Dwyer 16L User Manual

INSTRUCTIONS FOR THE 16L SERIES
FM
®
MICROPROCESSOR BASED
TEMPERATURE / PROCESS LIMIT CONTROL
LOVE CONTROLS DIVISION
Dwyer Instruments, Incorporated
®
December, 1998 Page 1 of 28 949-1270
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
www.love-controls.com
CONTENTS
MODEL IDENTIFICATION ...................................................................... 2
GETTING STARTED ............................................................................... 3
INSTALLATION .......................................................................................4
WIRING ................................................................................................... 5
Wiring for 4 to 20mA Transmitter inputs ........................................... 6
Wiring for Optional Inputs and Outputs.............................................6
FRONT PANEL KEY FUNCTIONS.........................................................8
NOTATION CONVENTIONS FOR THE MENUS .................................10
THE HOME DISPLAY ........................................................................... 11
OPERATION AND PROGRAMMING OF OPTIONS ............................ 11
MENU SELECTIONS...........................................................................14
PRIMARY MENU ..................................................................................14
SECONDARY MENU ............................................................................ 14
SECURE MENU....................................................................................17
DIAGNOSTIC ERROR MESSAGES ..................................................... 22
SPECIFICATIONS ................................................................................ 24
DIMENSIONS ....................................................................................... 27

MODEL IDENTIFICATION

Model 1 6 L 2 0
OPTIONS
Output 1
1 = SSR 2 = 15 VDC
Options:
934 Analog Retransmission of Process Variable, 4 to 20 mAdc. 936 Analog Retransmission of Process Variable, 0 to 10 Vdc. 948 4-Stage Set Point. 992 RS-485 Serial Communications. 993 RS-232 Serial Communications. 9502 12 - 24 Vdc/Vac 50-400Hz power supply (control operates on low
voltage equipment).
Note: Only Option 9502 may be combined with another option.
© 1998, Love Controls Division, Dwyer Instruments, Incorporated. All rights reserved. No portion may be copied without the express written consent of Love Controls.
949-1270 Page 2 of 28 December, 1998
3 = Relay, NO 4 = Relay, NC 8 = DC SSR
Output 2
0 = None 1 = SSR 2 = 15 VDC
3 = Relay, NO 4 = Relay, NC 8 = DC SSR

GETTING STARTED

1. Install the control as described on page 4.
2. Wire your control following the instructions on page 5. If you are
using a two-wire transmitter as an input, see the drawing and
instructions on page 6. Option wiring instructions are on Page 7.
Option descriptions and specific instructions start on page 16.
3. Most controls do not need many (if any) program changes to work
on your process. For best results when programming changes are
necessary, make all the necessary changes in the Secure Menu
(page 26) before making changes to the Secondary Menu (page 19).
If error messages occur, check the Diagnostic Error Messages on
page 35 for help. Take the example of a Model 16L2010 that comes from the factory
programmed for type J thermocouples. Suppose for this example you wish to change the input to type K and limit the set point range between 0° and 1000° C.
First, enter the Secure menu as instructed on page 5. Press the INDEX key until the display shows Inp and press the DOWN ARROW until the display shows CA. Don't forget to press the ENTER key to retain your setting.
Next, press the INDEX key to display Unit. Press the DOWN ARROW until the display shows C. Press ENTER.
Next, press the INDEX key until SPL is displayed (pass the dPt and InPt selections). Press the UP ARROW until the display shows 0. Press ENTER.
Finally, press INDEX key to display SPH. Press the DOWN ARROW until the display shows 1000. Press ENTER.
The necessary program changes are now complete. After 30 seconds the display will switch back to the temperature reading. If you want to return faster, press the UP ARROW and ENTER keys (at the same time) and then press the DOWN ARROW and INDEX keys ( again at the same time). This will 'back out' of the menu and immediately display the temperature reading.
December, 1998 Page 3 of 28 949-1270

INSTALLATION

Mount the instrument in a location that will not be subject to excessive temperature, shock, or vibration. All models are designed for mounting in an enclosed panel.
Select the position desired for the instrument on the panel. If more than one instrument is required, maintain the minimum of spacing requirements as shown on the drawing below. Closer spacing will structurally weaken the panel, and invalidate the IP66, UL type 4 rating of the panel.
Prepare the panel by cutting and deburring the required opening.
45mm
(1.77in)
45mm
(1.77in)
Cut Out
19mm
(0.75in)
45mm
(1.77in)
Cut Out
45mm
(1.77in)
All Tolerances are -0.00 +0.60mm (-0.000 +0.020)
From the front of the panel, slide the housing through the cut out. The housing gasket should be against the housing flange before installing.
From the rear of the panel slide the mounting collar over the hous­ing. Hold the housing with one
PANEL
10mm (0.25")
MAX.
GASKET
SPRING LOOP
hand and using the other hand, push the collar evenly against the panel until the spring loops are slightly compressed. The ratch­ets will hold the mounting collar and housing in place.
MOUNTING COLLAR (SHOWN IN POSITION) SLIDE COLLAR ONTO THE HOUSING BEFORE WIRING THE REAR TERMINALS
CAUTION: It is not necessary to remove the instrument chassis from the housing for installation. If the instru­ment chassis is removed from the housing, you must follow industry standard practice for control and pro­tection against Electro-Static Discharge (ESD). Failure to exercise good ESD practices may cause damage to the instrument.
949-1270 Page 4 of 28 December, 1998

