If you require assistance, please contact your local DV Systems Distributor or Authorized Service
center. You may contact the manufacturer directly as follows:
The Unit should be located in a dry, clean, cool, dust free,
and well ventilated area.
Allow a minimum of:
48” (1220mm) in front of and behind the Unit.
48” (1220mm) on either side of the Unit, and
60” (1524mm) above Unit.
The ambient temperature should be between 10°C and 40°C
(50°F and 104°F).
Ensure that the floor under the Unit is smooth, level and
capable of bearing the weight of the Compressor.
If installed in a compressor room, ensure that the room is
adequately ventilated.
Unit
Nameplate
Model No.
Fusible
Disconnect
Refer to
page 12 for
proper sizing
Serial No.
Unit voltage
[1524mm]
Pre-Filter
Refer to
page 8 for
proper sizing
(sold
separately)
Installation Kit
IK4050
Flex-Hose &
Vibration Isolators
(sold separately)
H40, H50, H50VSD-C
Jul ‘17
60”
48”
[1220mm]
48”
[1220mm]
48”
[1220mm]
- 2 -
Page 3
H40, H50, H50VSD-C
Jul ‘17
Quick Start (cont’d)
Shipping Cleats.
Your DV Systems ‘H Series’ Rotary Screw Compressor is shipped with several Shipping Cleats that
must be removed prior to the initial start-up.
The Cleats are located a) (1) under the Air End Mount and b) (1) under the Motor of the Unit. Please
remove these after locating the Unit but prior to running. Motor and Air End are orientated differently in
VSD and Belt Drive Units, Cleats can be located as shown below.
Air End Cleat Removal.
Locate the Air End Mount at the back of the Unit.
Locate the orange Shipping Cleat under the Air End Mount.
Remove the Bolt and Washers from the Cleat, and slide the Cleat out.
H50 VSD
Motor Cleat Removal.
The Motor is fastened to the Unit framework by means of (1) Shipping Cleat as indicated below. Access to the
Cleat is by means of both the front and rear of the Unit.
Remove the fasteners and slide the Cleat out of the assembly.
Motor Cleat from the Front of Unit.
Fasteners
Shipping Cleat
(1) Cleat at
Air End
H40/50 BD
Motor Cleat from the Rear of Unit.
Fasteners
Shipping Cleat
- 3 -
Page 4
Quick Start (cont’d)
Lubrication.
(Refer to Page 11)
Ensure the oil level
in the Air End is to
the level as shown
while at rest.
Check the oil after
the Unit has been at
rest for a minimum
of 5 minutes.
Rotation.
(Refer to Page 13)
Fixed Speed Units:
Units are equipped with Advanced Phase
Detection feature which prevents Units
from rotating in the reversed direction.
An ‘E:0090 Phase Sequence’ Error will
appear on the Controller Screen if the
phase sequence is incorrect. If this occurs,
simply switch the incoming leads ‘L1’ and
‘L3’ at the Control Panel
Note: Units with serial number 077771 and
earlier may be equipped with Anti-Rotation
Switches.
‘E:0902 Anti Rotation’ will appear on the
Controller Screen if the rotation is incorrect.
If this occurs, change ‘L1’ and ‘L3’ to the
Control Panel.
External Oil Level Indicator
showing proper oil level
when Unit is off
Correct
Oil Level
Oil Drain Tube
Variable Speed Units:
The Inverter to the Motor is pre-wired at the
factory.
Remove the Cover Plate from the Coupling
area and pay close attention to the arrow
indicating the correct rotation.
To verify the correct rotation, start the Unit
and turn off immediately using the
Emergency Stop Button.
If the rotation is not correct, simply change
two of the power leads to the Unit.
H40, H50, H50VSD-C
Jul ‘17
Oil Fill Port
Oil Drain Valve
Picture from Rear of Unit
Arrows Indicate
Correct Rotation
Picture from Front of Unit
- 4 -
Page 5
H40, H50, H50VSD-C
Jul ‘17
Quick Start (cont’d)
Unit Operation.
Shown below is the ‘CSC300’ Controller which regulates the operation of the Unit. It is used to start and stop the
Unit, and it provides information as to system pressure, temperature, etc.
Starting the Unit: Press the ‘Start’ Button.
Stopping the Unit: Press the ‘Stop’ Button
Note:
1. Do not stop the Unit using the ‘Emergency Stop’ Button unless there is a danger to the product or of
personnel injury.
2. Do not stop the Unit by use of a disconnect or breaker.
Using the Emergency Stop Button, disconnect, or breaker to stop the Unit will not
allow the Unit to go through an unloading sequence, and could result in damage to
the Motor, Starter, or other electrical components. Damage caused in this manner
is not covered by the manufacturers Warranty.
Emergency Stop.
Will quickly shut the
Unit off. Is only to be
used in an
emergency.
Enter, Up, Down & Escape.
Used in the programming and changing
of operating parameters of the Unit.
Start.
Starts the Unit.
Stop.
Causes the Unit to
enter ‘Idle’ mode
and then shut off.
Digital Readout.
Indicates Unit pressure,
temperature, etc.
- 5 -
Page 6
H40, H50, H50VSD-C
Jul ‘17
Safety Precautions
In order to operate the Compressor Unit safely and correctly, we have opted to use the following symbols to make
you aware of important points. These points relate to user safety and preventing equipment problems. Please pay
close attention to these sections.
Important safety Information.
A hazard that may cause
serious injury or loss of life.
Important information that
indicates how to prevent
damage to equipment, or how
to avoid a situation that may
cause minor injury.
Information that you should
pay special attention to.
The following hazards may occur during the normal use
of the equipment. Please read the following chart.
Area: Hazard: Safeguards:
What to look for: What may occur if precautions are not observed. How to avoid the hazard.
Tampering with the Unit while under full or partial
pressure may cause an explosion.
As the Unit starts and stops automatically, serious
injury may result from working on the Unit with the
power still in the on position.
As the Unit starts and stops automatically, do not
come into contact with moving parts.
Air compressed by the Unit is not suitable for
inhaling. It may contain vapours harmful to your
health.
Relieve all pressure from the Unit
before attempting any repair or
maintenance work.
Shut off all power to the Unit before
attempting any repair or maintenance
work.
Shut off all power to the Unit before
attempting any repair or maintenance
work.
Never directly inhale compressed air
produced by the Compressor.
The Compressor Pump, Motor, and Tubing
become hot when running. Touching these areas
may cause severe burns.
As the electrical components on the Unit are
General Purpose, there is a potential for explosion
should vapours be present in the area.
Never touch the Pump, Motor, or
Tubing during or immediately after
operation.
The Compressor must be a minimum
of 20 feet (6.1 meters) from any source
of potentially explosive vapours.
- 6 -
Page 7
H40, H50, H50VSD-C
Jul ‘17
Unpacking and Inspection
Each DV Systems Air Compressor is carefully tested and
inspected before shipment. Though every attempt is made to
ensure the safe and complete shipment of our product, freight
damage or misplacement of goods may occur.
Shipments of DV Systems products are the property of the
Consignee when the products leave our facility. DV Systems Inc.
is not responsible for any damages or shortages caused to the
product after it has left our shipping dock.
It is the responsibility of the receiver of the goods, either the Distributor or Customer, to ensure that the product
has been shipped in full, and has arrived in suitable condition. Damage to the product may not be visible at time
of off-loading, but may only become apparent upon unpacking or start-up.
Some areas to initially check are as follows:
a) Check for damage to the crating and/or packaging.
b) Check the exterior of the Cabinet for damage, either cosmetic or mechanical.
c) If there is mechanical damage, open the Cabinet to determine whether there is any internal
damage to the Unit.
Should there be damage to the product or shortages in shipment:
1) Stop any further unpacking or operation of the product.
2) Make note of the problem on the Freight Bill, should it concern a shortage or visible damage to the product.
3) Should the damage be noticed only after the product has been received, contact the transport company immediately to file a claim.
Depending on the problem, it may be wise to photograph the damage. Also, it may be wise to discuss with the carrier representative the time allotted to give notice of loss
or damage to the product; there may be guidelines which limit timeframes of same.
4) Do not attempt further unpacking or operation of the product. Also, do not discard any packing material used.
5) A Loss or Damage Claim must be submitted to the carrier and supported by the following documents:
- Copy of Freight Bill of Lading
- Copy of the Invoice and Estimate to repair, in case of damage
- Damage Report
- Copy of photos, if applicable
- 7 -
Page 8
H40, H50, H50VSD-C
Jul ‘17
Installation – Mechanical
The Importance of a Proper Installation
As with all Air Compressors, a proper installation is key to both a) long Compressor life and b) quality compressed
air. A Compressor Unit not installed correctly, and coupled with a poor maintenance program, can be plagued
with costly issues not covered by the manufacturer’s warranty.
