Dwyer 1600 User Manual

INSTRUCTIONS FOR THE
1600 SERIES
MICROPROCESSOR BASED
TEMPERATURE / PROCESS
CONTROL
INCLUDES FUZZY LOGIC OPTION
LOVE CONTROLS DIVISION
Dwyer Instruments, Incorporated
®
Rev. 10/98 1 949-1239-3
(800) 828-4588 (219) 879-8000 FAX (219) 872-9057
www.love-controls.com
TABLE OF CONTENTS
GETTING STARTED .............................................................................. 2
INSTALLATION.......................................................................................4
DIMENSIONS ......................................................................................... 5
INPUT SELECTION ................................................................................ 5
LOGIC JUMPER SELECTION................................................................ 6
WIRING................................................................................................... 7
FRONT PANEL KEY FUNCTIONS......................................................... 8
NOTATION CONVENTIONS FOR THE MENUS .................................10
THE HOME DISPLAY ........................................................................... 10
OPERATION OF SELF TUNE® FUNCTION........................................ 11
Theory of Operation .....................................................................11
Program Setup and Operation .................................................... 12
METHOD FOR SET UP OF A HEAT / COOL CONTROL WITH SELF
TUNE .................................................................................................... 12
PROGRAMMING AND OPERATION FOR RAMP / SOAK FEATURE13
Theory of Operation .....................................................................13
Program Setup .............................................................................. 13
Ramp / Soak Operation ................................................................ 14
MENU SELECTIONS........................................................................... 15
PRIMARY MENU ..................................................................................15
SECONDARY MENU ............................................................................ 15
SECURE MENU.................................................................................... 21
DIAGNOSTIC ERROR MESSAGES ....................................................28
CONFIGURATION MENU .................................................................... 30
SPECIFICATIONS ................................................................................ 35

GETTING STARTED

1. Install the control as described on page 4.
2. Make sure that the Input DIP switch is set correctly for the input you wish to use. Instructions on page 5.
3. If you wish to use the Logic (5 VDC) output, make sure that the Logic jumper is in the correct position. See page 6 for details.
4. Wire your control following the drawing on page 7.
5. Make any programming changes necessary first in the Secure Menu (page 21), next in the Secondary Menu (page 15), and finally in the Primary Menu (page 15). DO NOT make changes to the Configuration Menu unless specifically instructed. If you need to back up in a menu, press the INDEX and DOWN ARROW keys together.
949-1239-3 2 Rev. 10/98
6. To quickly return to the HOME position, press the UP ARROW and ENTER keys together, and then the INDEX and DOWN ARROW keys.
Take the example of a Model 16010 that comes from the factory pro­grammed for type J thermocouples. Suppose for this example you wish to change the input to 100 ohm Platinum DIN RTD and limit the set point range between 0° and 500° C.
First, change the input DIP switch as shown on page 5. For RTD inputs switches 1, 3, and 4 are off, switch 2 is on.
Next, enter the Secure menu as instructed on page 8. Press the INDEX key until the display shows Inp and press the DOWN ARROW until the display shows P385. Don't forget to press the ENTER key to retain your setting.
Next, press the INDEX key to display Unit. Press the DOWN ARROW until the display shows C. Press ENTER.
Next, press the INDEX key until SPL is displayed (pass the dPt and InPt selections). Press the UP ARROW until the display shows 0. Press ENTER.
Finally, press INDEX key to display SPH. Press the DOWN ARROW until the display shows 500. Press ENTER.
The necessary program changes are now complete. After 60 seconds the display will switch back to the temperature reading. If you want to return faster, press the UP ARROW and ENTER keys (at the same time) and then press the DOWN ARROW and INDEX keys ( again at the same time). This will 'back out' of the menu and immediately display the temperature reading.
If you want to use Self Tune®, Auto/Manual, or the Ramp/Soak Program­mer features, see the special sections on these items. Page numbers for
these are in the Contents section on the previous page.
Rev. 10/98 3 949-1239-3
INSTALLATION
Mount the instrument in a location that will not be subject to excessive temperature, shock, or vibration. All models are designed for mounting in an enclosed panel.
Select the position desired for the instrument on the panel. If more than one instrument is required, maintain the minimum of spacing requirements as shown on the drawing opposite. Closer spacing will structurally weaken the panel, and invalidate the IP66, UL type 4 rating of the panel.
Prepare the panel by cutting and deburring the required opening.
45mm
(1.77in)
45mm
(1.77in)
Cut Out
19mm
(0.75in)
45mm
(1.77in)
Cut Out
45mm
(1.77in)
All Tolerances are -0.00 +0.60mm (-0.000 +0.020)
From the front of the panel, slide the housing through the cut out. The housing gasket should be against the housing flange before installing.
From the rear of the panel slide the mounting collar over the hous­ing. Hold the housing with one
PANEL
10mm (0.25")
MAX.
GASKET
SPRING LOOP
hand and using the other hand, push the collar evenly against the panel until the spring loops are slightly compressed. The ratch­ets will hold the mounting collar and housing in place.
MOUNTINGCOLLAR(SHOWNINPOSITION) SLIDE COLLAR ONTO T HE HOUSING BEFORE WIRING THE REAR T ERMINALS
It is not necessary to remove the control chassis from the housing for installation. If the control chassis is removed from the housing, you must follow industry standard practice for control and protection against Electro-Static Discharge (ESD). Failure to exercise good ESD practices may cause damage to the control.
949-1239-3 4 Rev. 10/98