WIRING

Do not run thermocouple or other class 2 wiring in the same conduit as power leads. Use only the type of thermocouple or RTD probe for which the control has been programmed. Maintain separation between wiring of sensor, auxiliary in or out, and other wiring. See the "Secure Menu" for input selection.
For thermocouple input always use extension leads of the same type designated for your thermocouple.
For supply connections use No. 16 AWG or larger wires rated for at least 75°C. Use copper conductors only. All line voltage output circuits must have a common disconnect and be connected to the same pole of the disconnect.
Input wiring for thermocouple, current, and RTD; limit reset function; and output wiring for 15 VDC is rated CLASS 2.
Control wiring is as shown.
INPUTS
Current
RTD*
Voltage
Thermocouple
+
+
-
-
-
+
F1 3/8 A @250 VAC Medium Lag
Line Input See Rating
Label for details
* For 2-wire RTD use terminals 1 & 3, and
place a jumper wire between terminals 3 & 4.
ALARM RESET
An external normally open contact may be wired across terminals 9 & 10 for remote reset. Multiple units can not share common contacts. Terminals 9 & 10 share a common ground with the input.
December, 1998 Page 5 of 28 949-1270
OUTPUTS
Output A
Output B
+ -
For relay, NO (Order Code 3) or SSR (Order Code 1) outputs, 15 & 16 and 17 & 18 are Normally Open.
For relay, NC (Order Code 4) outputs, 15 & 16 and 17 & 18 are Normally Closed.
+ -
For Pulsed DC (Order Code 2) and DC SSR (Order Code 8) outputs, 15 & 17 are positive and 16 & 18 are negative.

Wiring for 4 to 20mA Transmitter inputs

Wire power and outputs as shown above. Two-wire transmitters wire as shown below.
For three or four wire transmitters follow the wiring instructions provided with your transmitter.
CAUTION: DO NOT WIRE THE 24 VOLT POWER SUPPLY ACROSS THE INPUT OF THE CONTROL. DAMAGE TO
THE CONTROL INPUT CIRCUITRY WILL RESULT.
Power Supply
+
Transmitter
15 to 28 VDC
+
-
-
+
-

Wiring for Optional Inputs and Outputs

Wire power and outputs as shown on page 5 and 6. Wiring for options is shown opposite. All wiring shown below is Class 2. Shielded twisted pair is required for Option 992.
949-1270 Page 6 of 28 December, 1998
CAUTION: DO NOT RUN SIGNAL WIRING IN THE SAME CONDUIT OR CHASE AS THE POWER WIRING. ER­RATIC OPERATION OR DAMAGE TO THE CONTROL CIRCUITRY WILL RESULT.
SWITCH CONTACTS FOR OPTION 948 MUST BE ISOLATED AND CAN NOT SHARE WIRING WITH OTHER CONTROLS.
OPTION 11 12 6 7 8 934, 936 + - na na na 948 na na Signal Ground A B 992 B A na na na 993 Data In Data Out Signal Ground na na
948 Truth Table
AB
7 to 6 8 to 6 SP
OPEN OPEN 1SP1
CLOSED OPEN 2SP1
RS-232 DB-25 WIRING
(VIEWED FROM WIRE SIDE)
DATA IN 11 DATA OUT 12 DATA GROUND 6
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 16 17 18 19 20 21 22 23 24 25
PIN DESCRIPTION 1 SHIELD 2 TRANSMIT 3 RECEIVE 4 RTS 5 CTS
PIN DESCRIPTION 6 DSR 7 GROUND 8 DCD 20 DTR
December, 1998 Page 7 of 28 949-1270
OPEN CLOSED 3SP1
CLOSED CLOSED 4SP1
RS-232 DB-9 WIRING
(VIEWED FROM WIRE SIDE)
DATA OUT 12 DATA IN 11 DATA GROUND 6
PIN DESCRIPTION
1 2 3 4 5
6 7 8 9
1 DCD 2 RECEIVE 3 TRANSMIT 4 DTR 5 GROUND 6 DSR 7 RTS 8 CTS