The drawing below indicates the components required for a good installation.
As the ‘H40’ and H50’’ Screw Units do not include an Air Receiver, one must be located as shown. And though
additional filtration and a Refrigerated Dryer is shown, they may not be required in all instances, this is dependent
on the quality of compressed air required.
Additional dry Air Receiver down-stream
could assist for demand surges.
No.: Part Number: Description: Notes:
Piping between Unit and Tank not
to exceed 10 ft (3 m)
1 H40 / H50 40 / 50 HP Compressor Unit
2 H-9038
3 Advanced Air Pipe Systems 1-1/4” Diameter Pipe Contact Distributor for sizing
4 TA-9008-2 Air Receiver, 240 Gallon, 200 psi Safety Valve sized to application
5 DF294C & DF294A Canister & 1 Micron Element
6 ASD200 Refrigerated Air Dryer
7 DF294C & DF294 Canister & 0.01 Micron Element
8 ECOTRONxxOil Water Separator Use ‘50’ for 40HP, ‘90’ for 50HP
9 KK-9860 Zero-Loss Autodrain
Plant piping from the system as shown above should be sized based on the Unit CFM and the length of the piping
as follows. Using smaller piping will greatly restrict air flow and cause issues downstream of the Unit.
When moving the Air
Compressor, the forklift or hand
lift forks go under the Unit from
the directions as indicated.
Slots in the Unit Base are
provided for moving of the
Compressor.
Please be advised that care
must be taken when moving and
positioning the Units as they may
be top heavy.
Location of the Unit.
Items to consider when installing the Unit are as
follows:
The Unit should be located in a dry, clean, cool,
dust free, and well ventilated area. If possible, the
Compressor should be located in a separate
room or area, away from the general operations
of the shop.
Allow a minimum of 48” (1220mm) around and
60” (1524mm) above the Unit for easy access to
the various sides, this being for both the proper
ventilation of the Unit and ease of servicing.
Ensure that the floor under the Unit is smooth,
level and capable of bearing the weight of the
Compressor. The Compressor must sit level on
the floor.
If installed in a compressor room, ensure that the
room is adequately ventilated. (One Horsepower
produces approximately 2500 BTU/HR.) See
Page 10.
The ambient temperature should be between
10°C to 40°C (50°F and 104°F).
H40, H50, H50VSD-C
Jul ‘17
If installing the Unit on a mezzanine, ensure that
the structure can safely support the weight of the
Unit. As well, the sound level of the Unit may
increase due to the vibration transmitted through
the floor; use Vibration Pads to lessen this.
Many common Compressor problems can be
attributed to the location or installation of the Unit.
Make sure the Unit is in a suitable location, and
installed correctly.
The Compressor must not be operated in
a confined area where the heat from the
Unit cannot readily escape.
- 9 -
Page 10
H40, H50, H50VSD-C
Jul ‘17
Installation – Mechanical (cont’d)
Shown below are items which assist in making a good installation. These are both intake and exhaust ductwork,
helping the Unit to a) draw in clean outside air and b) exhaust the warmer air away from the Unit. The warmer air
may be used, with the inclusion of a damper in the exhaust ducting, to warm the interior of the building during the
colder months of the year.
Intake and Exhaust Ducting
- 10 -
Page 11
Lubrication
Initial Start-up.
Each Compressor Unit built is extensively tested at
the factory before shipment. The Unit is shipped with
the original oil in it as used for testing purposes.
Check the Oil level and for any Oil leaks on a daily
basis. This must be done when the Unit is off. Top up
the Oil level when necessary.
Use only DV Systems ‘DEV-3000’ Synthetic Oil. As
well, do not mix the ‘DEV-3000’ with any other
lubricant.
Subsequent Oil Changes.
Drain the existing oil from the Unit. (Please be
advised that the Unit cannot be drained fully of oil, as
some oil may remain in various components ie
Cooler, Tubing, etc.)
Fill the Oil Reservoir to the Metal Band on the
External Oil Level Gauge as shown below. Do not
under or overfill. See drawing below.
Use only DV Systems ‘DEV-3000’ Synthetic Oil,
available in both 1 US gallon (3.8 litre) jugs or 5 US
gallon (5 x 3.8 litre) pails. Any remaining oil may be
used for ‘top-ups’.
The ‘MK-H50’ Maintenance Kit includes:
(5) US Gallon (5 x 3.8 litre) Oil (‘DEV-3000’)
(2) Oil Filter (’DSC-624’)
(1) Air/Oil Separator Filter (’DSC-002051’)
(2) Air Filter (’DSC-002073’)
(2) Air Filter (‘DSC-002074’)
(1) In Line Filter (‘DSC-612)
This Kit should be used in the regular servicing of
your Unit.
Oil Drain Valve
Oil Drain Tube
H40, H50, H50VSD-C
Do not attempt to operate the Unit without
first checking whether there is oil in the Oil
Reservoir. Add oil as required. Serious
damage may result from use, however
limited, without oil.
Use of improper oil may negatively affect
Compressor performance or shorten Unit life.
Resulting problems are not covered by the
DV Systems Inc. Warranty.
Condensation (water) may form in the Oil
Reservoir with the oil. If this occurs, as the
water will tend to settle on the bottom of the
Reservoir, drain the water from the Reservoir
until you notice oil draining. Top up the
Reservoir with new oil using only the DV
Systems ‘DEV-3000’ oil.
Oil Fill Port
Correct
Oil Level
External Oil Level Indicator
showing proper oil level
when Unit is off
Jul ‘17
- 11 -
Page 12
H40, H50, H50VSD-C
Installation - Electrical
General Information.
It is your responsibility to ensure that the Compressor
Unit is electrically connected in a safe and correct
manner. Any electrical work should be carried out
by a competent Electrician, and be done in such a
way that it meets all applicable Codes and
Regulations.
Failure to correctly connect the
Fusible Disconnects.
Compressor to your building's electrical
services may result in serious personal
injury or damage to the equipment.
Install all covers and panels before
applying power to the Unit.
Failure to observe any of the above precautions could result in severe personal injury or death,
and/or damage to the Unit.
Ensure that all wiring, fusing, etc is done in a manner that meets with the appropriate codes and
regulations.
See the sales drawings and electrical schematic contained in this manual for information about Motor
nameplate amps, this is used to determine the appropriate Disconnect / Breaker and Wiring sizes.
Units equipped with Variable Speed Drives (VSDs) MUST use FAST-ACTING FUSES. Refer to the table
below for fuse sizes.
Fixed Speed Units:
Use TIME-DELAY type fuse.
VSD Units:
HP Voltage Fuse
Max. Allowable Fuse =
1.75 x Motor Full Load Amp
50
Ensure that a suitable Fused Disconnect or Breaker
(by others than DV Systems) is installed in the
electrical supply before the Compressor Unit.
Electrical wiring and conduit from the building supply,
through the Compressor Cabinet, and to the Switch
in the Compressor Control Panel, must be rated for
125°C (257°F) or higher.
Before servicing the Unit, ensure the
power source has been shut down and
locked off.
Read and understand the information
contained in this manual before installing
or operating the Unit.
Type
200
230
460
DFJ/
HSJ
575
Fuse
Amp
175
150
70
60
DV
Fuse
Part
No.
DV Disconnect
Kit (Disconnect +
Fuses)
F175 FD-175
F150 FD-150
F070 FD-070
F060 FD-060
Jul ‘17
- 12 -
Page 13
H40, H50, H50VSD-C
Jul ‘17
Installation – Electrical (cont’d)
Motors.
Wiring must be done in a manner that the full Motor
nameplate voltage +/- 10% is available at the Motor
terminals during start-up. Contact your local Distributor or
Service Centre if additional information is needed.
The Warranty that exists on the Electric Motor is that of the
original manufacturer. In the event of a Motor failure, contact
your DV Systems Distributor or Service Centre for the
location of the nearest authorized Motor Service Centre.
Use of an incorrect Motor for your
particular building service will result in
premature Motor failure, and is not
covered by the DV Systems or Motor
Manufacturers Warranty.
Motor / Air End Rotation.
It is critical that the Motor and Air End in the Rotary Screw Unit be turning in the correct manner as the Unit may
not equipped with an ‘Anti Rotation Switch’. Irreparable damage will be done if the Unit rotates in the
reverse direction. Motor / Air End rotation must be visually verified. The correct rotation is as indicated at the
Coupling area or Belt Housing of the Unit.
