934 Analog Retransmission of Process Variable, 4 to 20 mAdc.
936 Analog Retransmission of Process Variable, 0 to 10 Vdc.
948 4-Stage Set Point.
992 RS-485 Serial Communications.
993 RS-232 Serial Communications.
9502 12 - 24 Vdc/Vac 50-400Hz power supply (control operates on low
voltage equipment).
Note:Only Option 9502 may be combined with another option.
2. Wire your control following the instructions on page 5. If you are
using a two-wire transmitter as an input, see the drawing and
instructions on page 6. Option wiring instructions are on Page 7.
Option descriptions and specific instructions start on page 16.
3. Most controls do not need many (if any) program changes to work
on your process. For best results when programming changes are
necessary, make all the necessary changes in the Secure Menu
(page 26) before making changes to the Secondary Menu (page 19).
If error messages occur, check the Diagnostic Error Messages on
page 35 for help.
Take the example of a Model 16L2010 that comes from the factory
programmed for type J thermocouples. Suppose for this example you
wish to change the input to type K and limit the set point range between
0° and 1000° C.
First, enter the Secure menu as instructed on page 5. Press the INDEX
key until the display shows Inp and press the DOWN ARROW until the
display shows CA. Don't forget to press the ENTER key to retain your
setting.
Next, press the INDEX key to display Unit. Press the DOWN ARROW
until the display shows C. Press ENTER.
Next, press the INDEX key until SPL is displayed (pass the dPt and InPt
selections). Press the UP ARROW until the display shows 0. Press
ENTER.
Finally, press INDEX key to display SPH. Press the DOWN ARROW
until the display shows 1000. Press ENTER.
The necessary program changes are now complete. After 30 seconds
the display will switch back to the temperature reading. If you want to
return faster, press the UP ARROW and ENTER keys (at the same time)
and then press the DOWN ARROW and INDEX keys ( again at the same
time). This will 'back out' of the menu and immediately display the
temperature reading.
December, 1998Page 3 of 28949-1270
INSTALLATION
Mount the instrument in a location that will not be subject to excessive
temperature, shock, or vibration. All models are designed for mounting in an
enclosed panel.
Select the position desired for the instrument on the panel. If more than one
instrument is required, maintain the minimum of spacing requirements as
shown on the drawing below. Closer spacing will structurally weaken the
panel, and invalidate the IP66, UL type 4 rating of the panel.
Prepare the panel by cutting and deburring the required opening.
45mm
(1.77in)
45mm
(1.77in)
Cut Out
19mm
(0.75in)
45mm
(1.77in)
Cut Out
45mm
(1.77in)
All Tolerances are -0.00 +0.60mm (-0.000 +0.020)
From the front of the panel, slide the housing through the cut out. The
housing gasket should be against the housing flange before installing.
From the rear of the panel slide
the mounting collar over the housing. Hold the housing with one
PANEL
10mm (0.25")
MAX.
GASKET
SPRING LOOP
hand and using the other hand,
push the collar evenly against the
panel until the spring loops are
slightly compressed. The ratchets will hold the mounting collar
and housing in place.
MOUNTING COLLAR (SHOWN IN POSITION)
SLIDE COLLAR ONTO THE HOUSING
BEFORE WIRING THE REAR TERMINALS
CAUTION: It is not necessary to remove the instrument
chassis from the housing for installation. If the instrument chassis is removed from the housing, you must
follow industry standard practice for control and protection against Electro-Static Discharge (ESD). Failure
to exercise good ESD practices may cause damage to
the instrument.
949-1270Page 4 of 28December, 1998
WIRING
Do not run thermocouple or other class 2 wiring in the same conduit as
power leads. Use only the type of thermocouple or RTD probe for which
the control has been programmed. Maintain separation between wiring of
sensor, auxiliary in or out, and other wiring. See the "Secure Menu" for input
selection.
For thermocouple input always use extension leads of the same type
designated for your thermocouple.
For supply connections use No. 16 AWG or larger wires rated for at least
75°C. Use copper conductors only. All line voltage output circuits must
have a common disconnect and be connected to the same pole of the
disconnect.
Input wiring for thermocouple, current, and RTD; limit reset function; and
output wiring for 15 VDC is rated CLASS 2.
Control wiring is as shown.
INPUTS
Current
RTD*
Voltage
Thermocouple
+
+
-
-
-
+
F1
3/8 A @250 VAC
Medium Lag
Line Input See Rating
Label for details
* For 2-wire RTD use terminals 1 & 3, and
place a jumper wire between terminals 3 & 4.
ALARM
RESET
An external
normally open
contact may
be wired
across
terminals 9 &
10 for remote
reset.
Multiple units
can not share
common
contacts.
Terminals 9 &
10 share a
common
ground with
the input.