FRONT PANEL KEY FUNCTIONS

Remote Indicator Limit 1 Lamp Limit 2 Lamp °F Indicator Process Display °C Indicator Set Point Display Limit Reset Key*
* Limit Reset key flashes when limit condition is present.
Keys are illuminated when pressed. Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next menu item. May also be used in conjunction with other keys as noted below.
UP ARROW: Increments a value, changes a menu item, or selects the item to ON. The maximum value obtainable is 9999 regardless of decimal point placement.
DOWN ARROW: Decrements a value, changes a menu item, or selects the item to OFF. The minimum value obtainable is -1999 regardless of decimal point placement.
ENTER: Pressing ENTER stores the value or the item changed. If not pressed, the previously stored value or item will be retained. The display will flash once when ENTER is pressed.
RST
UP ARROW & ENTER: Pressing these keys simultaneously brings up the secondary menu starting at the SP1d menu item. Pressing these keys for 5 seconds will bring up the secure menu.
INDEX & DOWN ARROW: Pressing these keys simultaneously will allow backing up one menu item, or if at the first menu item they will cause the display to return to the primary menu.
949-1270 Page 8 of 28 December, 1998
LIMIT RESET: This key resets the limit when the limit condition has been removed. Press and hold for three seconds to activate.
INDEX & ENTER: Pressing these keys simultaneously and holding them for 5 seconds allows recovery from the various error messages. The following menu items will be reset:
S1iH: Set Point 1 limit inhibit S2iH: Set Point 2 limit inhibit OPEn InP: Input error message CHEC CAL: Check calibration error
Correct the problems associated with the above conditions before using these reset keys. More than one error could be present. Caution is
advised since several items are reset at one time.
While in the Primary or Secondary Menu, if no key is pressed for a period of 30 seconds, the display will return to the HOME position displaying the temperature value. While in the Secure Menu, if no key is pressed for a period of 60 seconds, the display will return to the HOME position displaying the temperature value. Outputs are disabled (turned off) when the Secure
Menu is active. NOTE: To move to the Primary Menu quickly from any other menu, press
the UP ARROW & ENTER keys followed by pressing the INDEX & DOWN ARROW keys.
SECURITY LEVEL SELECTION
Four levels of security are provided. The display shows the current security level. To change security levels change the password value using the UP & DOWN ARROW keys and pressing the ENTER key. Refer to the password table (following) for the correct value to enter for the security level desired. The SECr menu item security level may be viewed or changed at any time regardless of the present security level.
To set the access level to, for example, 2, at the SECr menu item press the UP ARROW key until the upper display show the password, 1101. Press the ENTER key. The display will blink, and return with the level value, 2, in the upper display.
The password values shown in the table cannot be altered, so retain a copy of these pages for future reference. This is the only reference made to password values in this instruction book.
December, 1998 Page 9 of 28 949-1270
PASSWORD TABLE
Security Level
Menu Status Primary Locked
Secondary Locked Secure Locked
Primary Unlocked Secondary Locked Secure Locked
Primary Unlocked Secondary Unlocked Secure Locked
Primary Unlocked Secondary Unlocked Secure Unlocked
Displayed Value
When Viewed
1
2
3
4
Password Value
To Enter
1110
1101
1011
111

NOTATION CONVENTIONS FOR THE MENUS

Because of the number of features available in this control, information is included that may not apply to your specific control. All usable features are included in this book, but may not be used in your process. To increase clarity the following conventions are used:
1. Certain features, Menu Items, and functions shown in this book may or may not appear on your control, depending on other Menu Item selections. At various places in the Menus there are notes identifying Menu Items that "control" or "direct" other menu items. If you are looking for a particular menu item and can't find it, check the menu item that is its "control" for proper setting.
2. The "#" symbol is used in two ways. It is used inside a group of characters to indicate which set point function (SP1 or SP2) is being affected. It is also used before a group of characters of a menu item to indicate that there may be more than one selection or value for that menu item.
3.
Features that apply only to Options will be printed in Italics.
949-1270 Page 10 of 28 December, 1998

THE HOME DISPLAY

The home display is the normal display while the control is operating. The HOME display may be programmed to operate in one of three different ways. This is controlled by the diSP menu item in the Secure Menu.
If diSP is set for Pro, the HOME display will show only the Process Variable (the temperature, pressure, flow, RH, etc., that is being measured) on the top display with the bottom display blank. If diSP is set for SPt, the home display will show only the Set Variable (Set Point 1) on the top display with the bottom display blank. If diSP is set for both, the HOME display will indicate the Process Variable on the top display and the Set Variable on the bottom.
If no errors or functions are active, the HOME display as programmed will be shown.