Fixed Speed Units: Variable Speed Units:
With Advanced Phase Detection feature, an
‘E:0090 Phase Sequence’ Error will appear
on the Controller Screen if the phase
sequence is incorrect. If this occurs, simply
switch the incoming leads ‘L1’ and ‘L3’ at
the Control Panel.
If ‘Anti Rotation’ Switch is present, an
‘E:0902 Anti Rotation’ Error will appear on
the Controller Screen if the rotation is
incorrect. If this occurs, simply change ‘L1’
and ‘L3’ at the Control Panel.
The Inverter to the Motor is pre-wired at the
factory.
Remove the Cover Plate from the Coupling
area and pay close attention to the arrow
indicating the correct rotation.
To verify the correct rotation, start the Unit
If the rotation is not correct, simply change
and turn off immediately using the
Emergency Stop Button.
two of the power leads to the Unit.
Coupling
Arrow Indicates
Correct Rotation
Picture from Rear of Unit
Picture from Front of Unit
- 13 -
Page 14
Installation – Electrical (cont’d)
Cooling Fan Rotation.
To ensure that the Unit operates at optimum
temperatures, a Cooling Fan is located on the top of
the Unit to draw warm air from the Cabinet
Enclosure. It is imperative that the Fan rotate in the
correct direction.
A label inside the Unit (as
shown at right) indicates the
proper Fan rotation.
If the Cooling Fan rotation is incorrect, switch the
incoming leads ‘L1’ and ‘L3’ to the Unit.
H40, H50, H50VSD-C
Jul ‘17
Wiring from
Cooling Fan
- 14 -
Page 15
H40, H50, H50VSD-C
Jul ‘17
AC Motor Maintenance Instructions
Cleaning.
To ensure that the Motor operates at optimum temperatures and provides years of trouble-free service,
periodically clean the outside of the Motor Housing of any build-up of dust, etc. Though it is not anticipated that, if
installed correctly and in a suitable environment, there should be much build-up on the Motor, keeping the
Housing clean will allow the Motor to operate more efficiently.
Lubrication.
This is a ball bearing motor. The bearings have been lubricated at the factory. Motors that do not have re-grease
capability are factory lubricated for the normal life of the bearings.
Some motor designs use different bearings on each motor end. Noted below is a chart outlining the interval at
which the bearings of Motor should be lubricated, this based on the Bearing Sizes. This must be part of a regular
maintenance schedule.
Motor
In HP
50 1,700 0.76 (20.1) 1.2 (4.0) 0.61 (17)
40 2,000 0.76 (20.1) 1.2 (4.0) 0.61 (17)
*Drive End would be the end that is connected to the driven device (air end).
**Opposite Drive End would be the end that is connected to the fan assembly.
The above chart is based on a standard environment in which the Motor is operating of 40°C (104°F). For other
conditions, please multiply the Hour Interval from the chart above by the factor as indicated below.
Severity of Duty Factor Environmental Conditions
Low Temperature 1.0 < 30°C (86°F)
Lubricant.
50 HP Motors are pre-greased with High temperature Dow Corning ‘DC44’ Medium Grease. You must use this
grease. Do not mix with other types of grease.
40 HP Motors are pre-greased, normally with Mobil Polyrex EM. Equivalent and compatible greases are Texaco
Polystar, Chevron SRI #2, and Shell Dolium BRB.
Drive End *
Interval
in Hours
Standard 1.0 40°C (104°F) , clean, little corrosion
Severe 0.5 50°C (122°F), moderate dirt, corrosion
Extreme 0.1 > 50°C (122°F), severe dirt, abrasive dust
Weight of Grease Volume of Grease Weight of Grease
Ounces (Grams) In3 (Teaspoon) Ounces (Grams)
Opposite Drive End
- 15 -
Page 16
Start-up Procedures
ying
Do not attempt to operate the Unit without first checking
whether there is oil in the Oil Reservoir. Add oil as required.
Serious damage may result from use, however limited, without
oil.
Unit Controls
Start Button
Allows the Unit to
start.
Emergency Stop Button
Do not use to normally stop the Unit. To be used to
stop the Unit in emergencies only. Normal use will
damage electrical controls, drive, and Shaft Seal.
Stop Button
Use this to
shut the Unit
off. Allows the
Unit to idle
and then stop
after several
seconds.
Initial Start-up
1) Open the RH Front Access Panel, and ensure
that there is sufficient Oil in the Oil Reservoir.
Refer to the ‘Lubrication’ section (Page 11) in this
manual for proper type and level of Oil.
2) Ensure the Shipping Cleats are removed as
indicated on Page 3.
3) Do a brief visual inspection of the Unit.
Do not place any materials in close proximity
to the Compressor. Placing materials against
or close to the Unit will limit the cooling
required, and could lead to premature failure.
Adjusting the settings of the Controller could adversely affect
the performance of the Unit. Only those individuals with
knowledge of the Unit should make any adjustments.
4) Place the Fused Disconnect / Breaker in the ‘On’
Position. Check that there is power to the
Controller.
5) Turn the Unit on momentarily by pressing the
‘Start’ Button on the ‘CSC300’ Controller.
Immediately press the ‘Emergency Stop’ Button
to stop the Unit. Ensure the Motor/Air End are
rotating in the correct direction. See ‘Motor/Air
End Rotation on Page 13.
If the rotation of the Air End is incorrect,
switch the phases ‘T1’ and ‘T3’ between the
Inverter and Motor. Refer to the
accompan
Also ensure the Cooling Fan is rotating correctly.
See Page 14.
6) Allow the Unit to operate for approximately 15
minutes. During this time, measure the amp draw
and voltage of the Unit at full load, and ensure
that these do not exceed the figures as noted on
the Unit.
7) Stop the Compressor by pressing the ‘Stop’
Button on the Units ‘CSC300’ Control Pad. Check
for any air or oil leaks.
Shut off all power to the Compressor Unit
before attempting any repair or maintenance.
wiring schematic.
H40, H50, H50VSD-C
Jul ‘17
- 16 -
Page 17
H40, H50, H50VSD-C
Jul ‘17
Preventative Maintenance Schedule
When servicing the Air Compressor, shut off all
power to the Unit, and drain it of air pressure.
Noted on the following pages are general Maintenance guidelines based on average working conditions. Should
the Unit be worked under extreme conditions, please contact your DV Systems Distributor for further input. As
well, all maintenance/service work must be carried out by a qualified Technician.
The typical operating temperature of the Unit, this dependent on ambient temperatures, is between 70°C and
85°C (158°F and 185°F).
If the operating temperature of the Unit is too low (less than 70°C (158°F)):
condensation will build up in the system and mix with the oil, causing damage to the internal components
in the Unit
Change the ambient conditions to increase the operating temperature.
If the operating temperature of the Unit is too high (above 85°C (185°F)):
the oil will oxidize and lose it’s properties, this causing internal damage to components as well
to combat this, the oil must be changed more often than noted below.
Note: For Compressor Units used in an environment where the ambient temperature is above
32°C (90°F), the components marked with a ‘ # ’ (on the ‘Maintenance Schedule’ on Page
17) must be changed more frequently.
Regular Maintenance Items.
DV Systems offers a Maintenance Kit for your Unit,
namely:
MK-H5040/50 HP ‘H Series’ Units
Each Kit consists of the following items, follow
Schedule Table on page 17 for the Maintenance
Schedule.
(5) US Gallon (5 x 3.8 litre) Oil (‘DEV-3000’)
(2) Oil Filter (’DSC-624’)
(1) Air/Oil Separator Filter (’DSC-002051’)
(2) Air Filter (’DSC-002073’)
(2) Air Filter (‘DSC-002074’)
(1) In Line Filter (‘DSC-612)
It is the responsibility of the Compressor owner
to ensure that a regular Maintenance Schedule
is followed.
Internal Access for Maintenance.
The internal components of the Unit are accessible
for servicing by way of removing both Front Panels
and the Bottom Rear Panel.
