934 Analog Retransmission of Process Variable, 4 to 20 mAdc.
936 Analog Retransmission of Process Variable, 0 to 10 Vdc.
948 4-Stage Set Point.
992 RS-485 Serial Communications.
993 RS-232 Serial Communications.
9502 12 - 24 Vdc/Vac 50-400Hz power supply (control operates on low
voltage equipment).
Note:Only Option 9502 may be combined with another option.
2. Wire your control following the instructions on page 5. If you are
using a two-wire transmitter as an input, see the drawing and
instructions on page 6. Option wiring instructions are on Page 7.
Option descriptions and specific instructions start on page 16.
3. Most controls do not need many (if any) program changes to work
on your process. For best results when programming changes are
necessary, make all the necessary changes in the Secure Menu
(page 26) before making changes to the Secondary Menu (page 19).
If error messages occur, check the Diagnostic Error Messages on
page 35 for help.
Take the example of a Model 16L2010 that comes from the factory
programmed for type J thermocouples. Suppose for this example you
wish to change the input to type K and limit the set point range between
0° and 1000° C.
First, enter the Secure menu as instructed on page 5. Press the INDEX
key until the display shows Inp and press the DOWN ARROW until the
display shows CA. Don't forget to press the ENTER key to retain your
setting.
Next, press the INDEX key to display Unit. Press the DOWN ARROW
until the display shows C. Press ENTER.
Next, press the INDEX key until SPL is displayed (pass the dPt and InPt
selections). Press the UP ARROW until the display shows 0. Press
ENTER.
Finally, press INDEX key to display SPH. Press the DOWN ARROW
until the display shows 1000. Press ENTER.
The necessary program changes are now complete. After 30 seconds
the display will switch back to the temperature reading. If you want to
return faster, press the UP ARROW and ENTER keys (at the same time)
and then press the DOWN ARROW and INDEX keys ( again at the same
time). This will 'back out' of the menu and immediately display the
temperature reading.
December, 1998Page 3 of 28949-1270
INSTALLATION
Mount the instrument in a location that will not be subject to excessive
temperature, shock, or vibration. All models are designed for mounting in an
enclosed panel.
Select the position desired for the instrument on the panel. If more than one
instrument is required, maintain the minimum of spacing requirements as
shown on the drawing below. Closer spacing will structurally weaken the
panel, and invalidate the IP66, UL type 4 rating of the panel.
Prepare the panel by cutting and deburring the required opening.
45mm
(1.77in)
45mm
(1.77in)
Cut Out
19mm
(0.75in)
45mm
(1.77in)
Cut Out
45mm
(1.77in)
All Tolerances are -0.00 +0.60mm (-0.000 +0.020)
From the front of the panel, slide the housing through the cut out. The
housing gasket should be against the housing flange before installing.
From the rear of the panel slide
the mounting collar over the housing. Hold the housing with one
PANEL
10mm (0.25")
MAX.
GASKET
SPRING LOOP
hand and using the other hand,
push the collar evenly against the
panel until the spring loops are
slightly compressed. The ratchets will hold the mounting collar
and housing in place.
MOUNTING COLLAR (SHOWN IN POSITION)
SLIDE COLLAR ONTO THE HOUSING
BEFORE WIRING THE REAR TERMINALS
CAUTION: It is not necessary to remove the instrument
chassis from the housing for installation. If the instrument chassis is removed from the housing, you must
follow industry standard practice for control and protection against Electro-Static Discharge (ESD). Failure
to exercise good ESD practices may cause damage to
the instrument.
949-1270Page 4 of 28December, 1998
WIRING
Do not run thermocouple or other class 2 wiring in the same conduit as
power leads. Use only the type of thermocouple or RTD probe for which
the control has been programmed. Maintain separation between wiring of
sensor, auxiliary in or out, and other wiring. See the "Secure Menu" for input
selection.
For thermocouple input always use extension leads of the same type
designated for your thermocouple.
For supply connections use No. 16 AWG or larger wires rated for at least
75°C. Use copper conductors only. All line voltage output circuits must
have a common disconnect and be connected to the same pole of the
disconnect.
Input wiring for thermocouple, current, and RTD; limit reset function; and
output wiring for 15 VDC is rated CLASS 2.
Control wiring is as shown.
INPUTS
Current
RTD*
Voltage
Thermocouple
+
+
-
-
-
+
F1
3/8 A @250 VAC
Medium Lag
Line Input See Rating
Label for details
* For 2-wire RTD use terminals 1 & 3, and
place a jumper wire between terminals 3 & 4.
ALARM
RESET
An external
normally open
contact may
be wired
across
terminals 9 &
10 for remote
reset.