DIMENSIONS

(All dimensions in millimeters with inches in parenthesis.)
125 (4.925)
48 (1.880)
LOVE
CONTROLS CORP.
R
48
(1.880)
SP1
SP2
AL
˚F ˚C
INDEX
AL
R
ENTER
AL
MADE IN USA
PV
SV
12 (0.450) * 3 (0.125)
Panel cutout for all models is 45mm x 45mm (1.775 in x 1.775 in). Allow for 13 mm (0.5 in) clearance at the rear of the instrument. * Present for SSR outputs.

INPUT SELECTION

Before removing the instrument from its housing, make sure you take appropriate precautions to avoid electro-static discharge (ESD). See caution on opposite page. To change the input type, remove the instru­ment from its housing by grasping the front bezel sides and pulling forward to release it from the housing lock.
114 (4.475)
(1.760)
DIP SWITCH LOCATION
45
Locate the dip switch on the right pcb. Determine the input type desired and change the dip switch setting as shown at the right.
1
Reinstall the instrument into the housing.
THERMOCOUPLE INPUTS
2 3 4
After changing input selec­tion with the DIP switches,
RTD INPUTS
be sure to change the InP menu item (page 11) in the Secure Menu.
CURRENT INPUT
VOLTAGE INPUT
Rev. 10/98 5 949-1239-3

LOGIC JUMPER SELECTION

Instruments with SSR or RELAY type outputs can be changed to and from a LOGIC output in the field.
CAUTION: Damage to the instrument may result from an incorrectly installed jumper strip. Follow the instructions carefully. Damage to the instrument may also result from improper handling. Use appropriate precautions to avoid Electro-Static Discharge (ESD).
1. Remove the instrument from its housing. Grasp the front bezel sides and
pull forward to release it from the housing lock.
2. Locate the desired logic jumper strip on the left printed circuit board. The
OUTPUT A jumper strip is always lo-
OUTPUT A SET FOR LOGIC TYPE OUTPUT
cated near the top edge
3. To remove the logic
jumper strip, carefully insert a small flat blade screwdriver be­tween the retaining clip and the jumper at one end of the jumper strip. Apply slight pressure to
OUTPUT B SET FOR SSR or RELAY TYPE OUTPUT
SLIGHT PRESSURE TO RELEASE
RETAINING CLIP
move the clip away from the jumper end until it is released, then lift it up and out of the clip.
4. To re-install the jumper strip, hold it with the spring contacts in the desired
position. Face springs up for SSR or RELAY outputs, or face springs down for LOGIC outputs. Insert one end of the jumper strip under the retaining clip and press the other end down until the remaining clip engages the jumper.
SPRINGS DOWN
INSTALLING JUMPER FOR
LOGIC TYPE OUTPUT
SPRINGS UP
INSTALLING JUMPER FOR
SSR or RELAY TYPE
OUTPUT
5. To avoid any damage, recheck the jumper installation and the housing rear
terminal panel output wiring.
6. Replace the instrument into its housing.
949-1239-3 6 Rev. 10/98
Rev. 10/98 7 949-1239-3
WIRING
INPUTS
ocouple
RTD*
Current
Voltage
Therm
+
+
-
-
ALARM OUTPUT
Terminals 4 & 5 are Normally Open. See Rating Label.
F1 3/8 A @250 VAC Medium Lag
* For 2-wire 1000 RTD use terminals 1 & 3.
For 2-wire 100 RTD use terminals 1 & 3, and place a jumper wire between terminals 3 & 4.
INPUT WIRING: Do not run thermocouple of other signal wiring in the same conduit as power leads. Use only the type of thermocouple or RTD probe for which the instrument has been programmed. See Secure Menu for Input Programming.
For thermocouple input always use extension leads of the same type designated for your thermocouple.
Outputs A and B may be logically swiched. See Secure Menu for details.
AL1
Line Input See Rating
Label for details
F1
}{ }{
Relay** N.O.
Solid State Relay N.O.
SSR Derating Chart ˚C ˚F CURRENT
25 77 3.50 35 95 2.75 45 113 2.00 55 131 1.25
5VDC Output 5V = On, 0V = Off
5VDC @
25mA
5VDC @
25mA
For Relay or SSR outputs use type MDA or 3AB 3.5A medium lag fuse.
** R/C snubber is recommended for driving solenoid or contactor loads.
-
+
-
+
Current or
Voltage
+
}{
-
+
}{
-
Output
A
Output
B
OPTIONS
948
936
992
+
0 to 10 VDC @ 25 mA
-
B (+)
A (-)

