Dwyer 1950 User Manual

Series 1950 Explosion-Proof Differential Pressure Switches
Specifications - Installation and Operating Instructions
et Point Adjustment
S
crew
S
/2˝ (12.7)
1
female NPT
Electrical
Conduit onnection
C
CAUTION
For use only with air or compatible gases. Use of the Model 1950 switch with explosive media connected to the Low pressure port (including differential pressure applications in such media) is not rec­ommended. Switch contact arcing can cause an explosion inside the switch housing which, while contained, may render the switch inoper­ative. If switch is being used to sense a single positive pressure rela­tive to atmosphere, run a line from the low pressure port to a non-haz­ardous area free of combustible gases. This may increase response time on -0 and -00 models.
Note: The last number-letter combination in the model number identi­fies the switch’s electrical rating (number) and diaphragm material (let­ter). The 2F combination is standard as described in the physical data above. In case of special models, a number 1 rating is the same as 2; a number 3 or 4 rating is 10A 125, 250, 480 VAC; 1/8 H.P. 125 VAC; 1/4 H.P. 250 VAC; a number 5 or 6 rating is 1A 125 VAC. Letter B indicates a Buna-N diaphragm; N = Neoprene; S = Silicone; and V = Viton®.
Bulletin E-57
UL and CSA Listed, FM Approved For
L. I GR. C, D - CL. II GR. E, F, G - CL. III
C
Series 1950 Switches
Operating ranges and deadbands
pproximate
o order
T
pecify
s
odel Number
M
950-02-2S
1 1950-00-2F 1950-0-2F 1950-1-2F
950-5-2F
1
950-10-2F
1
950-20-2F
1
Model Number
1950P-2-2F 1950P-8-2F 1950P-15-2F 1950P-25-2F 1950P-50-2F
Operating Range:
nches, W.C.
I
.03 to 0.10
0
.07 to 0.15
0
0.15 to 0.5
0.4 to 1.6
1.4 to 5.5
3.0 to 11.0 .0 to 20.0
4
perating
O
ange: PSI
R
0.5 to 2.0
1.5 to 8.0
3.0 to 15.0
4.0 to 25.0
5.0 to 50
1
t Min. Set Point
A
.025
0
0.04
0.10
0.15 .3
0
.4
0
.4
0
Min. Set Point
0.3 psi
1.0 psi .9 psi
0
.7 psi
0
.0 psi
1
SPECIFICATIONS Service: Air and non-combustible, compatible gases. Wetted Materials: Consult factory. Temperature Limits: -40 to 140°F (-40 to 60°C); 0 to 140°F
(-17.8 to 60°C) for 1950P-8, 15, 25, and 50. -30 to 130°F (-34.4 to
54.4°C) for 1950-02.
Pressure Limits:
Continuous: 1950’s - 45˝ w.c. (0.11 bar); 1950P’s - 35 psi (2.41 bar); 1950P-50 only - 70 psi (4.83 bar). Surge: 1950’s - 10 psi (0.69 bar), 1950P’s - 50 psi (3.45 bar), 1950P-50 only - 90 psi (6.21 bar).
Enclosure Rating: IP54, NEMA 3, 7 and 9. Switch Type: Single-pole double-throw (SPDT). Electrical Rating: 15 A @, 125, 250, 480 VAC, 60 Hz. Resistive 1/8
HP @ 125 VAC, 1/4 HP @ 250 VAC, 60 Hz. Electrical Connections: 3 screw type, common, normally open and normally closed.
Process Connections: 1/8˝ female NPT. Mounting Orientation: Diaphragm in vertical position. Consult factory
for other position orientations.
Set Point Adjustment: Screw type on top of housing. Weight: 3.25 Ib (1.5 kg); 1950-02 model, 4.4 lb (2 kg). Agency Approvals: CE, UL, CSA, FM.
RESPONSE TIME: Because of restrictive effect of flame arrestors,
switch response time may be as much as 10-25 seconds where applied pressures are near set point.