OPERATION AND PROGRAMMING OF OPTIONS

Option 934, 936, Isolated Analog Retransmission.
The analog retransmission option allows the Process Variable or the Set Variable to be sent as an analog signal to an external device. The signal may be either 0 to 10 VDC (Option 936) or 0 (or 4) to 20 mADC (Option 934). The output may be changed in the field from one to the other by the toggle switch located on the top printed circuit board.
Wire the output as shown on page 7. To set up the analog retransmission, first determine the scale range
that the analog signal will represent. The maximum scale is 9999°F, 5530°C, or 9999 counts. In the Secondary Menu set POL for the scale value that will be represented by the low end of the analog signal (0 Volts or 0 mA). Set POH for the scale value that will be represented by the high end of the analog signal (10 Volts or 20 mA).
If you require a suppressed scale or output, you may use the following equations to determine the proper settings for POL and
POH.
K = (Highest desired scale reading - Lowest desired scale reading) /
(Maximum desired analog signal - Minimum desired analog signal). POH = ((Maximum possible analog output - Maximum desired analog signal) * K) + Highest desired analog reading.
December, 1998 Page 11 of 28 949-1270
POL = Lowest desired scale reading - ((Minimum desired analog output) * K).
Next select whether you want the retransmission signal to follow the Process Variable or the Set Variable. Usually the Process Variable is sent to recorders or other data acquisition devices. Usually the Set Variable is sent to other controls to be used as an analog remote set point. If you want the analog retransmission signal to follow the PV, in the Secondary Menu set POSr to InP. If you want the analog retransmission signal to follow the SV, set POSr to SPt.
Operation is automatic. There are no further programming steps required.
Option 948, 4-Stage Set Point.
The 4-stage set point option allows four different values to be used for SP1. The control will switch to a given stage when an external contact or contacts are made or opened across the appropriate terminals at the rear of the control (when SPSA, Set Point Switch Action, is set for remote, rE), or when the stage is selected from the Secondary Menu, SP (when SPSA is set for Int). When the state of a contact changes (or the stage number is changed in the Secondary Menu), the values in use are stored and the previously stored values for the new stage are used.
Wire the input as shown on page 7. Usually the control is configured for external switching of the stages.
In this case, the operation is usually automatic, selected by the external switches driven by the machine logic. If it is necessary to program the stages in advance, you may select the stage to modify with the SP menu item. When SP is changed while the SPSA is set for rE, the selected stage is displayed for modification, but only used
when the appropriate contact is made.
Option 992, 993, Serial Communication.
The serial communications options allow the control to be written to and read from a remote computer or other similar digital device. Communication is allowed either through a RS-485 (Option 992) port, or a RS-232 (Option 993) port.
949-1270 Page 12 of 28 December, 1998
Wire the communication lines as shown on Page 7. Wiring for the RS-485 is run from control to control in a daisy chain fashion with a termination resistor (120 ohms) across the transmit and receive terminals of the last control in the chain.
Select the control address and communication baud rate with the Addr and bAUd menu items in the Secure Menu. THE BAUD RATE AND ADDRESS MENU ITEMS WILL TAKE EFFECT ON THE NEXT POWER UP OF THE CONTROL. BE SURE TO POWER CYCLE THE CONTROL BEFORE USING THE NEW BAUD RATE AND ADDRESS.
In operation, you have the option of preventing a write command from the host computer. To prevent the host from writing to the control change the LOrE menu item in the Secondary Menu to LOC. To allow the host to write commands to the control set LOrE to rE. (The host does have the ability to change the LOrE state, but it is not automatic.) If your system depends on constant reading or writing to and from the host, you may wish to set the No Activity Timer (nAt) to monitor the addressing of the control. When the LOrE is set to rE and the nAt is set to any value other than Off, the control will expect to be addressed on a regular basis. If the control is not addressed in the time set by the value of nAt, then the control will display the error message CHEC LOrE. To clear the message set LOrE to LOC.
December, 1998 Page 13 of 28 949-1270

MENU SELECTIONS

PRIMARY MENU Press INDEX to advance to the next menu item. Press UP ARROW or DOWN ARROW to change the value in the display. Press ENTER to retain

the value.
#SP1 (Option 948, 4-Stage Set Point) or
SP1 Set Point 1 Adjust, Limit Point 1. SP2 Set Point 2 Adjust (if equipped), Limit Point 2.