Front Access
Rear Access
- 17 -
Page 18
H40, H50, H50VSD-C
Jul ‘17
Preventative Maintenance Schedule (cont’d)
Maintenance Item: Daily
Compressor Room
Temperature Inspect Ambient Temperature should be between 10°C and 40°C (50°F and 104°F)
Cleanliness Inspect
Air Compressor Unit
Check Oil Level Inspect
Replace Oil # (See Note b) (1) X X X X X
Replace Oil Filter # (2) X X X X X X X X X X
Replace Air / Oil Separator # (3) X X X X X
Replace Air Intake Filter # (4) X X X X X X X X X X X X X X X X X X X X
Replace Coupling Spider* (5) X X X X X
Replace Belts** X X X X X
Replace Tank Relief Valve X X X
Replace Solenoid (6) X X X X X
Rebuild Intake Valve (7) X X X X X
Rebuild Thermo Valve (8) X X X
Rebuild Minimum Pressure Valve (9) X X X X X
Replace Scavenge Line Filter (10) X X X X X
Motor Bearing Lubrication Refer to Motor Manufacturer’s Recommendations on Page 14
*H series compressors with Variable Speed Drive
**H series fixed speed compressors
Notes: a) For Compressor Units used in an environment where the ambient temperature is above 32°C (90°F),
or b) where the Unit temperature runs regularly above 80°C (175°F), the components marked with a
‘#’ must be changed twice as often (example: in 4000 hours instead of 8000), and not as noted
above.
b) The DV Systems Oil used in the Rotary Screw Units is rated as an 8000 hour Oil. A complete Oil
change must be done every 8000 hours of Unit operation, or every 12 months, whichever occurs first.
Please refer to the Warranty on Page 28 for further information.
c) If a component, during a regular inspection, has proven to be defective or unfit for regular operation, it
must be repaired or replaced.
Parts and Repair Kits based on the above chart are as follows:
(1) Oil: DEV-3000
(2) Oil Filter DSC-624
(3) Air / Oil Separator: DSC-002051
(4) Air Intake Filter DSC-002073 + DSC-002074
(5) Coupling Spider DSC-001983
(6) Solenoid DSC-002052
(7) Intake Valve Repair Kit DSC-002075
(8) Thermo Valve Repair Kit: DSC-111-1
(9) Minimum Pressure Valve Kit: DSC-231
(10) Scavenge Line ‘In Line’ Filter DSC-612
Ambient Filter DSC-002069
As noted previously, the ‘MK-H50’ Maintenance Kit includes the following items:
(5) ‘DEV-3000’ US Gallon (5 x 3.8 litre) Oil
(2) ‘DSC-624’ Oil Filter
(1) ‘DSC-002051’ Air/Oil Separator Filter
(2) ‘DSC-002073’ Air Filter
(2) ‘DSC-002074’ Air Filter
(1) ‘DSC-612’ In Line Filter
Noted below are the most common Faults experienced.
‘CSC300’ Alarms.
There is an issue with the Unit, but it will still operate.
Code: Description: Most Common Items to Check:
A:0083 Motor phase imbalance Check supply voltage, fuses and cable
H40, H50, H50VSD-C
Jul ‘17
A:0119 Delivery Pressure High
A:0129 Delivery Temperature High Ambient temp high, Unit dirty, low oil level, no air flow through Unit, Temp Sensor defective
A:2816 Power Failure Occurred Press ‘Reset’ Button and restart Unit
A:4819 Routine Service Due Service Unit and reset Service Timer (Page ‘P16’ on Controller)
A:4809 Grease Service Due Service motor and reset Grease Service Timer (Page ‘P16’ on Controller)
Solenoid not working, Intake Valve Orifice clogged, Transducer dirty or faulty, pressure changed
incorrectly, alternate external pressure source
‘CSC300’ Shutdown Errors.
There is an issue with the Unit, and the Unit will not operate until the Fault has been addressed.
Code: Description: Most Common Items to Check:
E:0010 Emergency Emergency stop switch is pressed
E:0070 Fan Motor Alarm Check electrical connections
E:0082 Motor Overload Motor drawing high amps, low voltage, high pressure settings, low oil level
E:0083 Motor phase Imbalance Check motor connections in the control panel and motor connection box
E:0090 Phase Sequence Rotation of Motor wrong, sequence order of supply cable incorrect
E:00910093
E:0115 Delivery Pressure Sensor Fault Transducer not making good electrical contact, or defective
Phase L1/L2/L3 Fault Check supply voltage, fuses and cable
E:0119 Delivery Pressure High
E:0125 Delivery Temp Sensor Fault Temperature Sensor not making good electrical contact, or defective
E:0129 Delivery Temperature High Ambient temp high, Unit dirty, low oil level, no air flow through Unit, Temp Sensor defective
E:0902 Anti-Rotation Rotation of Main Motor wrong, Solenoid Valve not relieving pressure
E:1902 Inverter Fault Variable frequency drive tripped. Check VFD screen for more info.
Solenoid Not working, Intake Valve Orifice clogged, Transducer dirty or faulty, pressure
changed incorrectly, alternate external pressure source
- 19 -
Page 20
H40, H50, H50VSD-C
Jul ‘17
Variable Speed Drive
Your DV Systems ‘H Series’ Rotary Screw Compressor Unit may have been equipped with a ‘Variable Speed
Drive’, or ‘VSD’. A Compressor with an integral VSD can handle the constant loads for an extended period of time
(running at 100% duty cycle), but it can also run at slower speeds to accommodate lower air demands at other
times of the day.
Variable Speed Drives can reduce the overall energy costs associated with operating the Compressor Unit by
simply controlling the speed of the Motor and Air End to match consumption. As Rotary Screw Compressors
using the variable speed technology match the varying air demands and therefore have the ability to impact your
energy consumption, some energy providers have offered rebates when these Units are purchased. Consult your
local energy provider to determine if this applies.
Shown below is an ‘H Series’ Unit with a Variable Speed Drive.
VSD Interface
The VSD Controller Interface is shown at right. It
provides a means of operating, monitoring, and adjusting
the parameters of the Variable Speed Drive.
Please note that adjustments to the parameters of the
Variable Speed Drive should be made only by qualified
Technicians, or with the guidance of factory trained
personnel. Incorrect adjustments will affect the
performance of the Unit, and could result in damage to
the Drive.
‘CSC300’ Controller
Variable Speed Drive
- 20 -
Page 21
Variable Speed Drive (cont’d)
Operating Screen
Typical Drive Status Indicators on Screen
H40, H50, H50VSD-C
Jul ‘17
- 21 -
Page 22
H40, H50, H50VSD-C
Jul ‘17
Variable Speed Drive (cont’d)
Common VSD Fault Codes
Noted below are the most common fault codes that may appear on the VSD. For a more thorough list, please
check the manual which deals exclusively with the Vacon Variable Speed Drive and which accompanied the Unit.
Fault
Code
FaultPossible Causes:Corrective Measures:
1Over-current.Current too high in Motor Cable.Check loading.
Check Motor.
Check Cables.
2Over-voltage.The DC link voltage has exceeded the limits.
- too short a deceleration timeMake deceleration time longer.
- high voltage spikes in supplyCheck input voltage.
3Ground Fault.Insulation failure in Motor or wiring.Check Motor wires and Motor.
8System Fault.- component failureReset the fault and restart the Unit.
- faulty operation
13Frequency Converter underHeatsink temperature is below -10°C.
temperature.
14Frequency Converter overHeatsink temperature is over 90°C.Check the amount and flow of cooling air.
temperature.Overtemperature warning is issued when the heatsinkCheck the heatsink for dust.
temperature exceeds 85°C.Check the ambient temperature.
Ensure the switching frequency is not too high
in relation to ambient temperature and motor
load
15Motor stalled.Motor stall protection has tripped.Check Motor and load.
16Motor over-temperature.Motor is overloaded.Decrease motor load.
17Motor under-load.Motor under-load temperature has tripped.Check load.
22EEPRON checksum fault.Parameter save fault.Should the fault re-occur, contact the Distributor.
- faulty operation.
- component failure.
25Microprocessor watchdog- faulty operation.Reset the fault and restart the Unit.
fault.- component failure.Contact Distributor.
31IGBT temperatureIGBT Inverter Bridge overtemp protection has detected tooCheck loading.
(hardware).high a short term overload current.Check motor size.
Make identification run.
32Fan cooling.Cooling Fan of frequency converter does not start whenContact Distributor.
ON command is given.
50Analogue Input Iin < 4mA.Current at the analogue input is less than 4 mA.Check the current loop circuitry.
- control cable is broken or loose.
- signal source has failed.
52Keypad communicationThe data connection between the control keypad and theCheck keypad connection and possible keypad cable.
fault.frequency converter is broken.
54Slot fault.Defective option board or slot.Check board and slot.
Contact the nearest Vacon Distributor.
56PT100 board temperatureTemperature limit values set for the PT100 boardFind the cause of temperature rise.
fault.parameters have been exceeded.
- 22 -
Page 23
H40, H50, H50VSD-C
Jul ‘17
Air Filtration and Refrigerated Air Dryer
Your Unit may have been shipped with a Separator Filter and Refrigerated Air Dryer, these to assist in providing
good quality air to your point of use. Shown below is a typical installation showing the Compressor, Air Receiver,
Refrigerated Air Dryer, and Filters.
