Dwyer 40M User Manual

DISPLAYING ROOM TEMPERATURE
2
-31/64
[
63.22]
1-3/32
[27.94]
3
[
76.20]
1-11/32
[33.99]
2-3/8
[60.33]
3
-3/16
[
80.92]
2-3/16
[55.52]
7
/16
[
10.92]
If the P5 parameter is set to display the temperature set point, the probe temperature can be displayed by pressing the DOWN ARROW key for two seconds until Pb1 is displayed. Next, hit the SET key. To return to the normal display, press SET key.
MANUAL DEFROST ACTIVATION/DEACTIVATION
To manually activate the defrost cycle, press the UP ARROW key for four seconds. This feature is disabled during heating operation.
PARAMETER LOCK OUT ACTIVATION/DEACTIVATION
The key pad lock out can be activated/deactivated by pressing the SET and DOWN ARROW keys simultaneously for two seconds. The display will flash Loc or UnL to signify the change in states.
ALARM BUZZER RESET
The audible alarm can be silenced by pressing any key.
RESTORING FACTORY DEFAULT SETTINGS
Factory settings can be restored by following the below procedure:
• Pressing the UP ARROW and DOWN ARROW keys for four seconds until PA is displayed
• Press the SET key
• Press the UP ARROW or DOWN ARROW to adjust the value to 743
• Press SET key
• Pressing the UP ARROW and DOWN ARROW keys for four seconds until dEF is displayed
• Press SET key
• Press the UP ARROW or DOWN ARROW to adjust the value to 149
• Press SET key
• Cycle the power after the flashing dEF goes away
©Copyright 2013 Dwyer Instruments, Inc. Printed in U.S.A. 5/13 FR# R5-443741-00 Rev. 4
Programming Device with Configuration Key
The Model 40X-K is not battery powered and requires that the device being programmed be powered. If a power source is not available, a 40X-PS power supply must be installed into the port on the edge of the key.
Copying Parameters to Configuration Key
1. Cut off power to the temperature switch
2. Connect the key to the temperature switch
3. Turn on power to the temperature switch or connect the power supply to the key (LED on key will be green and the temperature switch will flash “CIn”)
4. Press and hold the SET button on the temperature switch for 4 seconds (display will flash “St”)
5. Release the SET button on the temperature switch, the press and hold the SET button again for 4 seconds. (“St” on display will stop flashing and the LED on the key will turn red)
6. Do not disconnect the key while the LED is red, as it is copying the parameters
7. After LED on key returns to green, it is okay to disconnect the key. (If using 40X-PS power supply, disconnect the power supply before disconnecting the key)
Copying Parameters to Temperature Switch
1. Cut off power to the temperature switch
2. Connect the key to the temperature switch
3. Turn on power to the temperature switch or connect the power supply to the key (LED on key will be green and the temperature switch will read “CIn”)
4. Press and hold the button on the configuration key
5. After one second release the button on the key. Parameters will be copied from the key to the temperature switch. (LED will turn red)
6. The display on the temperature switch will read “PrG” and the LED will turn green once the temperature switch has been programmed successfully.
7. Do not disconnect the key while the LED is red, as it is copying the parameters
8. After LED on key returns to green, it is ok to disconnect the key. (If using 40X-PS power supply, disconnect the power supply before disconnecting the key)
DISPLAY MESSAGES
Out 1 solidly lit Out 1 flashing
°C °F Loc Pr1
MAINTENANCE, CLEANING AND REPAIR
After final installation of the unit no routine maintenance is required. Clean the surface of the display controller with a soft and damp cloth. Never use abrasive detergents, petrol, alcohol or solvents. A periodic check of the system calibration is recommended. The Series 40T/40M is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
Output 1 is active Either modification of set point or call for load during load protection (C1 or C2) Defrost cycle is active Alarm condition is present Temperature is measured in °C Temperature is measured in °F Key pad is locked Probe 1 error
Series 40T/40M Digital Temperature Switch
Specifications - Installation and Operating Instructions
The Series 40T/40M Digital Temperature Switch accepts a variety of inputs to allow temperature measurements and set points up to 1999°F (1300°C). Observing the current status of the control is made easier with the 3-1/2 digit, multi-color LED display that has alarm, defrost and output symbols. For added versatility, the temperature units can be field selected for °F or °C. For cooling applications, manual defrost mode can be initiated by pushing a single button. A flashing alarm informs users when the current temperature exceeds preset limits. When programming multiple units, a programming key is available to reduce set up time.
INSTALLATION Note: Unit must be mounted away from vibration, impacts, water and corrosive gases.
• Cut hole in panel 71 x 29 mm (2.80 x 1.14 in)
• Apply silicone around the perimeter of the hole to prevent leakage
• Insert unit into hole from the front side of the panel
• Slide the mounting bracket securely against the panel from the rear of the unit
• Wiring diagram is displayed on top of the control
ADJUSTING PARAMETER VALUES
In order to change the parameter values, follow the procedure below:
• Press UP ARROW and DOWN ARROW simultaneously for four seconds until PA is displayed
• Press SET
• Use UP ARROW or DOWN ARROW to adjust value to -19
• Press SET
• Press UP ARROW and DOWN ARROW simultaneously for four seconds until SP is displayed
• Use UP ARROW or DOWN ARROW to cycle through parameters
• Press SET to view value of parameter
• Use UP ARROW or DOWN ARROW to adjust value of parameter
• Press SET to store value
• Press UP ARROW and DOWN ARROW simultaneously for four seconds to exit menu
ulletin T-40T
B
SPECIFICATIONS Range: Current: -1999 to 1999;
Voltage: -1999 to 1999; K T/C: -140 to 1999°F (-100 to 1300°C); J T/C: -140 to 1450°F (-100 to 800°C); RTD: -320 to 1200°F (-200 to 650°C); PTC: -58 to 300°F (-50 to 150°C); NTC: -40 to 230°F (-40 to 110°C);
N. RTD: -110 to 570°F (-80 to 300°C). Input: RTD thermocouple, thermistor current and voltage (depending on model).
Output: 16A @ 250 VAC SPDT relay (max current allowed is 10A). Control Type: On/off. Power Requirements: 12 to 24 VAC/VDC, 115 VAC or 230 VAC
(depending on model).