SECONDARY MENU

Hold UP ARROW & ENTER. Press INDEX to advance to the next menu item. Press UP ARROW or DOWN ARROW to change the value in the display. Press ENTER to retain the value.
SP1d Set Point On-Off Differential (hysteresis). Select 1 to 9999 (when
S1F=Lo) or -1 to -9999 (when S1F=Hi). Set the value for the
amount of difference between the turn on point (Set Point 1) and the turn off point. See the following chart.
S2F = Hi
S2F = Lo
DEVIATION ALARM
SP2 WHEN S2t = dE
SP2
SP1
SP2
SP1
ABSOLUTE ALARMS
SP2 when S2t = ABS
High Alarm
S#F = Hi
Low Alarm
S#F = Lo
SP1
SP#
SP#
High Alarm
Low Alarm
The following menu items apply only if your control is equipped with a second set point (last digit of model number is not zero). If your control does not have a second set point, jump to the "SP" menu item below.
SP2d Set Point On-Off Differential (hysteresis). Select 1 to 9999 (when
S2F=Lo) or -1 to -9999 (when S2F=Hi). Set the value for the
amount of difference between the turn on point (Set Point 2) and the turn off point. See chart above.
949-1270 Page 14 of 28 December, 1998
SP (Option 948, 4-Stage Set Point) Active Set Point Stage. Select
1SP1, 2SP1, 3SP1, 4SP1. (See Page 17 for more detail.) 1SP1 Set Menu Items to display Stage 1 for view and change
access. If SPSA is set for Int, 1SP1 is made active.
2SP1 Set Menu Items to display Stage 2 for view and change
access. If SPSA is set for Int, 2SP1 is made active.
3SP1 Set Menu Items to display Stage 3 for view and change
access. If SPSA is set for Int, 3SP1 is made active.
4SP1 Set Menu Items to display Stage 4 for view and change
access. If SPSA is set for Int, 4SP1 is made active.
#SP1 (Option 948, 4-Stage Set Point) Adjust Control Point 1 for Stage
selected above.
PEA The Peak feature stores the highest input the control has measured
since the last reset or Power On. At Power On PEA is reset to the present input. To manually reset the value PEA must be in the lower display. Press the ENTER key to reset. PEA will be reset and display the present input value.
UAL The Valley feature stores the lowest input the Instrument has
measured since the last reset or Power On. At Power On UAL is reset to the present input. To manually reset the value UAL must be in the lower display. Press the ENTER key. UAL will be reset and display the present input value.
InPC Input Correction: Select ±500 °F, °C, or counts. This feature
allows the input value to be changed to agree with an external reference or to compensate for sensor error. Note: InPC is reset to zero when the input type is changed, or when decimal position is changed.
FiLt Digital Filter: Select OFF, 1 to 99. In some cases the time constant
of the sensor, or noise could cause the display to jump enough to be unreadable. A setting of 2 is usually sufficient to provide enough filtering for most cases, (2 represents approximately a 1 second time constant). When the 0.1 degree resolution is se­lected this should be increased to 4. If this value is set too high, controllability will suffer.
POL (Option 934, 936, Analog Retransmission Output) Process Out-
put Low: Select -450°F, -260°C, or -1999 counts to any value less than POH.
December, 1998 Page 15 of 28 949-1270
POH (Option 934, 936, Analog Retransmission Output) Process Out-
put High: Select from any value greater than POL to +9999°F, +5530°C, or 9999 counts.
LOrE (Option 992, 993, Serial Communications) Local / Remote Status:
Select LOC or rE. LOC The host computer is advised not to send remote
commands. Any write commands sent to the controls will be rejected.
rE The host computer is allowed to send write commands.If
the control is not addressed within the time set in the nAt (No Activity Timer, see Secure Menu) the CHEC LorE error message will be displayed.
Addr (Option 992, Serial Communications) Control Address: Set from 1
to 3FF. This number (hexadecimal, base 16) must match the address number used by the host computer. Viewed only in this menu. To change this parameter, see Addr in the Secure Menu.
949-1270 Page 16 of 28 December, 1998