More detailed information concerning the Dryer Unit is included in the Dryer manual. The information contained in
this manual is a ‘quick reference’ only.
Dryer Controls.
On/Off
Button
Refrigerated
Air Dryer
Filters
Test/Programming
Buttons
Air Receiver
Compressor Unit
LED’s for
Compressor,
Drain, and Fan
Readout
- 23 -
Page 24
H40, H50, H50VSD-C
Air Filtration and Refrigerated Air Dryer (cont’d)
Motors. Typical Dryer Operation.
The Dryer will operate as follows:
Pressing the ‘On/Off’ Button for 3 seconds will start the Unit
There is a time delay of up to 2 minutes before the Refrigerant Compressor starts.
The Condenser Fan will start approx. 30 seconds there-after.
The Fan will not normally run at full speed, this indicated by a flashing LED
The readout will initially show ambient temperature indicated by 3 horizontal bars on the readout
Once the Fan and Compressor start, the dew point of the Unit will decrease to approx. 1°C, this indicated
by 1 or no horizontal bars.
Once at approx. 1°C, the Fan will stop, only to be called to run again once the temperature increases to
approx. 5°C
Pressing the ‘On/Off’ Button (when the Unit is operating) will run the Fan at full speed for several
seconds, after which the Unit will stop. (The LED will be on continually while the Fan runs at full speed.)
As well as showing the dew point, the readout may indicate several fault codes as suggested below.
Typical Fault Codes.
The readout will indicate a variety of ‘fault codes’, the most common being as follows:
Energy Saving Mode.
The Dew Point has been running at below -1°C for over 6
minutes.
The Unit will automatically restart operation at 6°C.
Temperature Probe Alarm.
The Temperature Probe is not working properly. It may
not be connected to the Board, or the Probe may be
defective.
Replace the Probe if necessary.
High Temperature Alarm.
The Dew Point has been running at above 12.5°C for
over 6 minutes. The Unit must be manually turned off and
on.
The fault could be caused by a dirty radiator, high
ambient temperature, a faulty Fan, or a faulty refrigerant
Compressor, to name only a few.
Jul ‘17
- 24 -
Page 25
H40, H50, H50VSD-C
Jul ‘17
Air Filtration and Refrigerated Air Dryer (cont’d)
Typical Separator Filter.
As previously noted, the Separator Filter should be located between the Compressor and the Refrigerated Dryer.
It contains a 1 micron Separator Element which protects the Dryer Unit by removing liquids and solid particles 1
microns and larger.
Filter Element Replacement.
To replace a dirty Filter Element:
Arrow Indicates
Direction of Air Flow
Alignment
Indicators:
triangles on
canister and
head will align &
prevent further
tightening when
canister is
secured to the
head
Shut the Compressor Unit off.
Bleed any compressed air from the system to ensure there is no pressure at the Filter.
Unscrew the Bowl from the assembly, exposing the dirty Filter Element.
Pull the Filter Element out of the Canister Head
Clean any debris from the inside of the Bowl
Remove the O-ring from the inside of the Canister Head
Install the new O-ring making sure it is properly seated
Place the new 1 micron Separator Filter Element into the Bowl (the filter is self-centring).
Screw the Canister with the Element inside it to the Canister Head until the indicators line up.
Gauge will return to green when Filter is once again under pressure.
Dual Indicating Gauge (DF002)
Arrow pointing to Green = Filter Element is Clean
Arrow pointing to Red = Filter Element is Dirty
The label shown above is included with a
replacement Filter Element, and should be
affixed to the outside of the Bowl for future
reference.
Bowl which Contains Filter Element (DF294A)
Float Drain (DF003)
- 25 -
Page 26
H40, H50, H50VSD-C
Jul ‘17
Trouble Shooting Guide
When servicing the Air Compressor, shut off all
power to the Unit, and drain it of air pressure.
The ‘Conditions’, ‘Causes’, and ‘Suggested Corrections’ as indicated below and on the following page(s) are only
a guideline for failures that we have found to be most common.
Though this information is provided in this booklet, it is assumed and expected that any personnel involved in the
servicing of an Air Compressor Unit is knowledgeable with this type of equipment. Do not attempt to service a
Compressor Unit unless you are familiar with it, as there are many issues that may come into play, the most
important being personal safety and the welfare of the Unit.
Should you have any questions, or require servicing to your Unit, please contact your local DV Systems
Distributor/Service Center.
Condition: Cause: Suggested Correction:
A. Unit won’t start.
No power to the Unit.
Loose and/or missing wires in the electrical
circuit.
Emergency Stop Button pressed in.
Motor Overload is tripped.
Compressor over-heated and stopped.
Compressor stopped by over-pressure.
Unit has ‘timed out’ / shut off because pressure
has not gone below cut-in pressure of 100 psi
(6.9 bar).
Power interruption.
Check that power at the disconnect or breaker is
on. Also, check any primary and secondary fuses.
Check that all wiring connections are tight.
With a wiring schematic, check that all wiring is
present and correct.
Release by twisting and pulling out.
Reset the overload.
Insufficient air flow to cool Unit.
Ambient temperature too high.
Heat Exchanger is dirty.
Faulty Temperature Switch.
Oil level is low.
Solenoid Valve faulty.
Seals on Intake Valve leaking.
Intake Valve Spring broken.
Pressure Transducer stopped Unit. Lower
maximum pressure setting.
Drop pressure below 100 psi (6.9 bar).
Reset the Unit.
- 26 -
Page 27
H40, H50, H50VSD-C
Trouble Shooting Guide (cont’d)
Condition: Cause: Suggested Correction:
B. No or Insufficient Air Flow. Air Filter is dirty.
Oil Separator is blocked.
Intake Valve is faulty.
Air leaks in the system.
Pressure limits are incorrectly set.
Blowdown Solenoid Valve is open.
Replace the Air Filter.
Replace the Oil Separator.
Repair or replace the Intake Valve.
Check the Unit and system for air leaks.
Adjust the pressure settings.
Check the wiring to the Solenoid and replace as
necessary.
Jul ‘17
C. Unit is overheating.
D. Compressor Starts Slowly. Intake Valve not functioning properly.
Ambient temperature is too high.
Blocked air circulation at the Unit.
Heat Exchanger is dirty.
Oil level is too low.
Using wrong type of compressor oil.
Thermo Valve is faulty.
Oil Filter is blocked.
Temperature Sensor is faulty.
Thermostat is faulty.
Pressure is too high.
Cabinet door/panel is open/off.
Ambient temperature is too low.
Minimum Pressure Valve leaking back to Air
End.
Minimum Pressure Valve setting is too high.
Using wrong type of oil.
Check cooling air circulation.
Check the air circulation in and around the Unit.
Clean the Heat Exchanger
Add oil as required.
Change to the factory recommended oil.
Check and repair as necessary.
Replace the Oil Filter.
Check the wiring to the Temperature sensor.
Replace the Sensor if necessary.
Replace the Thermostat.
Lower the pressure setting.
Secure the door/panel to the Unit.
Check Intake Valve operation. Repair or replace as
required.
Stop and restart once ambient increases.
Repair or replace the Minimum Pressure Valve.
Adjust Minimum Pressure Valve setting to 65 psi.
Change to factory recommended oil.
- 27 -
Page 28
H40, H50, H50VSD-C
Trouble Shooting Guide (cont’d)
Condition: Cause: Suggested Correction:
E. Intake Valve Leaks Oil
When Unit Stops.
F. Oil Consumption is Too
High.
G. Compressor Surges.
H. High Power Consumption. Improper air pressure settings.
I Fault Alarms.
Intake Valve Seal leaks.
Intake Valve stuck in open position.
Blowdown Solenoid not functioning.
Oil level is too high.
Oil Return Line (Scavenge Line) is blocked.
Oil Separator is saturated with oil.
Wrong type of oil used.
Unit is operating at too high a temperature.
Oil leak.
Unit load is light or excessive load/idle cycles.
Restriction in Heat Exchanger or Hoses.
Pressure Transducer setting is incorrect or
malfunctioning.
Blockage at Unit outlet.
Dryer is freezing up, not allowing air to pass
through.
Air Receiver is too small.
Blowdown Solenoid is not functioning.
The voltage in the building is too low or there is
a phase imbalance.
The Motor is failing.
Emergency Stop.
High Temperature.
Low Temperature.
High pressure.
Repair using an Intake Valve Repair Kit.
Repair or replace the Intake Valve.