Multiple units
can not share
common
contacts.
Terminals 9 &
10 share a
common
ground with
the input.
December, 1998Page 5 of 28949-1270
OUTPUTS
Output A
Output B
+ -
For relay, NO (Order Code 3) or SSR (Order
Code 1) outputs, 15 & 16 and 17 & 18 are
Normally Open.
For relay, NC (Order Code 4) outputs, 15 & 16
and 17 & 18 are Normally Closed.
+ -
For Pulsed DC (Order Code 2) and DC SSR
(Order Code 8) outputs, 15 & 17 are positive
and 16 & 18 are negative.
Wiring for 4 to 20mA Transmitter inputs
Wire power and outputs as shown above. Two-wire transmitters wire as
shown below.
For three or four wire transmitters follow the wiring instructions provided
with your transmitter.
CAUTION: DO NOT WIRE THE 24 VOLT POWER SUPPLY
ACROSS THE INPUT OF THE CONTROL. DAMAGE TO
THE CONTROL INPUT CIRCUITRY WILL RESULT.
Power Supply
+
Transmitter
15 to 28 VDC
+
-
-
+
-
Wiring for Optional Inputs and Outputs
Wire power and outputs as shown on page 5 and 6. Wiring for options is
shown opposite. All wiring shown below is Class 2. Shielded twisted pair
is required for Option 992.
949-1270Page 6 of 28December, 1998
CAUTION: DO NOT RUN SIGNAL WIRING IN THE SAME
CONDUIT OR CHASE AS THE POWER WIRING. ERRATIC OPERATION OR DAMAGE TO THE CONTROL
CIRCUITRY WILL RESULT.
SWITCH CONTACTS FOR OPTION 948 MUST BE ISOLATED AND CAN
NOT SHARE WIRING WITH OTHER CONTROLS.
OPTION1112678
934, 936+-nanana
948nanaSignal GroundAB
992BAnanana
993Data InData Out Signal Groundnana
Remote Indicator
Limit 1 Lamp
Limit 2 Lamp°F Indicator
Process Display°C Indicator
Set Point Display
Limit Reset Key*
* Limit Reset key flashes when limit condition is present.
Keys are illuminated when pressed. Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next
menu item. May also be used in conjunction with other keys as noted
below.
UP ARROW: Increments a value, changes a menu item, or
selects the item to ON. The maximum value obtainable is 9999
regardless of decimal point placement.
DOWN ARROW: Decrements a value, changes a menu item, or
selects the item to OFF. The minimum value obtainable is -1999
regardless of decimal point placement.
ENTER: Pressing ENTER stores the value or the item changed. If
not pressed, the previously stored value or item will be retained. The
display will flash once when ENTER is pressed.
RST
UP ARROW & ENTER: Pressing these keys simultaneously brings up
the secondary menu starting at the SP1d menu item. Pressing these keys
for 5 seconds will bring up the secure menu.
INDEX & DOWN ARROW: Pressing these keys simultaneously will allow
backing up one menu item, or if at the first menu item they will cause the
display to return to the primary menu.
949-1270Page 8 of 28December, 1998
LIMIT RESET: This key resets the limit when the limit condition has
been removed. Press and hold for three seconds to activate.
INDEX & ENTER: Pressing these keys simultaneously and holding them
for 5 seconds allows recovery from the various error messages. The
following menu items will be reset:
S1iH: Set Point 1 limit inhibitS2iH: Set Point 2 limit inhibit
OPEn InP: Input error messageCHEC CAL: Check calibration error
Correct the problems associated with the above conditions before
using these reset keys. More than one error could be present. Caution is
advised since several items are reset at one time.
While in the Primary orSecondary Menu, if no key is pressed for a period
of 30 seconds, the display will return to the HOME position displaying the
temperature value. While in the SecureMenu, if no key is pressed for a
period of 60 seconds, the display will return to the HOME position displaying
the temperature value. Outputs are disabled (turned off) when the Secure
Menu is active.
NOTE: To move to the Primary Menu quickly from any other menu, press
the UP ARROW & ENTER keys followed by pressing the INDEX & DOWN
ARROW keys.
SECURITY LEVEL SELECTION
Four levels of security are provided. The display shows the current security
level. To change security levels change the password value using the UP &
DOWN ARROW keys and pressing the ENTER key. Refer to the password
table (following) for the correct value to enter for the security level desired.
The SECr menu item security level may be viewed or changed at any time
regardless of the present security level.
To set the access level to, for example, 2, at the SECr menu item press the
UP ARROW key until the upper display show the password, 1101. Press
the ENTER key. The display will blink, and return with the level value, 2, in
the upper display.