FRONT PANEL KEY FUNCTIONS

Set Point 1 Lamp Process Variable Alarm Lamp Set Point 2 Lamp Set Variable
°F Indicator °C Indicator
INDEX: Pressing the INDEX key advances the display to the next menu item. May also be used in conjunction with other keys as noted below.
UP ARROW: Increments a value, changes a menu item, or selects the item to ON in the upper display.
DOWN ARROW: Decrements a value, changes a menu item, or selects the item to OFF in the upper display.
ENTER: Pressing ENTER stores the value or the item changed. If not pressed, the previously stored value or item will be retained.
UP ARROW & ENTER: Pressing these keys simultaneously brings up the secondary menu starting at the auto/manual selection. Pressing these keys for 5 seconds will bring up the secure menu.
INDEX & DOWN ARROW: Pressing these keys simultaneously will allow
backing up one menu item, or if at the first menu item they will cause the display to return to the primary menu. If an alarm condition has occurred, these keys may be used to reset the alarm.
INDEX & ENTER: Pressing these keys simultaneously and holding them for 5 seconds allows recovery from the various error messages. The following menu items will be reset:
LPbr: Loop break SEnC: Sensor rate of change ALiH: Alarm inhibit OPEn InP: Open input error message ArEA: Area error message bAd InP: Bad input error message CHEC CAL: Check calibration error message
Correct the problems associated with the above conditions first before using these reset keys. More than one error could be present. Caution is advised since several items are reset at one time.
949-1239-3 8 Rev. 10/98
While in the Primary or Secondary menu, if no key is pressed for a period of 30 seconds, the display will return to the HOME position displaying the PV and SV values. The time is increased to 1 minute when in the Secure menu.
NOTE: To move to the primary menu quickly from any other menu, press the UP ARROW & ENTER keys followed by pressing the INDEX & DOWN
ARROW keys.
NOTE: Program the Secure Menu first, the Secondary Menu second, and the Primary Menu last.
SECURITY LEVEL SELECTION
Four levels of security are provided. The display shows the current security level. To change security levels change the password value using the UP & DOWN ARROW keys and pressing the ENTER key. Refer to the password table below for the correct value to enter for the security level desired. The SECr menu item security level may be viewed or changed at any time regardless of the present security level. The password values shown in the table cannot be altered, so retain a copy of this page for future reference. This will be the only reference made to password values in this instruction book.
PASSWORD TABLE
MENU SECURITY
SECURITY LEVEL
Primary Locked Secondary Locked Secure Locked
Primary Unlocked Secondary Locked Secure Locked
Primary Unlocked Secondary Unlocked Secure Locked
Primary Unlocked Secondary Unlocked Secure Unlocked
DISPLAYED VALUE
WHEN VIEWED
1
2
3
4
PASSWORD
VALUE TO ENTER
1110
1101
1011
111
Rev. 10/98 9 949-1239-3