Replace the Solenoid.
Reduce the oil level to the proper level.
Clean and/or replace the Scavenge In-Line Filter.
Replace the Oil Separator.
Change to factory recommended oil.
See ‘Section C’.
Repair oil leak.
Ensure Unit is set to operate at correct pressures,
and there is a minimum of 10 psi (0.7 bar)
differential. Also the Unit could be oversized for the
tank capacity.
Flush out or replace.
Set pressure as per instructions or replace.
Check for obstructions in outlet piping.
Check that the Dryer parameters are correct.
Increase dew point to 2.0 if required.
Use a minimum 240 Gallon Tank for 50 HP Units.
Reset the pressure as per factory defaults.
Inspect or replace as necessary.
Contact an Electrician to verify.
Have Motor inspected.
Ensure Emergency Stop Button is not pressed in.
See ‘Section C’.
Ambient temperature is too low. Increase to 10°C
(50°F).
Check the pressure settings, the Pressure
Transducer and the wiring to the Transducer.
Jul ‘17
- 28 -
Page 29
H40, H50, H50VSD-C
Jul ‘17
Limited Warranty : H Series Screw Compressors
The manufacturer warrants the product manufactured by it and sold to the original purchaser, when properly installed, operated, applied, and
maintained in accordance with procedures and recommendations outlined in the manufacturer’s instruction manuals, to be free of defects in material
and workmanship for a period of one (1) year from the date of installation, not to exceed eighteen (18) months from the date of manufacture, provided
such defect is discovered and brought to the manufacturers attention within the aforesaid warranty period, conditional upon the following:
1) Genuine ‘DEV-3000’ Lubricant and Parts are used for the full warranty period.
2) The Unit is maintained in accordance with the manufacturer’s instruction manual for the Unit, with the following minimum maintenance
requirements:
A) Complete Oil change every 8000 hours (not to exceed 12 months) from the date of initial start-up using ‘DEV-3000’ Lubricant. When
operating in adverse conditions, Oil changes must be done more frequently.
B) Oil Filter must be changed every 4000 hours (not to exceed 6 months) from the date of initial start-up using the appropriate DV Systems part.
When operating in adverse conditions, Oil Filter changes must be done more frequently.
C) Air Intake Filter must be changed every 2000 hours (not to exceed 6 months) from the initial date of start-up using the appropriate DV
Systems part. When operating in adverse conditions, Air Intake Filter changes must be done more frequently.
D) Air/Oil Separator Filter must be changed every 8000 hours (not to exceed 12 months) from the date of initial start-up using the appropriate
DV Systems part. When operating in adverse conditions, Air/Oil Separator changes must be done more frequently.
E) Appropriate and complete maintenance records must be kept by the End User. As well, the End User must retain copies of invoices
indicating the timely purchase of the DV Systems Compressor Oil and maintenance/service parts. All records and invoices must be kept for
the duration of the manufacturer’s warranty period.
3) Disclaimer:
A) The following items are considered normal wear items, and are warranted for a period of one (1) year from the date of installation, not to
exceed eighteen (18) months from the date of manufacture; the Shaft Seal on the Air End Drive Shaft, the Intake Valve Assembly (and its
components), and the Minimum Pressure Valve.
B) All electrical components are warranted for a period of one (1) year from the date of installation, not to exceed eighteen (18) months from the
date of manufacture.
An additional four (4) year extended Air End Warranty and a four (4) year extended Three Phase Baldor Motor Warranty are available on those
Units that:
A) have been registered with the manufacturer within thirty (30) days from the date of purchase, this done by returning the ‘DV Systems Rotary
Screw Compressor Start-Up Sheet’ and
B) have been maintained in accordance with the manufacturer’s instruction manual as noted in ‘2’ above.
The manufacturer will repair or replace any product or part determined to be defective by the manufacturer within the warranty period, provided such
defect occurred in normal service and is not the result of misapplication, misuse, abuse, neglect, incorrect maintenance, accident, or normal wear.
Normal maintenance items requiring routine replacement are not warranted. Please refer to the appropriate service bulletin to determine normal
maintenance requirements.
The warranty covers parts and labour for the warranty period (excluding the Three Phase Baldor Motors. Labour is not covered in the (4) year extended
Baldor Motor Warranty.) Either repair or replacement shall be at the sole option of the manufacturer. Any service performed on the product by anyone
other than the manufacturer must first be authorized by the manufacturer. Unauthorized service voids the warranty and any resulting charge or
subsequent claim will not be paid.
Products repaired or replaced under warranty shall be warranted for the unexpired portion of the warranty applying to the original product, based on the
original date of invoice as outlined above.
There is no other expressed warranty. Implied warranties including those of merchantability and fitness for a particular purpose are limited to one (1)
year from the date of invoice to the extent permitted by law and any and all implied warranties are excluded. This is the exclusive remedy. Liability for
consequential damages under any and all warranties are excluded to the extent exclusion is permitted by law.
This warranty gives you specific rights, and you may also have other rights within your jurisdiction.
This warranty does not cover:
All decisions by DV Systems Inc. with regard to this policy shall be final. DV Systems will not be responsible for any claimed defective materials
returned other than in accordance with this statement of policy or without our prior authorization.
andise that has become inoperative because of ordinary wear, misuse, neglect, accident, or improper and unauthorized repair or alteration.
1) Merch
2) Electric Motors manufactured and identified as the product of another company.
3) Compressor Units that have not been properly maintained in accordance with the recommended maintenance and lubrication change procedures
and/or that have been subject to inordinate use through being inadequately sized or poorly installed.
4) Compressor Units using other than the recommended lubricant.
5) Costs occasioned by the removal, replacement, or repair of merchandise (other than by DV Systems) without previous authorization from DV
Systems.
6) Expenses incurred in travel or lodging beyond a 100 kilometre (60 mile) distance from the nearest DV Systems Authorized Service Centre.
7) Expenses incurred in the return of equipment for inspection purposes to the manufacturers facility. All returns must be pre-authorized, returned
‘Freight Prepaid’, and accompanied by a ‘Return Material Authorization (RMA) Number’ (obtainable through DV Systems).
8) Products, parts, materials, components, or accessories manufactured by others or supplied in connection with the sale of the manufacturers
products.
9) Repair and transportation costs of merchandise determined not to be defective under the terms and conditions of this warranty.
10) The cost of rental or loaner equipment while the customer’s original equipment is being assessed, repaired, or replaced.
11) Consequential damages in the event of product failure.
DV Systems Inc. (Canada) DV Systems, Ltd. (USA)
490 Welham Road Tel: (705) 728-5657 128-B Talbert Road Tel: (704) 799-0046
Barrie, Ontario, L4N 8Z4, Canada Fax: (705) 728-4974 Mooresville, NC, 28117, USA Fax: (704) 799-0355
- 29 -
Page 30
34" 864mm
REAR ACCESS
PANEL
REMOVABLE
9/16" HOLES ON
4 STEEL FOOT PADS
7/31/17LT
H40-50 SCREW COMPRESSOR
SCALE
N.T.S
SALES-ENGINEERING DRAWING
specifications subject to change without notice.
DESCRIPTION OF DRAWING
DRAWING NO.
SHT NO
REV.
NAME OF PROJECT
DRAWN BY
CHECKED BY
DATE
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC. It is not to be used
or reproduced in any manner, nor submitted to other parties for examination without the prior
approval of DV SYSTEMS, INC. DV SYSTEMS, INC. is continually trying to improve its products,
H40 H50
MODEL
NO.
HPkW
PRESSURE
PSI
PRESSURE
bar
SCFM @
MAX.
PRESSURE
m3/min @
MAX.
PRESSURE
AIR END
RPM
NOMINAL
SOUND @
1 METRE
dBA
SYSTEM AMP
3-PHASE
WEIGHT
LBS
WEIGHT
kG
200V 230V 460V 575V
H404029.8
100 - 110 6.9 - 8.31654.673546
701079447381660753
125 - 145 8.6 - 10.01504.253085
H505037.3
100 - 110 6.9 - 8.32005.664562
7213111457461680762
125 - 145 8.6 - 10.01865.273960
INSTALLATION REQUIREMENTS
1. MAINTAIN 1.5M (4FT) DISTANCE FROM WALLS AND OTHER
OBJECTS FOR PURPOSE OF COOLING AND SERVICING
2. COMPRESSOR MUST BE LEVEL AND ANCHORED
TO SOLID LEVEL FLOOR
3. AMBIENT CONDITIONS:
10ºC (50ºF) MIN. 40ºC (104ºF) MAX.