The password values shown in the table cannot be altered, so retain a copy
of these pages for future reference. This is the only reference made to
password values in this instruction book.
December, 1998Page 9 of 28949-1270
PASSWORD TABLE
Security Level
MenuStatus
PrimaryLocked
SecondaryLocked
SecureLocked
PrimaryUnlocked
SecondaryLocked
SecureLocked
PrimaryUnlocked
SecondaryUnlocked
SecureLocked
PrimaryUnlocked
SecondaryUnlocked
SecureUnlocked
Displayed Value
When Viewed
1
2
3
4
Password Value
To Enter
1110
1101
1011
111
NOTATION CONVENTIONS FOR THE MENUS
Because of the number of features available in this control, information is
included that may not apply to your specific control. All usable features are
included in this book, but may not be used in your process. To increase
clarity the following conventions are used:
1. Certain features, Menu Items, and functions shown in this book may or
may not appear on your control, depending on other Menu Item selections.
At various places in the Menus there are notes identifying Menu Items that
"control" or "direct" other menu items. If you are looking for a particular
menu item and can't find it, check the menu item that is its "control" for
proper setting.
2. The "#" symbol is used in two ways. It is used inside a group of
characters to indicate which set point function (SP1 or SP2) is being
affected. It is also used before a group of characters of a menu item to
indicate that there may be more than one selection or value for that menu
item.
3.
Features that apply only to Options will be printed in Italics.
949-1270Page 10 of 28December, 1998
THE HOME DISPLAY
The home display is the normal display while the control is operating. The
HOME display may be programmed to operate in one of three different
ways. This is controlled by the diSP menu item in the Secure Menu.
If diSP is set for Pro, the HOME display will show only the Process Variable
(the temperature, pressure, flow, RH, etc., that is being measured) on the
top display with the bottom display blank. If diSP is set for SPt, the home
display will show only the Set Variable (Set Point 1) on the top display with
the bottom display blank. If diSP is set for both, the HOME display will
indicate the Process Variable on the top display and the Set Variable on the
bottom.
If no errors or functions are active, the HOME display as programmed will
be shown.
OPERATION AND PROGRAMMING OF OPTIONS
Option 934, 936, Isolated Analog Retransmission.
The analog retransmission option allows the Process Variable or the
Set Variable to be sent as an analog signal to an external device.
The signal may be either 0 to 10 VDC (Option 936) or 0 (or 4) to 20
mADC (Option 934). The output may be changed in the field from
one to the other by the toggle switch located on the top printed circuit
board.
Wire the output as shown on page 7.
To set up the analog retransmission, first determine the scale range
that the analog signal will represent. The maximum scale is 9999°F,
5530°C, or 9999 counts. In the Secondary Menu set POL for the
scale value that will be represented by the low end of the analog
signal (0 Volts or 0 mA). Set POH for the scale value that will be
represented by the high end of the analog signal (10 Volts or 20 mA).
If you require a suppressed scale or output, you may use the
following equations to determine the proper settings for POL and
(Maximum desired analog signal - Minimum desired analog signal).
POH = ((Maximum possible analog output - Maximum desired analog
signal) * K) + Highest desired analog reading.
December, 1998Page 11 of 28949-1270
POL = Lowest desired scale reading - ((Minimum desired analog
output) * K).
Next select whether you want the retransmission signal to follow the
Process Variable or the Set Variable. Usually the Process Variable
is sent to recorders or other data acquisition devices. Usually the
Set Variable is sent to other controls to be used as an analog remote
set point. If you want the analog retransmission signal to follow the
PV, in the Secondary Menu set POSr to InP. If you want the analog
retransmission signal to follow the SV, set POSr to SPt.
Operation is automatic. There are no further programming steps
required.
Option 948, 4-Stage Set Point.
The 4-stage set point option allows four different values to be used
for SP1. The control will switch to a given stage when an external
contact or contacts are made or opened across the appropriate
terminals at the rear of the control (when SPSA, Set Point Switch
Action, is set for remote, rE), or when the stage is selected from the
Secondary Menu, SP (when SPSA is set for Int). When the state of
a contact changes (or the stage number is changed in the Secondary
Menu), the values in use are stored and the previously stored values
for the new stage are used.
Wire the input as shown on page 7.
Usually the control is configured for external switching of the stages.
In this case, the operation is usually automatic, selected by the
external switches driven by the machine logic. If it is necessary to
program the stages in advance, you may select the stage to modify
with the SP menu item. When SP is changed while the SPSA is set
for rE, the selected stage is displayed for modification, but only used
when the appropriate contact is made.
Option 992, 993, Serial Communication.
