Dwyer 166T User Manual

Model 166T Telescoping Pitot Tube
7/16 [11.11] DIA.
11-15/32
[291.3]
Dimensions — Operating Instructions
40-7/16
[1027]
Bulletin H-18
The Model 166T Telescoping Pitot Tube is a convenient
The Model 166T consists of a standard 1/8˝ diameter Pilot tube attached to a four-section stainless steel telescoping tube and a comfortable hand grip designed for ease in maintaining proper orientation. This device can be used at any length from 1115/ to 407/16˝ (30 to 103 cm). A 3/8˝ (9.5 mm) diameter hole is required for full insertion. For maximum accuracy, the 1/8˝ diam­eter tip should be always be extended to its full 3˝ length regard­less of how far the telescopic sections are extended.
While extending the tip, twist it slowly back and forth until you feel it engage with the end of the first telescoping section. Next, extend the Model 166T to the required length and rotate the tele-
32
scoping sections to align the tip so it points in the same direction as the finger grips on the handle. See drawings. Now when unit is inserted in the duct, you can refer to the handle orientation as a guide to assuring the tip is pointing into the airstream as required for best accuracy.
When extending or collapsing the telescopic tube, be sure the flexible rubber tubing moves freely through the opening in the end of the handle. The pressure connections on the terminal block are marked "S" for static pressure and "T" for total pres­sure. Connect the static pressure to the minus (-) or low pres-
˝
sure port on the manometer or gage and the total pressure to the positive (+) or high pressure port. See Dwyer Instruments, Inc. full line catalog for complete air flow measuring instructions, for­mulas and flow curves.
©Copyright 2009 Dwyer Instruments, Inc. Printed in U.S.A. 7/09 FR# 72-440948-00 Rev. 2
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Phone: 219/879-8000 www.dwyer-inst.com