NOTATION CONVENTIONS FOR THE MENUS

Because of the number of features available in this control, information is included that may not apply to your specific control. All usable features are included in this book, but may not be used in your process. To increase clarity the following conventions are used:
1. Certain features, Menu Items, and functions shown in this book may or may not appear on your control, depending on other Menu Item selections. At various places in the Menus there are notes identifying Menu Items that "control" or "direct" other menu items. If you are looking for a particular menu item and can't find it, check the menu item that is its "control" for proper setting.
2. The "#" symbol is used in two ways. It is used inside a group of characters to indicate which set point function (SP1 or SP2) is being affected. It is also used before a group of characters of a menu item to indicate that there may be more than one selection or value for that menu item.
3.
Features that apply only to Options will be printed in Italics.

THE HOME DISPLAY

The home display is the normal display while the control is operating. If no errors or functions are active, the HOME display will indicate the Process Variable (the temperature, pressure, flow, RH, etc., that is being measured) on the top display and the Set Variable (Set Point 1) on the bottom.
Items that can change the HOME display are the Auto/Manual function, the Prog function, the PctO function, and any error message. Description of these special displays follow.
If Auto/Manual Menu Item is On, the home display is changed. The upper display continues to show the Process Variable (PV), but the lower display changes to show the percentage of output in tenths of a percent to 99.9% (0.0 to 99.9), or 100 if 100%. The display digit to the right of the number shows a flashing letter o to indicate that the value displayed is no longer the SV, but percent output. The SP2 output is indicated by the use of an overline on the letter õ. Access to the SP2 value is done by the INDEX key. See Auto/Manual Operation on Page 13 for further information.
If Prog is turned On, the HOME display changes the SV display from SP1 to the Present Set Variable as calculated by the Ramp/Soak Programmer function. When Prog is On the StAt Menu Item changes the hHOME display firther. When StAt is selected OFF, the HOME display alternately indicates the normal HOME and the Ramp/Soak partial status in the Lower Display.
949-1239-3 10 Rev. 10/98
The partial status display sequences with the set value showing the ramp (S1rA) or soak (S1So) segment being processed at that moment. It will also show the Program output status if at Hold or OoFF.
When StAt is selected On, the HOME Display alternately indicates the normal HOME and the Ramp/Soak full status in both the upper and lower displays. The full status display sequences with the set value; Program run, Hold, or OoFF; and with the time remaining for the ramp S1rA or the soak S1So segments.See Programming and Operation for Ramp/Soak Feature below for more information.
If PctO (Secondary Menu) is turned On, the lower display changes to show the active percentage of output as required to maintain SP1. The display is similar to the Auto/Manual display above, except that the letter indicators do not flash, and the output is displayed in whole percentages of output, not in tenths of a percent. If the control has both SP1 and SP2, the lower display will alternate between the SP1 percent output and the SP2 percent output.

OPERATION OF SELF TUNE® FUNCTION

Self Tune® allows automatic selection of the necessary parameters to achieve best control operation from your 1600 Series control. If you are using the control output as a simple on-off function (S#Ot set for OnOF), none of the following will apply.

Theory of Operation

The Self Tune function calculates the Pb1, rES, and rtE parameters under the PID tunE selection as shown in the Secondary Menu . These values are determined by measuring the response of the process connected to the control. When Self Tune is started, the control temporarily acts as an on­off control. While in this mode the control measures the overshoot and undershoot of the process, and the period of the process (the time from peak value to the next peak value). These measurements are collected over a period that lasts three periods of overshoot and undershoot. The data collected over this time is then compared and calculated into final PID values. The calculations for the PID values are the same as used in the standard Ziegler - Nichols equations that have been recognized as standard for decades.
The only modification to the application of the Ziegler - Nichols equations is controlled by the dFAC menu item. This menu item controls the amount of rate (derivative) that is applied. A dFAC setting of 3 (factory default) or less allows for less damping. A dFAC setting of 4 allows for critical damping as
Rev. 10/98 11 949-1239-3
Loading...
+ 25 hidden pages