The serial communications options allow the control to be written to
and read from a remote computer or other similar digital device.
Communication is allowed either through a RS-485 (Option 992)
port, or a RS-232 (Option 993) port.
949-1270Page 12 of 28December, 1998
Wire the communication lines as shown on Page 7. Wiring for the
RS-485 is run from control to control in a daisy chain fashion with a
termination resistor (120 ohms) across the transmit and receive
terminals of the last control in the chain.
Select the control address and communication baud rate with the
Addr and bAUd menu items in the Secure Menu. THE BAUD RATE
AND ADDRESS MENU ITEMS WILL TAKE EFFECT ON THE NEXT
POWER UP OF THE CONTROL. BE SURE TO POWER CYCLE
THE CONTROL BEFORE USING THE NEW BAUD RATE AND
ADDRESS.
In operation, you have the option of preventing a write command
from the host computer. To prevent the host from writing to the
control change the LOrE menu item in the Secondary Menu to LOC.
To allow the host to write commands to the control set LOrE to rE.
(The host does have the ability to change the LOrE state, but it is not
automatic.)
If your system depends on constant reading or writing to and from
the host, you may wish to set the No Activity Timer (nAt) to monitor
the addressing of the control. When the LOrE is set to rE and the
nAt is set to any value other than Off, the control will expect to be
addressed on a regular basis. If the control is not addressed in the
time set by the value of nAt, then the control will display the error
message CHEC LOrE. To clear the message set LOrE to LOC.
December, 1998Page 13 of 28949-1270
MENU SELECTIONS
PRIMARY MENU
Press INDEX to advance to the next menu item. Press UP ARROW or
DOWN ARROW to change the value in the display. Press ENTER to retain
the value.
#SP1(Option 948, 4-Stage Set Point) or
SP1Set Point 1 Adjust, Limit Point 1.
SP2Set Point 2 Adjust (if equipped), Limit Point 2.
SECONDARY MENU
Hold UP ARROW & ENTER. Press INDEX to advance to the next menu
item. Press UP ARROW or DOWN ARROW to change the value in the
display. Press ENTER to retain the value.
SP1dSet Point On-Off Differential (hysteresis). Select 1 to 9999 (when
S1F=Lo) or -1 to -9999 (when S1F=Hi). Set the value for the
amount of difference between the turn on point (Set Point 1) and
the turn off point. See the following chart.
S2F = Hi
S2F = Lo
DEVIATION ALARM
SP2 WHEN S2t = dE
SP2
SP1
SP2
SP1
ABSOLUTE ALARMS
SP2 when S2t = ABS
High Alarm
S#F = Hi
Low Alarm
S#F = Lo
SP1
SP#
SP#
High Alarm
Low Alarm
The following menu items apply only if your control is equipped with
a second set point (last digit of model number is not zero). If your
control does not have a second set point, jump to the "SP" menu item
below.
SP2dSet Point On-Off Differential (hysteresis). Select 1 to 9999 (when
S2F=Lo) or -1 to -9999 (when S2F=Hi). Set the value for the
amount of difference between the turn on point (Set Point 2) and
the turn off point. See chart above.
949-1270Page 14 of 28December, 1998
SP(Option 948, 4-Stage Set Point) Active Set Point Stage. Select
1SP1, 2SP1, 3SP1, 4SP1. (See Page 17 for more detail.)
1SP1Set Menu Items to display Stage 1 for view and change
access. If SPSA is set for Int, 1SP1 is made active.
2SP1Set Menu Items to display Stage 2 for view and change
access. If SPSA is set for Int, 2SP1 is made active.
3SP1Set Menu Items to display Stage 3 for view and change
access. If SPSA is set for Int, 3SP1 is made active.
4SP1Set Menu Items to display Stage 4 for view and change
access. If SPSA is set for Int, 4SP1 is made active.
#SP1(Option 948, 4-Stage Set Point) Adjust Control Point 1 for Stage
selected above.
PEAThe Peak feature stores the highest input the control has measured
since the last reset or Power On. At Power On PEA is reset to the
present input. To manually reset the value PEA must be in the lower
display. Press the ENTER key to reset. PEA will be reset and display
the present input value.
UALThe Valley feature stores the lowest input the Instrument has
measured since the last reset or Power On. At Power On UAL is reset
to the present input. To manually reset the value UAL must be in the
lower display. Press the ENTER key. UAL will be reset and display
the present input value.
InPCInput Correction: Select ±500 °F, °C, or counts. This feature
allows the input value to be changed to agree with an external
reference or to compensate for sensor error. Note: InPC is reset
to zero when the input type is changed, or when decimal position
is changed.