Accuracy: ±1% F.S. Display: 3-1/2 digit red display. Resolution: 0.1°C. Memory Backup: Non-volatile memory. Temperature Limits: 32 to 131°F (0 to 55°C). Weight: 2.3 oz (65 g). Front Panel Rating: IP 65. Agency Approvals: UL, CE.
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
WIRING
Avoid installing the temperature probe cables in close proximity of any power cables. If the length of the probe cables is longer than 100 meters, a recalibration adjustment may be made using the CA1 parameter.
PARAMETER LIST
Parameter
SP CA1 P0 P1 P2 P3 P4 P5 r0 r1 r2 r3 r5 C1 C2 C3 C4 C5 d0 d3 d4 d5 d6 A1 A2 A3 A4 A5 A6 A7 E9
Description
Set point Ambient probe adjustment Type of input probe Decimal point position Display units Minimum process input value Maximum process input value Value displayed during normal operation Set point differential Minimum set point value Maximum set point value Set point locked Cooling or heating Minimum time between compressor starts Minimum compressor stoppage time Minimum on time of compressor Off time of fault cycle On time of fault cycle Interval between defrost Duration of defrost cycle Defrost on power up Defrost delay upon power up Display during defrost cycle Alarm set point 1 Alarm delay for A1 Alarm 1 type Alarm delay upon set point modification Alarm set point 2 Alarm delay for A2 Alarm 2 type Reserved for future use
Units
Degrees Degrees Option Option Option Counts Counts Option Degrees Degrees Degrees Option Option Minutes Minutes Seconds Minutes Minutes Hours Minutes Option Minutes Option Degrees Minutes Option Minutes Degrees Minutes Option None
Range
r1 to r2
-25 to 25 0 to 13 0 or 1 0 or 1
-999 to 1999
-999 to 1999 0 or 1
0.1 to 99.0
-199.0 to r2 r1 to 1999 0 or 1 0 or 1 0 to 240 0 to 240 0 to 240 0 to 240 0 to 240 0 to 99 0 to 99 0 or 1 0 to 99 0 or 1
-199 to 1999 0 to 240 0 to 4 0 to 240
-199 to 1999 0 to 240 0 to 4 None
Factory Setting
0.0
0.0 0 1 0
-20 80 0
2.0
0.0
350.0 0 1 0 0 0 10 10 8 0 1 0 1
0.0 0 0 0
0.0 0 0 None
PARAMETER DESCRIPTION
SP Sets ambient temperature set point between r1 and r2 CA1 Ambient probe calibration adjustment P0 Type of input probe
40T
0 = J type thermocouple 1 = K type thermocouple 2 = 3 wire Pt100 RTD 3 = 2 wire Pt100 RTD
P1 Position of decimal place P2 Display engineering units
0 = °C 1 = °F
2 = No units P3 Minimum value for process input P4 Maximum value for process input P5 Value shown during normal operation
0 = Probe temperature
1 = Set point r0 Set point differential or hysteresis r1 Minimum value for set point r2 Maximum value for set point r3 Set point lock out
0 = Unlocked
1 = Locked r5 Selection of heating/cooling operation
0 = Cooling
1 = Heating C1 Minimum time between compressor starts C2 Minimum time compressor must remain off before being restarted C3 Minimum time compressor must remain on after being started C4 During probe error, time compressor is off C5 During probe error, time compressor is on d0 Interval of time between defrost cycles (if 0, defrost will never be activated) d3 Duration of defrost cycle d4 Start defrost cycle upon power up
0 = No
1 = Yes d5 Defrost delay time upon power up (d4 must be 1) d6 Temperature shown during defrost
0 = Display probe temperature
1 = Display probe temperature up to (set point + r0) if probe temperature is below (set point + r0) at activation of
defrost cycle. Display probe temperature if the probe temperature is above (set point + r0) at activation of defrost cycle. A1 Alarm 1 temperature set point A2 Alarm 1 not activated unless temperature remains in alarm state for this time A3 Alarm 1 type
0 = Alarm disabled
1 = Absolute low alarm (A1)
2 = Absolute high alarm (A1)
3 = Deviation low alarm (SP - A1)
4 = Deviation high alarm (SP + A1) A4 Temperature alarms not activated for this time after modifications to set point A5 Alarm 2 temperature set point A6 Alarm 2 not activated unless temperature remains in alarm state for this time A7 Alarm 2 type
0 = Alarm disabled
1 = Absolute low alarm (A1)
2 = Absolute high alarm (A1)
3 = Deviation low alarm (SP - A1)
4 = Deviation high alarm (SP + A1) E9 Reserved
40M
0 = PTC 1 = NTC 2 = J Type Thermocouple 3 = K Type Thermocouple 4 = 3 wires Pt 100 5 = 2 wires Pt 100 6 = 3 wires Pt 1000 7 = 2 wires Pt 1000 8 = 4-20 mA 9 = 0-20 mA 10 = 2-10 V 11 = 0-10 V 12 = 3 wires Ni 120 13 = 2 wires Ni 120