A
ead Band
D
At Max. Set Point
.05
0
.05
0
.15
0
0.20
0.4
0.5
pproximate Dead Band
A
0.6
ax. Set Point
M
.3 psi
0
1.0 psi .9 psi
0
.7 psi
0
.5 psi
1
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
3-1/2
[88.9]
3/8
[9.53]
1-7/16
[36.5]
1/8 NPT(F)
PRESSURE
PORT
1-11/16
[42.9]
1/8 NPT(F)
HIGH PRESSURE
PORT
1/2 NPT(F)
ELEC.
CONDUIT
CONNECTION
RANGE ADJUSTMENT
SCREW
17/64 [6.75] DIA MTG
HOLES (2)
4-7/8
[123.8]
5-7/16
[138.1]
VENT DRAIN
PLUG
950 Switch Outline Dimensions
1
950-02: 7-3/4˝ (196.9) dia. x 4-11/32˝
1
110.3) depth. For complete dimensions
(
equest drawing 28-700175-00 from our
r Customer Service Department
INSTALLATION
1. Select a location free from excess vibration and corrosive atmos­pheres where temperatures will be within the limits noted under Specifications on reverse. Switch may be installed outdoors or in areas where the hazard of explosion exists. See reverse for specific types of hazardous service.
2. Mount standard switches with the diaphragm in a vertical plane and with switch lettering and nameplate in an upright position. Some switch­es are position sensitive and may not reset properly unless they are mounted with the diaphragm vertical.
3. Connect switch to source of pressure, vacuum or differential pressure. Metal tubing with 1/4″ O.D. is recommended, but any tubing which will not restrict the air flow can be used. Connect to the two 1/8″ female NPT pressure ports as noted below:
4. To make electrical connections, remove the three hex head screws from the cover and after loosening the fourth captive screw, swing the cover aside. Electrical connections to the standard single pole, double throw snap switch are provided by means of terminals marked “COM” (common), “NO” (norm open), “NC” (norm closed). The normally open contacts close and the normally closed contacts open when pressure increases beyond the set point. Switch loads for standard models should not exceed the maximum specified current rating of 15 amps resistive. Switch capabilities decrease with an increase in ambient temperature, load inductance, or cycling rate. Whenever an application involves one or more of these factors, the user may find it desirable to limit the switched current to 10 amps or less in the interest of prolonging switch life.
A. Differential pressures - connect pipes or tubes from source of greater pressure to high pressure port marked HIGH PRESS, and from source of lower pressure to low pressure port marked LOW PRESS.
B. Pressure only (above atmospheric pressure) - connect tube from source of pressure to high pressure port. The low pressure port is left open to atmosphere.
C. Vacuum only (below atmospheric pressure) - connect tube from source of vacuum to low pressure port. The high pressure port is left open to atmosphere.
ADJUSTMENT: To Change the Set point
1. Remove the plastic cap and turn the slotted Adjust-ment Screw at the top of the housing clockwise to raise the set point pressure and counter­clockwise to lower the set point. After calibration, replace the plastic cap and re-check the set point.
2. The recommended procedure for calibrating or checking calibration is to use a “T” assembly with three rubber tubing leads, all as short as pos­sible and the entire assembly offering minimum flow restriction. Run one lead to the pressure switch, another to a manometer of known accuracy and appropriate range, and apply pressure through the third tube. Make final approach to the set point very slowly. Note that manometer and pressure switch will have different response times due to different inter­nal volumes, lengths of tubing, fluid drainage, etc. Be certain the switch is checked in the position it will assume in use, i.e. with diaphragm in a vertical plane and switch lettering and Dwyer nameplate in an upright position.
3. For highly critical applications check the set point adjustment and if necessary, reset it as noted in step A.
MAINTENANCE
The moving parts of these switches need no maintenance or lubrication. The only adjustment is that of the set point. Care should be taken to keep the switch reasonably clean. Periodically the vent drain plug should be rotated, then returned to its original position. This will dislodge deposits which could accumulate in applications where there is excessive con­densation within the switch. The Series 1950 Explosion-Proof Differential Pressure Switch is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
©Copyright 2012 Dwyer Instruments, Inc. Printed in U.S.A. 1/12 FR# 26-440332-00 Rev. 13