FiLtDigital Filter: Select OFF, 1 to 99. In some cases the time constant
of the sensor, or noise could cause the display to jump enough
to be unreadable. A setting of 2 is usually sufficient to provide
enough filtering for most cases, (2 represents approximately a 1
second time constant). When the 0.1 degree resolution is selected this should be increased to 4. If this value is set too high,
controllability will suffer.
POL(Option 934, 936, Analog Retransmission Output) Process Out-
put Low: Select -450°F, -260°C, or -1999 counts to any value less
than POH.
December, 1998Page 15 of 28949-1270
POH(Option 934, 936, Analog Retransmission Output) Process Out-
put High: Select from any value greater than POL to +9999°F,
+5530°C, or 9999 counts.
LOrE(Option 992, 993, Serial Communications) Local / Remote Status:
Select LOC or rE.
LOCThe host computer is advised not to send remote
commands. Any write commands sent to the controls
will be rejected.
rEThe host computer is allowed to send write commands.If
the control is not addressed within the time set in the nAt
(No Activity Timer, see Secure Menu) the CHEC LorE
error message will be displayed.
Addr(Option 992, Serial Communications) Control Address: Set from 1
to 3FF. This number (hexadecimal, base 16) must match the
address number used by the host computer. Viewed only in this
menu. To change this parameter, see Addr in the Secure Menu.
949-1270Page 16 of 28December, 1998
SECURE MENU
Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to advance to the
next menu item. Press UP ARROW or DOWN ARROW to change the value
in the display. Press ENTER to retain the value.
OUTPUTS ARE DISABLED (TURNED OFF) WHILE CONTROL IS IN
SECURE MENU.
SECrSecurity Code: See the Security Level Selection and the Password
Table in this manual, in order to enter the correct password.
InPInput Type: Select one of the following. Refer to the Input wiring
section for the proper wiring.
J-ICType “J” Thermocouple
CAType “K” Thermocouple
E-Type “E” Thermocouple
t-Type “T” Thermocouple
L-Type “L” Thermocouple
n-Type “N” Thermocouple
r-13Type “R” Thermocouple
S-10Type “S” Thermocouple
b-Type “B” Thermocouple
C-Type “C” Thermocouple
P392100 ohm Platinum (NIST 0.00392 Ω/Ω/°C)
n120120 ohm Nickel
P385100 ohm Platinum (DIN 0.00385 Ω/Ω/°C)
1P381000 ohm Platinum (DIN 0.00385 Ω/Ω/°C)
CurrDC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.
UoLtDC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.
diFFDC Voltage Input -10 to +10 mV.
----Reserved
OSUPZero Suppression: Select On or OFF. Only with Current and Voltage
input types.
OFFThe input range will start at 0 (zero) Input.
OnThe input range will start at 4.00 mA or 2.00 V.
UnitF, C or None.
F°F descriptor is On and temperature inputs will be dis-
played in actual degrees Fahrenheit.
C°C descriptor is On and temperature inputs will be dis-
played in actual degrees Celsius.
nonE°F and °C descriptors will be Off. This is only available with
Current and Voltage Inputs.
December, 1998Page 17 of 28949-1270
dPtDecimal Point Positioning: Select 0, 0.0, 0.00, 0.000, or .0000.
On temperature type inputs this will only effect the Process
Value, SP1, SP2, and InPC. For Current and Voltage Inputs all
Menu Items related to the Input will be affected.
0No decimal Point is selected. This is available for all
Input Types.
0.0One decimal place is available for Type J, K, E, T, L,
RTD’s, Current and Voltage Inputs.
0.00Two decimal places is only available for Current and
Voltage Inputs.
0.000Three decimal places is only available for Current and
Voltage inputs.
.0000Four decimal places is only available for Current and
Voltage inputs.
diSPHome Display: Select Pro, SPt, or both.
ProThe upper display of the HOME display shows the
current Process Variable. The lower display is blank.
SPtThe upper display of the HOME display shows the
current Set Variable. The lower display is blank.
bothThe upper display of the HOME display shows the
current Process Variable. The lower display shows the
current Set Variable.
InPtInput Fault Timer: Select OFF, 0.1 to 540.0 minutes. Whenever an
Input is out of range (UFL or OFL displayed), shorted, or open the
timer will start. When the time has elapsed, the controller outputs
will be forced into their de-energized states. If OFF is selected, the
Input Fault Timer will not be recognized (time = infinite).