SERVICE DOORS (2)
CONTROLER
E-STOP
WITH Y-DELTA START
AIR OUTLET
1-1/4" NPT
REMOVABLE
CSC300
FRONT & REAR
FORKLIFT ACCESS
60 1/2" 1537mm
33 5/8" 854mm
22 3/8" 568mm
1638mm64 1/2"
28" 711mm
POWER IN
1-1/2" CONDUIT
OPENING
COOLING AIR INLET
WITH AMBIENT FILTER
25" X16.5" FOR FRESH
AIR DUCTING
1096mm43 3/16"
902mm35 1/2"
64 1/2" 1638mm
26 7/8" 681mm
20 1/8" 510mm
COOLING AIR OUTLET
WITH MOTORIZED FAN
FOR EXHAUST DUCTING
664mm26 1/8"
376mm
759mm29 7/8"
14 13/16"
2 13/16" 71mm
Page 31
34" 864mm
REMOVABLE
SERVICE DOORS (2)
1-1/4" NPT
AIR OUTLET
VARIABLE SPEED DRIVE
E-STOP
CONTROLS WITH
CSC300
CONTROLLER
FRONT & REAR
FORKLIFT ACCESS
22 3/8" 568mm
1638mm64 1/2"
1537mm60 1/2"
854mm33 5/8"
28" 711mm
MODEL
NO.
HPkW
PRESSURE
PSI
PRESSURE
bar
SCFMm3/min
NOMINAL
SOUND @
1 METRE
SYSTEM AMP
3-PHASE
WEIGHT
LBS
WEIGHT
kG
200V230V460V575V
H50VSD50
37.3
100
6.9
200
5.66
6913111457461700
771
125
8.6
186
5.27
145
10.0
170
4.81
INSTALLATION REQUIREMENTS
1. MAINTAIN 1.25M (4FT) DISTANCE FROM WALLS AND OTHER
OBJECTS FOR PURPOSE OF COOLING AND SERVICING
2. COMPRESSOR MUST BE LEVEL AND ANCHORED
TO SOLID LEVEL FLOOR
3. AMBIENT CONDITIONS:
10ºC (50ºF) MIN. 40ºC (104ºF) MAX.
FUSE TABLE
VOLTAGE PHASE FUSE TYPEFUSE AMP
200
3JFAST-ACTING
(DFJ/HSJ)
175
230150
46070
57560
SALES-ENGINEERING DRAWING
N.T.S7/31/17LT
specifications subject to change without notice.
DESCRIPTION OF DRAWING
DRAWING NO.
SHT NO
REV.
NAME OF PROJECT
DRAWN BY
CHECKED BY
DATE
SCALE
H50 SCREW COMPRESSOR
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC. It is not to be used
or reproduced in any manner, nor submitted to other parties for examination without the prior
approval of DV SYSTEMS, INC. DV SYSTEMS, INC. is continually trying to improve its products,
H50VSD
COOLING AIR OUTLET
WITH MOTORIZED FAN
FOR EXHAUST DUCTING
14 13/16" 376mm
759mm29 7/8"
664mm26 1/8"
2 13/16" 71mm
REAR ACCESS
PANEL
REMOVABLE
9/16" HOLES ON
4 STEEL FOOT PADS
POWER IN
1-1/2" CONDUIT
OPENING
COOLING AIR INLET
WITH AMBIENT FILTER
25" X16.5" FOR FRESH
AIR DUCTING
26 7/8" 681mm
20 1/8" 510mm
43 3/16" 1096mm
902mm35 1/2"
64 1/2" 1638mm
Page 32
10
11
13
12
7
21
2
6
1
32
22
31
8
9
38
29
23
18
35
20
35
16
15
14
33
34
17
26
27
25
23
9
36
37
4
5
3
NOTES:
1. PULLEYS TIGHTENING TORQUE: 48 Nm
2. BELTS TENSION (NEW):
- 51.2 Hz FOR DSC-002398
- 47.9 Hz FOR DSC-002400 (H40-145)
- 56.7 Hz FOR DSC-002229
- 53.8 Hz FOR DSC-002400 (H50-145)
40
12
13
12
13
23
9
28
26
25
24
29
9
30
9
23
7
12
13
19
29
9
23
31
39
23
29
10
11
NO.
PART NUMBER
DESCRIPTION
QTY.
1
DSC-001980
H50 AIR END
1
2
DSC-001155
TAPER BUSHING FOR MOTOR PULLEY 1-7/8
1
3
DSC-002228
TAPER BUSHING FOR AIR END PULLEY 45 MM
1
4
DSC-002398
DSC-002229
DSC-002400
BELT H40 110 PSI (SPA1607 LD)
BELT H50 110 PSI (XPA1607 LD)
BELT H40-50 145 PSI (SPA632 LD)
4
5
PU-9255
PU-9272
PU-9268
AIR END PULLEY H40 110 PSI, H50 145 PSI
AIR END PULLEY H40 145 PSI
AIR END PULLEY H50 110 PSI
1
6
PU-9272
PU-9255
PU-9269
MOTOR PULLEY H40 110 PSI
MOTOR PULLEY H40 145 PSI
MOTOR PULLEY H50 110, 145 PSI
1
7
DSC-002010
H50 ISOLATOR
3
8
SS-10133
M12 X 45MM HHCS
2
9
SS-1506
1/2" MEDIUM LOCKWASHER
9
10
SS-25
3/8-16 X 1" HHCS GR2
6
11
SS-1525
3/8" FLAT WASHER
6
12
SS-657
3/8-16 HEX NUT
8
13
SS-1502
3/8" LOCKWASHER
8
14
SS-10105
M8 X 25MM HHCS
2
15
SS-1503
5/16" LOCKWASHER
2
16
SS-1524
5/16" FLAT WASHER
2
17
MO-9308
MO-9309
MO-9310
MO-9293
MO-9294
MO-9295
MOTOR 40HP, 200/60/3
MOTOR 40HP, 230/460 60/3
MOTOR 40HP, 575/60/3
MOTOR 50HP,200/60/3
MOTOR 50HP, 230-460/60/3
MOTOR 50HP, 575/60/3
1
18
DSC-001986
H50 INTAKE VALVE
1
19
DSC-002233
AIR END BRACKET H50
1
20
DSC-002062
H50 & H40 BD AIR INLET DUCTING
1
21
DSC-002234
BELT GUARD H50
1
22
DSC-002235
AIR END PLATE H50
1
23
DSC-294
M12-1.75 X 30 SHCS
9
24
SS-81
5/8-11 X 1-3/4 HEX BOLT GR.5
4
25
SS-1508
5/8" MEDIUM LOCKWASHER
8
26
SS-1529
5/8" FLAT WASHER
8
27
DSC-261
5/8"-11 X 1-1/2 HEX BOLT GR 5
4
28
SS-33
3/8-16" X 4" HHCS
1
29
SS-1527
1/2" FLAT WASHER
7
30
SS-50
1/2-13 x 1.5" HHCS
2
31
SS-659
1/2-13 HEX NUT
2
32
DSC-002236
AIR END BAR H50
2
33
DSC-002013
H50 AIR FILTER BRACKET
1
34
DSC-002064
H50 INLET FILTER HOUSING W/FILTER
1
35
DSC-002063
H50 INTAKE FILTER CLAMP
2
36
DSC-002074
H50 AIR INLET SAFETY ELEMENT
1
37
DSC-002073
H50 INLET FILTER ELEMENT
1
38
DSC-001991
H50 INTAKE VALVE O-RING
1
39
DSC-001937
1-1/2" 45º PLASTIC CONNECTOR
1
40
DSC-002189
ELBOW-SWIVEL 3/4"BSPPM - JIC12
1
DESCRIPTION OF DRAWING
DRAWING NO.
SHT NO
REV.
NAME OF PROJECT
DRAWN BY
CHECKED BY
DATE
SCALE
H40-50 BD SCREW COMPRESSOR
T.V.
9/03/13
N.T.S
DRIVE COMPONENTS
H40-50 BD
D1
9/03/13
NEW PROJECT
12-04
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC. It is not to be used
or reproduced in any manner, nor submitted to other parties for examination without the prior
approval of DV SYSTEMS, INC. DV SYSTEMS, INC. is continually trying to impreove its products,
specifications subject to change without notice.
MOTOR 50HP 200/60/3
MOTOR 50HP 230-460/60/3
MOTOR 50HP 575/60/3
1
3
DSC-001936
1-1/2" STRT PLACTIC CONNECTOR
1
4
DSC-001935
1-1/2" FLEX CONDUIT
21"
5
DSC-001937
1-1/2" 45º PLASTIC CONNECTOR
1
6
SS-10133
M12 X 45MM HHCS
2
7
SS-1506
1/2" MEDIUM LOCKWASHER
7
8
SS-13
5/16-18 X 7/8" HHCS
4
9
SS-1524
5/16" FLAT WASHER
6
10
SS-1503
5/16" LOCKWASHER
6
11
SS-725
5/16 HEX NUT
4
ITEM NO.