SECURE MENU

Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to advance to the next menu item. Press UP ARROW or DOWN ARROW to change the value in the display. Press ENTER to retain the value.
OUTPUTS ARE DISABLED (TURNED OFF) WHILE CONTROL IS IN SECURE MENU.
SECr Security Code: See the Security Level Selection and the Password
Table in this manual, in order to enter the correct password.
InP Input Type: Select one of the following. Refer to the Input wiring
section for the proper wiring.
J-IC Type “J” Thermocouple CA Type “K” Thermocouple E- Type “E” Thermocouple t- Type “T” Thermocouple L- Type “L” Thermocouple n- Type “N” Thermocouple r-13 Type “R” Thermocouple S-10 Type “S” Thermocouple b- Type “B” Thermocouple C- Type “C” Thermocouple P392 100 ohm Platinum (NIST 0.00392 Ω/Ω/°C) n120 120 ohm Nickel P385 100 ohm Platinum (DIN 0.00385 Ω/Ω/°C) 1P38 1000 ohm Platinum (DIN 0.00385 Ω/Ω/°C) Curr DC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA. UoLt DC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts. diFF DC Voltage Input -10 to +10 mV.
---- Reserved
OSUP Zero Suppression: Select On or OFF. Only with Current and Voltage
input types.
OFF The input range will start at 0 (zero) Input. On The input range will start at 4.00 mA or 2.00 V.
Unit F, C or None.
F °F descriptor is On and temperature inputs will be dis-
played in actual degrees Fahrenheit.
C °C descriptor is On and temperature inputs will be dis-
played in actual degrees Celsius.
nonE °F and °C descriptors will be Off. This is only available with
Current and Voltage Inputs.
December, 1998 Page 17 of 28 949-1270
dPt Decimal Point Positioning: Select 0, 0.0, 0.00, 0.000, or .0000.
On temperature type inputs this will only effect the Process Value, SP1, SP2, and InPC. For Current and Voltage Inputs all Menu Items related to the Input will be affected. 0 No decimal Point is selected. This is available for all
Input Types.
0.0 One decimal place is available for Type J, K, E, T, L, RTD’s, Current and Voltage Inputs.
0.00 Two decimal places is only available for Current and Voltage Inputs.
0.000 Three decimal places is only available for Current and Voltage inputs.
.0000 Four decimal places is only available for Current and
Voltage inputs.
diSP Home Display: Select Pro, SPt, or both.
Pro The upper display of the HOME display shows the
current Process Variable. The lower display is blank.
SPt The upper display of the HOME display shows the
current Set Variable. The lower display is blank.
both The upper display of the HOME display shows the
current Process Variable. The lower display shows the current Set Variable.
InPt Input Fault Timer: Select OFF, 0.1 to 540.0 minutes. Whenever an
Input is out of range (UFL or OFL displayed), shorted, or open the timer will start. When the time has elapsed, the controller outputs will be forced into their de-energized states. If OFF is selected, the Input Fault Timer will not be recognized (time = infinite).
SEnC Sensor Rate of Change: Select OFF, 1 to 4000 °F, °C, or counts
per 1 second period. This value is usually set to be slightly greater than the fastest process response expected during a 1 second period, but measured for at least 2 seconds. If the process is faster than this setting, the SEnC bAd error message will appear. The outputs will then be turned off. This function can be used to detect a runaway condition, or speed up detection of an open thermo­couple. Use the INDEX & ENTER keys to reset.
SCAL Scale Low: Select 100 to 9999 counts below SCAH. The total span
between SCAL and SCAH must be within 11998 counts. Maximum setting range is -1999 to +9999 counts. For Current and Voltage inputs, this will set the low range end. Viewable only for Thermo­couple and RTD ranges.
949-1270 Page 18 of 28 December, 1998
SCAH Scale High: Select 100 to 9999 counts above SCAL. The total span
between SCAL and SCAH must be within 11998 counts. Maximum setting range is -1999 to +9999 counts. For Current and Voltage inputs, this will set the high range end. Viewable only for Thermo­couple and RTD ranges.
SPL Set Point Low: Select from the lowest input range value to SPH
value. This will set the minimum SP1 or SP2 value that can be entered. The value for SP1 or SP2 will not stop moving when this value is reached.
SPH Set Point High: Select from the highest input range value to SPL
value. This will set the maximum SP1 or SP2 value that can be entered. The value for SP1 or SP2 will not stop moving when this value is reached.
SP1O Set Point 1 Output Select: Select A or A-b.
A Set Point 1 is routed through Output A, Set Point 2 (if
equipped) is routed through Output B.
A-b Set Point 1 is routed through both Output A and Output
B. Set Point 2 menu items are suppressed. This allows for both NO and NC (Order Code types 3 and 4) outputs to be driven at the same time.
S1FSet Point 1 Function: Select Hi or Lo.
Hi Output is energized above set point. Lo Output is energized below set point.
S1rE Set Point 1 Reset. Select OnOF or Hold.
OnOF Control will automatically reset when process passes
back through SP1d.
HoLd Manual Reset. Reset (acknowledge) by pressing the
LIMIT RESET key for 3 seconds.
S1Pi Set Point 1 Power Interrupt. Select On or OFF.
On Alarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFF Alarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S1iH Set Point 1 Inhibit: Select On or OFF.
On Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF Alarm Inhibit is OFF.
December, 1998 Page 19 of 28 949-1270
S1St Set Point 1 State: Select Eng or dEng.
Eng Output Energized. The output device (per Order Code)
will be energized at set point. (Normally Open contacts will close, Normally Closed contacts will open.)
dEng Output De-energized. The output device (per Order
Code) will be de-energized at set point. (Normally Open contacts will open, Normally Closed contacts will close.)
S1LP Set Point Lamp: Select O on or OoFF.
O on Lamp ON when Output is ON (energized). OoFF Lamp OFF when Output is ON (energized).
If your instrument is not equipped with Set Point 2, then proceed to the option section (next page). If the instrument has no Set Point 2 and no options, then the menu ends.
S2t Set Point 2 type: Select Abs or dE.
AbS Absolute SP2. SP2 is independent of SP1, and may be set
anywhere between the limits of SPL and SPH.
dE Deviation SP2. SP2 is set as a deviation from SP1, and
allows SP2 to retain its relationship with SP1 when SP1 is changed (tracking SP2).
S2F Set Point 2 Function: Select Hi of Lo.
Hi Output is energized above set point. Lo Output is energized below set point.
S2rE Set Point 2 Reset. Select OnOF or Hold.
OnOF Control will automatically reset when process passes
back through SP2d.
HoLd Manual Reset. Reset (acknowledge) by pressing the
LIMIT RESET key for 3 seconds.
S2Pi Set Point 2 Power Interrupt. Select On or OFF.
On Alarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFF Alarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S2iH Set Point 2 Inhibit: Select On or OFF.
On Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF Alarm Inhibit is OFF.
949-1270 Page 20 of 28 December, 1998
S2St Set Point 2 State: Select Eng or dEng.
Eng Output Energized. The output device (per Order Code)
will be energized at set point. (Normally Open contacts will close, Normally Closed contacts will open.)
dEng Output De-energized. The output device (per Order
Code) will be de-energized at set point. (Normally Open contacts will open, Normally Closed contacts will close.)
S2LP Set Point 2 Lamp: Select O on or OoFF.
O on Lamp ON when Output is ON (energized). OoFF Lamp OFF when Output is ON (energized).
SPSA (Option 948, 4-Stage Set Point) Switch Action: Select rE or Int.
rE Set Point Stage selected by external contact closures. Int Set Point Stage selected by internal menu selection. See
SP menu item in Secondary Menu.
Addr (Option 992, 993, Serial Communications) Control Address: Set
from 1 to 3FF. This number (hexadecimal, base 16) must match the address number used by the host computer.
bAUd (Option 992, 993, Serial Communications) Communication Baud
Rate: Select 300, 1200, 2400, 4800, 9600, or 19200. This number must match the baud rate used by the host computer.
nAt (Option 992, 993, Serial Communications) No Activity Timer: Set
from OFF or 1 to 99 minutes. 1 - 99 Maximum time between host computer accesses. If timer
counts to 0, CHEC/LorE will be displayed.
OFF No Activity Timer function is disabled.
December, 1998 Page 21 of 28 949-1270
DISPLAY