SEnCSensor Rate of Change: Select OFF, 1 to 4000 °F, °C, or counts
per 1 second period. This value is usually set to be slightly greater
than the fastest process response expected during a 1 second
period, but measured for at least 2 seconds. If the process is faster
than this setting, the SEnC bAd error message will appear. The
outputs will then be turned off. This function can be used to detect
a runaway condition, or speed up detection of an open thermocouple. Use the INDEX & ENTER keys to reset.
SCALScale Low: Select 100 to 9999 counts below SCAH. The total span
between SCAL and SCAH must be within 11998 counts. Maximum
setting range is -1999 to +9999 counts. For Current and Voltage
inputs, this will set the low range end. Viewable only for Thermocouple and RTD ranges.
949-1270Page 18 of 28December, 1998
SCAHScale High: Select 100 to 9999 counts above SCAL. The total span
between SCAL and SCAH must be within 11998 counts. Maximum
setting range is -1999 to +9999 counts. For Current and Voltage
inputs, this will set the high range end. Viewable only for Thermocouple and RTD ranges.
SPLSet Point Low: Select from the lowest input range value to SPH
value. This will set the minimum SP1 or SP2 value that can be
entered. The value for SP1 or SP2 will not stop moving when this
value is reached.
SPHSet Point High: Select from the highest input range value to SPL
value. This will set the maximum SP1 or SP2 value that can be
entered. The value for SP1 or SP2 will not stop moving when this
value is reached.
SP1OSet Point 1 Output Select: Select A or A-b.
ASet Point 1 is routed through Output A, Set Point 2 (if
equipped) is routed through Output B.
A-bSet Point 1 is routed through both Output A and Output
B. Set Point 2 menu items are suppressed. This allows
for both NO and NC (Order Code types 3 and 4) outputs
to be driven at the same time.
S1FSet Point 1 Function: Select Hi or Lo.
HiOutput is energized above set point.
LoOutput is energized below set point.
S1rESet Point 1 Reset. Select OnOF or Hold.
OnOFControl will automatically reset when process passes
back through SP1d.
HoLdManual Reset. Reset (acknowledge) by pressing the
LIMIT RESET key for 3 seconds.
S1PiSet Point 1 Power Interrupt. Select On or OFF.
OnAlarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFFAlarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S1iHSet Point 1 Inhibit: Select On or OFF.
OnAlarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFFAlarm Inhibit is OFF.
December, 1998Page 19 of 28949-1270
S1StSet Point 1 State: Select Eng or dEng.
EngOutput Energized. The output device (per Order Code)
will be energized at set point. (Normally Open contacts
will close, Normally Closed contacts will open.)
dEngOutput De-energized. The output device (per Order
Code) will be de-energized at set point. (Normally Open
contacts will open, Normally Closed contacts will close.)
S1LPSet Point Lamp: Select O on or OoFF.
O onLamp ON when Output is ON (energized).
OoFFLamp OFF when Output is ON (energized).
If your instrument is not equipped with Set Point 2, then proceed to
the option section (next page). If the instrument has no Set Point 2 and
no options, then the menu ends.
S2tSet Point 2 type: Select Abs or dE.
AbSAbsolute SP2. SP2 is independent of SP1, and may be set
anywhere between the limits of SPL and SPH.
dEDeviation SP2. SP2 is set as a deviation from SP1, and
allows SP2 to retain its relationship with SP1 when SP1 is
changed (tracking SP2).
S2FSet Point 2 Function: Select Hi of Lo.
HiOutput is energized above set point.
LoOutput is energized below set point.
S2rESet Point 2 Reset. Select OnOF or Hold.
OnOFControl will automatically reset when process passes
back through SP2d.
HoLdManual Reset. Reset (acknowledge) by pressing the
LIMIT RESET key for 3 seconds.
S2PiSet Point 2 Power Interrupt. Select On or OFF.
OnAlarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFFAlarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S2iHSet Point 2 Inhibit: Select On or OFF.
OnAlarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFFAlarm Inhibit is OFF.
949-1270Page 20 of 28December, 1998
S2StSet Point 2 State: Select Eng or dEng.
EngOutput Energized. The output device (per Order Code)
will be energized at set point. (Normally Open contacts
will close, Normally Closed contacts will open.)
dEngOutput De-energized. The output device (per Order
Code) will be de-energized at set point. (Normally Open
contacts will open, Normally Closed contacts will close.)
S2LPSet Point 2 Lamp: Select O on or OoFF.
O onLamp ON when Output is ON (energized).
OoFFLamp OFF when Output is ON (energized).
SPSA(Option 948, 4-Stage Set Point) Switch Action: Select rE or Int.
rESet Point Stage selected by external contact closures.
IntSet Point Stage selected by internal menu selection. See
SP menu item in Secondary Menu.