December, 1998Page 5 of 28949-1270
OUTPUTS
Output A
Output B
+ -
For relay, NO (Order Code 3) or SSR (Order
Code 1) outputs, 15 & 16 and 17 & 18 are
Normally Open.
For relay, NC (Order Code 4) outputs, 15 & 16
and 17 & 18 are Normally Closed.
+ -
For Pulsed DC (Order Code 2) and DC SSR
(Order Code 8) outputs, 15 & 17 are positive
and 16 & 18 are negative.
Wiring for 4 to 20mA Transmitter inputs
Wire power and outputs as shown above. Two-wire transmitters wire as
shown below.
For three or four wire transmitters follow the wiring instructions provided
with your transmitter.
CAUTION: DO NOT WIRE THE 24 VOLT POWER SUPPLY
ACROSS THE INPUT OF THE CONTROL. DAMAGE TO
THE CONTROL INPUT CIRCUITRY WILL RESULT.
Power Supply
+
Transmitter
15 to 28 VDC
+
-
-
+
-
Wiring for Optional Inputs and Outputs
Wire power and outputs as shown on page 5 and 6. Wiring for options is
shown opposite. All wiring shown below is Class 2. Shielded twisted pair
is required for Option 992.
949-1270Page 6 of 28December, 1998
CAUTION: DO NOT RUN SIGNAL WIRING IN THE SAME
CONDUIT OR CHASE AS THE POWER WIRING. ERRATIC OPERATION OR DAMAGE TO THE CONTROL
CIRCUITRY WILL RESULT.
SWITCH CONTACTS FOR OPTION 948 MUST BE ISOLATED AND CAN
NOT SHARE WIRING WITH OTHER CONTROLS.
OPTION1112678
934, 936+-nanana
948nanaSignal GroundAB
992BAnanana
993Data InData Out Signal Groundnana
Remote Indicator
Limit 1 Lamp
Limit 2 Lamp°F Indicator
Process Display°C Indicator
Set Point Display
Limit Reset Key*
* Limit Reset key flashes when limit condition is present.
Keys are illuminated when pressed. Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next
menu item. May also be used in conjunction with other keys as noted
below.
UP ARROW: Increments a value, changes a menu item, or
selects the item to ON. The maximum value obtainable is 9999
regardless of decimal point placement.
DOWN ARROW: Decrements a value, changes a menu item, or
selects the item to OFF. The minimum value obtainable is -1999
regardless of decimal point placement.
ENTER: Pressing ENTER stores the value or the item changed. If
not pressed, the previously stored value or item will be retained. The
display will flash once when ENTER is pressed.
RST
UP ARROW & ENTER: Pressing these keys simultaneously brings up
the secondary menu starting at the SP1d menu item. Pressing these keys
for 5 seconds will bring up the secure menu.
INDEX & DOWN ARROW: Pressing these keys simultaneously will allow
backing up one menu item, or if at the first menu item they will cause the
display to return to the primary menu.
949-1270Page 8 of 28December, 1998
LIMIT RESET: This key resets the limit when the limit condition has
been removed. Press and hold for three seconds to activate.
INDEX & ENTER: Pressing these keys simultaneously and holding them
for 5 seconds allows recovery from the various error messages. The
following menu items will be reset:
S1iH: Set Point 1 limit inhibitS2iH: Set Point 2 limit inhibit
OPEn InP: Input error messageCHEC CAL: Check calibration error
Correct the problems associated with the above conditions before
using these reset keys. More than one error could be present. Caution is
advised since several items are reset at one time.
While in the Primary orSecondary Menu, if no key is pressed for a period
of 30 seconds, the display will return to the HOME position displaying the
temperature value. While in the SecureMenu, if no key is pressed for a
period of 60 seconds, the display will return to the HOME position displaying
the temperature value. Outputs are disabled (turned off) when the Secure
Menu is active.
NOTE: To move to the Primary Menu quickly from any other menu, press
the UP ARROW & ENTER keys followed by pressing the INDEX & DOWN
ARROW keys.
SECURITY LEVEL SELECTION
Four levels of security are provided. The display shows the current security
level. To change security levels change the password value using the UP &
DOWN ARROW keys and pressing the ENTER key. Refer to the password
table (following) for the correct value to enter for the security level desired.
The SECr menu item security level may be viewed or changed at any time
regardless of the present security level.
To set the access level to, for example, 2, at the SECr menu item press the
UP ARROW key until the upper display show the password, 1101. Press
the ENTER key. The display will blink, and return with the level value, 2, in
the upper display.
The password values shown in the table cannot be altered, so retain a copy
of these pages for future reference. This is the only reference made to
password values in this instruction book.
December, 1998Page 9 of 28949-1270
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.