DIAGNOSTIC ERROR MESSAGES

MEANING
SP OUTPUTS
ACTION REQUIRED
No display lighted
FAIL
tESt
CHEC
SP1,
CHEC
SP2
CHEC
SPL
or
CHEC
SPH
Display is blank. In­strument is not get­ting power, or the supply voltage is too low.
Fail test appears upon power up if the internal diagnostics detect a failure. This message may oc­cur during operation if a failure is detect­ed. Displays flash.
This message will appear upon power up if SP1, SP2, or #SP1 is set outside of the SPL or SPH values.
This message ap­pears at power up if SPL or SPH values are programmed outside the input range ends.
Set point
outputs inactive
Alarm inactive
Set point
outputs inactive
Alarm inactive
Set point
outputs inactive
Alarm active
Set point
outputs inactive
Alarm inactive
Check that the power supply is on, or that the external fuses are good.
The display alternate between FAIL tESt and one of the fol­lowing messages: FACt dFLt: Memory may be corrupted. Press the ENTER key and the DOWN ARROW key to start the factory default procedure. Recheck controller program­ming. rEt FACt: Unrecover­able error, return to factory for service.
Correct the SP1, etc. or adjust the SPL or SPH values by programming new values.
Correct the SPL or SPH val­ues by programming new val­ues.
CHEC
LorE
ArEA
(Alter-
nates
with PV)
ArEA
This message ap­pears if the Serial Communications has timed out.
This message appears when the ambient tem­perature of the control approaches unaccept­able ambients.
This message appears if the ambiient temper­ature of the control is out of range or RJC sensor is broken.
Set point outputs active Alarm inactive
Set point outputs active
Alarms active
Set point outputs active
Alarms active
Restore the communications line and switch the LorE to LOC.
Correct the ambient temperature conditions. Ventilate the area of the cabinet or check for clogged filters. If RJC broken, return to factory for service.
Correct the ambient temperature conditions. Ventilate the area of the cabinet or check for clogged filters. If RJC broken, return to factory for service.
949-1270 Page 22 of 28 December, 1998
DISPLAY
DIAGNOSTIC ERROR MESSAGES
MEANING
SP OUTPUTS
ACTION REQUIRED
UFL
or
OFL
bAd
InP
OPEn
InP
SEnC
bAd
CHEC
CAL
Underflow or Over­flow: Process value has exceeded input range ends.
UFL or OFL will se­quence to display one of these mes­sages if the InPt is set for a time value.
For RTD inputs RTD is open or shorted.
For THERMOCOU­PLE inputs thermo­couple is open.
Sensor Rate of Change exceeded the programmed lim­its set for SEnC.
Check calibration ap­pears as an alternat­ing message if the instrument calibra­tion nears tolerance edges.
Set point
outputs active
Alarm active
Set point
outputs inactive
Alarm active
Set point
outputs
inactive.
Alarm Active
Set point
outputs active
Alarm active
Input signals may normally go above or below range ends. If not, check input and correct.
To reset use the INDEX & ENTER keys. When InPt (in- put fault timer) has been set for a time, the outputs will be turned off after the set time. Setting the time to OFF caus­es the outputs to remain ac­tive, however UFL or OFL will still be displayed. Correct or replace sensor. To reset use the INDEX & EN- TER keys.
Check for the cause of the error. The value setting may be too slow for the process, or the sensor is intermittent. Correct the problem and press INDEX and ENTER to reset.
Remove the instrument for service and / or recalibration. To reset use the INDEX & ENTER keys.
Check calibration ap­pears as a flashing message if the instru­ment calibration ex­ceeds specification.
Set point
outputs inactive
Alarm active
Remove the instrument for service and / or recalibration. To reset use the INDEX & ENTER keys.
December, 1998 Page 23 of 28 949-1270