Addr(Option 992, 993, Serial Communications) Control Address: Set
from 1 to 3FF. This number (hexadecimal, base 16) must match the
address number used by the host computer.
bAUd(Option 992, 993, Serial Communications) Communication Baud
Rate: Select 300, 1200, 2400, 4800, 9600, or 19200. This number
must match the baud rate used by the host computer.
nAt(Option 992, 993, Serial Communications) No Activity Timer: Set
from OFF or 1 to 99 minutes.1 - 99Maximum time between host computer accesses. If timer
counts to 0, CHEC/LorE will be displayed.
OFFNo Activity Timer function is disabled.
December, 1998Page 21 of 28949-1270
DISPLAY
DIAGNOSTIC ERROR MESSAGES
MEANING
SP OUTPUTS
ACTION REQUIRED
No
display
lighted
FAIL
tESt
CHEC
SP1,
CHEC
SP2
CHEC
SPL
or
CHEC
SPH
Display is blank. Instrument is not getting power, or the
supply voltage is too
low.
Fail test appears
upon power up if the
internal diagnostics
detect a failure. This
message may occur during operation
if a failure is detected. Displays flash.
This message will
appear upon power
up if SP1, SP2, or
#SP1 is set outside
of the SPL or SPH
values.
This message appears at power up if
SPL or SPH values
are programmed
outside the input
range ends.
Set point
outputs inactive
Alarm inactive
Set point
outputs inactive
Alarm inactive
Set point
outputs inactive
Alarm active
Set point
outputs inactive
Alarm inactive
Check that the power supply is
on, or that the external fuses
are good.
The display alternate between
FAIL tESt and one of the following messages: FACt dFLt:
Memory may be corrupted.
Press the ENTER key and the
DOWN ARROW key to start
the factory default procedure.
Recheck controller programming. rEt FACt: Unrecoverable error, return to factory for
service.
Correct the SP1, etc. or adjust
the SPL or SPH values by
programming new values.
Correct the SPL or SPH values by programming new values.
CHEC
LorE
ArEA
(Alter-
nates
with PV)
ArEA
This message appears if the Serial
Communications
has timed out.
This message appears
when the ambient temperature of the control
approaches unacceptable ambients.
This message appears
if the ambiient temperature of the control is
out of range or RJC
sensor is broken.
Set point
outputs active
Alarm inactive
Set point
outputs active
Alarms active
Set point
outputs active
Alarms active
Restore the communications
line and switch the LorE to
LOC.
Correct the ambient temperature
conditions. Ventilate the area of
the cabinet or check for clogged
filters. If RJC broken, return to
factory for service.
Correct the ambient temperature
conditions. Ventilate the area of
the cabinet or check for clogged
filters. If RJC broken, return to
factory for service.
949-1270Page 22 of 28December, 1998
DISPLAY
DIAGNOSTIC ERROR MESSAGES
MEANING
SP OUTPUTS
ACTION REQUIRED
UFL
or
OFL
bAd
InP
OPEn
InP
SEnC
bAd
CHEC
CAL
Underflow or Overflow: Process value
has exceeded input
range ends.
UFL or OFL will sequence to display
one of these messages if the InPt is
set for a time value.
For RTD inputs RTD
is open or shorted.
For THERMOCOUPLE inputs thermocouple is open.
Sensor Rate of
Change exceeded
the programmed limits set for SEnC.
Check calibration appears as an alternating message if the
instrument calibration nears tolerance
edges.
Set point
outputs active
Alarm active
Set point
outputs
inactive
Alarm active
Set point
outputs
inactive.
Alarm Active
Set point
outputs active
Alarm active
Input signals may normally go
above or below range ends. If
not, check input and correct.
To reset use the INDEX &
ENTER keys. When InPt (in-
put fault timer) has been set
for a time, the outputs will be
turned off after the set time.
Setting the time to OFF causes the outputs to remain active, however UFL or OFL will
still be displayed.
Correct or replace sensor. To
reset use the INDEX & EN-TER keys.
Check for the cause of the
error. The value setting may
be too slow for the process, or
the sensor is intermittent.
Correct the problem and press
INDEX and ENTER to reset.
Remove the instrument for
service and / or recalibration.
To reset use the INDEX &
ENTER keys.
Check calibration appears as a flashing
message if the instrument calibration exceeds specification.
Set point
outputs
inactive
Alarm active
Remove the instrument for
service and / or recalibration.
To reset use the INDEX &
ENTER keys.
December, 1998Page 23 of 28949-1270
SPECIFICATIONS
Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current
selectable.
Input Impedance:
Thermocouple = 3 megohms minimum.RTD current = 200 µA.
Current = 10 ohms.Voltage = 5000 ohms.
