 0-100 psid
1.5-0-1.5 in.w.c. 3-0-3 in.w.c. 5-0-5 in.w.c. 10-0-10 in.w.c. 0-500 Pa 0-750 Pa 0-1.5 kPa 0-2.5 kPa 0-5 kPa 0-25 kPa
Maximum Pressure
2 psig 2 psig 2 psig 5 psig 5 psig 11 psig 11 psig 29 psig 29 psig 29 psig 58 psig 58 psig 150 psig 150 psig 2 psig 5 psig 5 psig 11 psig
13.8 kPa
13.8 kPa
34.5 kPa
34.5 kPa
75.8 kPa 200 kPa
Digital Display
0-1.00 0-2.00 0-3.00 0-6.00
0-10.00 0-20.0 0-40.0 0-100.0 0-200 0-10.0 0-20.0 0-30.0 0-50.0 0-100.0
-1.50-0-1.50
-3.00-0-3.00
-5.00-0-5.00
-10.00-0-10.00 0-500 0-750 0-1.50 1-2.50 0-5.00 0-25.0
2. Position: A vertical position, with the pressure connection pointing down, is recommended. That is the position in which all standard models are spanned and zeroed at the factory. They can be used at other angles, but final spanning and zeroing must be done while transmitter is in that alternate position.
3. Pressure Connections: Two integral barbed tubing connections are provided. They are dual-sized to fit both 1/8˝ and 3/16˝ (3.2 and 4.8 mm) I.D. tubing. Be sure the pressure rating of the tubing exceeds that of the operating range. On ranges over 20 psi, we recommend use of a suitable hose clamp to assure the integrity of the connection.
ELECTRICAL CONNECTIONS
CAUTION: Do not exceed specified supply voltage ratings. Permanent damage not covered by warranty will result. This unit is not designed for 120 or 240 volts AC line operation.
Electrical connections are made to the terminal block located on the inside of the transmitter. Terminals are marked 1, 2, 3 and 4. See Fig. B. Determine which of the following circuit drawings applies to your application and wire accordingly.
Fig. B
Wire Length - The maximum length of wire connecting transmitter and
receiver is a function of wire size and receiver resistance. Wiring should not contribute more than 10% of the receiver resistance to total loop resistance. For extremely long runs (over 1000 feet), choose receivers with higher resistance to minimize size and cost of connecting leads. Where wiring length is under 100 feet, hook-up wire as small as 22 AWG can be used.
2-Wire Operation - An external power supply delivering 10-35 VDC with minimum current capability of 40 mA DC (per transmitter) must be used to power the control loop. See Fig. C for connection of the power supply, transmitter and receiver. Note the jumper between terminals 3 and 4. The range of appropriate receiver load resistance (RL) for the DC power supply voltage available is expressed by the formula.
RLMax = Vps - 10V
20mA DC
Shielded two wire cable is recommended for control loop wiring. If grounding is required, use the negative side of the control loop after the receiver. Otherwise, in 2-wire operation it is not necessary to observe polarity of control loop connections.
2-Wire Connections
Fig. C