SPECIFICATIONS

Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current
selectable.
Input Impedance:
Thermocouple = 3 megohms minimum. RTD current = 200 µA. Current = 10 ohms. Voltage = 5000 ohms.
Sensor Break Protection: De-energizes output(s) to protect system after
customer set time. (See InPt in Secondary Menu.)
Set Point Range: Selectable (See Range Chart Page 26). Display: Two 4 digit, 7 segment 0.3" high LEDs. Output Action: Fully programmable to allow output(s) to energize or de-
energize above or below set point(s).
On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F,
1° C, or 1 count steps.
Accuracy: ±0.25% of span, ±1 least significant digit. Resolution: 1 degree or 0.1 degree, selectable. Line Voltage Stability: ±0.05% over the supply voltage range. Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F)
maximum (100 ppm / °C typical, 200 ppm / °C maximum).
Common Mode Rejection: 140 db minimum at 60 Hz. Normal Mode Rejection: 65 db typical, 60 db at 60 Hz. Isolation:
Relay and SSR outputs: 1500 Vac to all other inputs and outputs. SP1 and SP2 Switched Voltage outputs: 500 Vac to all other inputs
and outputs, but not isolated from each other.
Process Output (934, 936): 500 VAC to all other inputs and outputs.
Supply Voltage: 100 to 240 Vac, nominal., +10 -15%, 50 to 400 Hz. single
phase; 132 to 240 Vdc, nominal., +10 -20%.
Supply Voltage (Option 9502): 12 to 24 Vdc, Vac 40-400 Hz, ±20%. Power Consumption: 5VA maximum. Operating Temperature: -10 to +55 °C (+14 to 131 °F). Storage Temperature: -40 to +80 °C (-40 to 176 °F). Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at
55 °C non-condensing.
Memory Backup: Nonvolatile memory. No batteries required.
949-1270 Page 24 of 28 December, 1998
Output Ratings:
AC SSR: 2.0 A @ 240 Vac at 25 °C (77°F). Derates to 1.0 A @ 55° C
(130°F).
DC SSR: 1.75 A @ 32 Vdc maximum. Relay: SPST, 3 A @ 240 Vac resistive; 1.5A @240 Vac inductive;
Pilot duty rating 240 VA, 2 A @ 120 Vac or 1 A 240 Vac.
Switched Voltage (isolated): 15 Vdc @ 20 mA. Panel Cutout: 45 mm x 45 mm (1.775" x 1.775"). Depth Behind Mounting Surface: 121.6 mm (4.79"), maximum. Weight: 220 g (8 oz). Agency Approvals: FM, CE. Front Panel Rating: IP66, (NEMA4X).
December, 1998 Page 25 of 28 949-1270
Input Ranges (Field Selectable)
Thermocouple T ypes
Input Type
Range
1°F
1°C
Input Type
Range
1°F 1°C
Input Type
Range
1°F 1°C
Type J or L*
-100 to +1600
-73 to +871
Type R
0 to 3200
-17 to +1760
Type N*
-100 to +2372
-73 to +1300
Type K*
-200 to +2500
-129 to +1371
Type S
0 to 3200
-17 to +1760
* These Input Types can be set for 0.1° display. If temperature goes above 999.9° or less than
-199.9° the display will return to whole degree resolution.
Type T*
-350 to +750
-212 to +398
Type B
+75 to 3308 +24 to 1820
Type E*
-100 to +1800
-73 to +982
Type C
0 to 4208
-17 to 2320
RTD Types
Input Type
Range
1°F 1°C
100 Ohm
Platinum
0.00385 DIN Curve*
-328 to +1607
-200 to +875
100 Ohm
Platinum
0.00392 Nist Curve*
-328 to +1607
-200 to +875
120 Ohm
Nickel
0.00628 US Ind. Curve*
-112 to +608
-80 to +320
1000 Ohm
Platinum
0.00385 Nist Curve*
-328 to +1607
-200 to +875
Process Input Types
The 0 to 20 mAdc, 4 to 20 mAdc, 0 to 10 Vdc, 2 to 10 Vdc, and -10 to +10 mVdc inputs are fully scalable from a minimum of 100 counts span placed anywhere within the within the range of -1999 to +9999. Decimal point position is adjustable from the zero place (9999), tenths (999.9), hun­dredths (99.99), thousandths (9.999), or ten thousandths (.9999).
949-1270 Page 26 of 28 December, 1998
December, 1998 Page 27 of 28 949-1270

DIMENSIONS

L
LM
LM
All dimensions in millimeters (inches). Panel cut out is 45 +0.6 (1.77 +0.02) square.
RESET
FM
®
LOVE CONTROLS DIVISION
Dwyer Instruments, Incorporated
®
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
949-1270 Page 28 of 28 December, 1998
www.love-controls.com
Loading...