Sensor Break Protection: De-energizes output(s) to protect system after
customer set time. (See InPt in Secondary Menu.)
Set Point Range: Selectable (See Range Chart Page 26).
Display: Two 4 digit, 7 segment 0.3" high LEDs.
Output Action: Fully programmable to allow output(s) to energize or de-
energize above or below set point(s).
On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F,
1° C, or 1 count steps.
Accuracy: ±0.25% of span, ±1 least significant digit.
Resolution: 1 degree or 0.1 degree, selectable.
Line Voltage Stability: ±0.05% over the supply voltage range.
Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F)
maximum (100 ppm / °C typical, 200 ppm / °C maximum).
Common Mode Rejection: 140 db minimum at 60 Hz.
Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
Isolation:
Relay and SSR outputs: 1500 Vac to all other inputs and outputs.
SP1 and SP2 Switched Voltage outputs: 500 Vac to all other inputs
and outputs, but not isolated from each other.
Process Output (934, 936): 500 VAC to all other inputs and outputs.
Supply Voltage: 100 to 240 Vac, nominal., +10 -15%, 50 to 400 Hz. single
phase; 132 to 240 Vdc, nominal., +10 -20%.
Supply Voltage (Option 9502): 12 to 24 Vdc, Vac 40-400 Hz, ±20%.
Power Consumption: 5VA maximum.
Operating Temperature: -10 to +55 °C (+14 to 131 °F).
Storage Temperature: -40 to +80 °C (-40 to 176 °F).
Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at
55 °C non-condensing.
Memory Backup: Nonvolatile memory. No batteries required.
949-1270Page 24 of 28December, 1998
Output Ratings:
AC SSR: 2.0 A @ 240 Vac at 25 °C (77°F). Derates to 1.0 A @ 55° C
(130°F).
DC SSR: 1.75 A @ 32 Vdc maximum.
Relay: SPST, 3 A @ 240 Vac resistive; 1.5A @240 Vac inductive;
Pilot duty rating 240 VA, 2 A @ 120 Vac or 1 A 240 Vac.
Switched Voltage (isolated): 15 Vdc @ 20 mA.
Panel Cutout: 45 mm x 45 mm (1.775" x 1.775").
Depth Behind Mounting Surface: 121.6 mm (4.79"), maximum.
Weight: 220 g (8 oz).
Agency Approvals: FM, CE.
Front Panel Rating: IP66, (NEMA4X).
December, 1998Page 25 of 28949-1270
Input Ranges (Field Selectable)
Thermocouple T ypes
Input
Type
Range
1°F
1°C
Input
Type
Range
1°F
1°C
Input
Type
Range
1°F
1°C
Type J or L*
-100 to +1600
-73 to +871
Type R
0 to 3200
-17 to +1760
Type N*
-100 to +2372
-73 to +1300
Type K*
-200 to +2500
-129 to +1371
Type S
0 to 3200
-17 to +1760
* These Input Types can be set for 0.1° display.
If temperature goes above 999.9° or less than
-199.9° the display will return to whole degree
resolution.
Type T*
-350 to +750
-212 to +398
Type B
+75 to 3308
+24 to 1820
Type E*
-100 to +1800
-73 to +982
Type C
0 to 4208
-17 to 2320
RTD Types
Input
Type
Range
1°F
1°C
100 Ohm
Platinum
0.00385 DIN
Curve*
-328 to +1607
-200 to +875
100 Ohm
Platinum
0.00392 Nist
Curve*
-328 to +1607
-200 to +875
120 Ohm
Nickel
0.00628 US
Ind. Curve*
-112 to +608
-80 to +320
1000 Ohm
Platinum
0.00385 Nist
Curve*
-328 to +1607
-200 to +875
Process Input Types
The 0 to 20 mAdc, 4 to 20 mAdc, 0 to 10 Vdc, 2 to 10 Vdc, and -10 to +10
mVdc inputs are fully scalable from a minimum of 100 counts span placed
anywhere within the within the range of -1999 to +9999. Decimal point
position is adjustable from the zero place (9999), tenths (999.9), hundredths (99.99), thousandths (9.999), or ten thousandths (.9999).
949-1270Page 26 of 28December, 1998
December, 1998Page 27 of 28949-1270
DIMENSIONS
L
LM
LM
All dimensions in millimeters (inches). Panel cut out is 45 +0.6 (1.77 +0.02) square.
RESET
FM
®
LOVE CONTROLS DIVISION
Dwyer Instruments, Incorporated
®
PO Box 338 Michigan City, IN 46361-0338
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
949-1270Page 28 of 28December, 1998
m
m
www.love-controls.com
m
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.