PART NUMBER
DESCRIPTION
QTY.
12
SS-25
3/8-16 X 1" HHCS GR2
6
13
SS-1525
3/8" FLAT WASHER
6
14
DSC-002010
H50 ISOLATOR
3
15
SS-1502
3/8" LOCKWASHER
6
16
SS-657
3/8-16 HEX NUT
6
17
DSC-001981
H50 MOTOR HUB
1
18
DSC-001983
H50 COUPLING SPIDER
1
19
DSC-001984
H50 COUPLING LOCKING RING
1
20
DSC-001982
H50 AIR END HUB
1
21
DSC-001985
H50 MOTOR - AIR END ADAPTER
1
ITEM NO.
PART NUMBER
DESCRIPTION
QTY.
22
SS-1508
5/8" MEDIUM LOCKWASHER
4
23
SS-81
5/8-11 X 1-3/4 HEX BOLT GR.5
4
24
DSC-244
M12 HC LOCKWASHER
4
25
DSC-294
M12-1.75 X 30 SHCS
13
26
DSC-002012
ADAPTER GUARD
2
27
SS-1
1/4-20 X 0.5" HHCS
4
28
DSC-002011
H50 AIR END BRACKET
1
29
SS-1527
1/2" FLAT WASHER
9
30
DSC-001980
H50 AIR END
1
31
DSC-001991
H50 INTAKE VALVE O-RING
1
32
DSC-001986
H50 INTAKE VALVE
1
33
DSC-002063
H50 INTAKE FILTER CLAMP
2
34
DSC-002062
H50 AIR INLET DUCTING
1
35
DSC-002064
H50 INLET FILTER HOUSING W/FILTER
1
36
SS-10105
M8 X 25MM HHCS
2
37
DSC-002013
H50 AIR FILTER BRACKET
1
REV.
DATE
REVISION DESCRIPTION
PCN NO.
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC. It is not to be used
or reproduced in any manner, nor submitted to other parties for examination without the prior
approval of DV SYSTEMS, INC. DV SYSTEMS, INC. is continually trying to improve its products,
specifications subject to change without notice.
DESCRIPTION OF DRAWING
DRAWING NO.
SHT NO
REV.
NAME OF PROJECT
DRAWN BY
CHECKED BY
DATE
SCALE
H50VSD SCREW COMPRESSOR
LT
2/14/12
N.T.S
DRIVE COMPONENTS
H50VSD
D1
A
12/16/13
DSC-002077,78 REMOVED, 001935,36 ADDED
---
A
Page 34
14
8
9
13
M3
12
11*
29*
M4
28*
24
26
22
18
19
18
20
21
16
23
17
30
6
31
32
33
27
35
7
4
5
6
34
2
3
M2
M1
11
15
27
11
16
11
10
25
17
1
DSC-002209
MAINTENANCE KITS
M NO.
PART NO.
KIT DESCRIPTION
M1
DSC-002075
H50 INTAKE VALVE REPAIR KIT
M2
DSC-002076
H50 AIR END SHAFT SEAL KIT
M3
DSC-111-1
THERMO VALVE REPAIR KIT
M4
DSC-231
MINIMUM PRESSURE VALVE REPAIR KIT
---
MK-H50
4000 HR MAINTENANCE KIT
ITEM NO.
PART NUMBER
DESCRIPTION
QTY.
1
DSC-001980
AIR END H-SERIES
1
2
DSC-001986
INTAKE VALVE H-SERIES
1
3
DSC-002052
SOLENOID GH-SERIES N.C.
1
4
DSC-376
PNEUMATIC ELBOW 1/8"BSPP X 8MM
1
5
INTAKE VALVE CNTRL BLOCK GH-SERIES
1
6
DSC-381
PNEUMATIC TUBE BLACK 8MM OD
2
7
DSC-110
PNEUMATIC TEE 1/4"BSPP X 8MM
1
8
DSC-712
THERMO VALVE CAP
1
9
DSC-711
THERMO VALVE CAP O-RING
1
10
DSC-120
BONDED WASHER 3/4" BSPP
3
11
DSC-427
BONDED WASHER 3/8"
4
12
DSC-279
ADAPTER 3/8"BSPPM - 3/8"NPTF
1
13
DSC-436
ADAPTER 3/8"NPTM X 1/2"NPTF
1
14
TIA-6165
SAFETY VALVE 1/2"NPT 165PSI
1
15
DSC-002881
MANIFOLD ASSEMBLY G-SERIES II
1
16
DSC-278
ADAPTER 3/8"BSPM X 1/4"BSPF
2
17
DSC-382
PNEUMATIC TUBE NATURAL 6MM OD
1
18
DSC-175
PNEUMATIC STRAIGHT 1/8" X 6MM
2
19
DSC-001358
CHECK VALVE 1/8"NPT(F)
1
20
DSC-612
INLINE FILTER
1
21
DSC-002904
SOLENOID CABLE ASSEMBLY HJK
1
22
DSC-001237
PRESSURE TRANSDUCER CSC200300
1
23
DSC-377
PNEUMATIC ELBOW 1/4"BSPP X 8MM
1
24
DSC-158
PNEUMATIC ELBOW 1/4"BSPP X 6MM
1
25
DSC-121
ADAPTER R3/4" - JIC12
3
ITEM NO.
PART NUMBER
DESCRIPTION
QTY.
26
DSC-002958
PLUG 1/4"BSPP
1
27
DSC-001217
BONDED WASHER 1/4" BSPP
2
28
DSC-102*
ANTI-ROTATION PRESSURE SWITCH
1
29
DSC-426*
ADAPTER 3/8"BSPM - 1/4"NPTF
1
30
DSC-185
PNEUMATIC ELBOW 1/8"BSPP X 6MM
1
31
DSC-677
ORIFICE 1MM
1
32
DSC-001667
COPPER SEALING RING 1/8"BSPP
3
33
DSC-002059
BONDED WASHER M14
1
34
DSC-002066
THERMAL WELL H50
1
35
DSC-002907
TEMPERATURE SENSOR CSC200300 HJKN
1
REV.
DATE
REVISION DESCRIPTION
PCN NO.
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC. It is not to be used or reproduced
in any manner, nor submitted to other parties for examination without the prior approval of DV SYSTEMS, INC.
DESCRIPTION OF DRAWING
DRAWING NO.
SHT NO
REV.
NAME OF PROJECT
DRAWN BY
CHECKED BY
DATE
SCALE
H40-50 SCREW COMPRESSOR
LT
3/01/17
N.T.S
PNEUMATIC COMPONENTS
H40-50 BD
H50VSD
D3
B
A
6/26/14
BD-VSD COMBINED, ANTY-ROTATION PARTS FOR REF.
14-15
3/01/17
B
17-04
DSC-002881 MANIFOLD & PARTS SN.>085501
Page 35
1
2
54
53
13
12
15
16
10
9
10
9
21
20
20
19
18
22
11
29
30
25
24
23
4
7
6
M1
26
27
28
33
34
8
5
36
35
4
37
38
10
9
31
10
9
17
16
15
9
40
10
42
41
24
25
43
49
48
46
45
44
57
53
56
553
52
51
55
14
32
39
50
M3
M2
47
3
VSD
ORIENTAT'N
BELT
ORIENTAT'N
MAINTENANCE KITS
M1
DSC-002075
H50 INTAKE VALVE REPAIR KIT
M2
DSC-111-1
THERMO VALVE REPAIR KIT
M3
DSC-231
MINIMUM PRESSURE VALVE REPAIR KIT
---
MK-H50
4000 HR MAINTENANCE KIT
NO.
PART NUMBER
DESCRIPTION
QTY.
1
DSC-001980
AIR END H-SERIES
1
2
DSC-002065
H50 AIR END OUTLET GASKET
1
NO.
PART NUMBER
DESCRIPTION
QTY.
3
DSC-002189
ELBOW-SWIVEL 3/4"BSPPM - JIC12
1
4
DSC-002063
H50 INTAKE FILTER CLAMP
2
5
DSC-002062
H50 AIR INLET DUCTING
1
6
DSC-002074
H50 AIR INLET SAFETY ELEMENT
1
7
DSC-002073
H50 INLET FILTER ELEMENT
1
8
DSC-002064
H50 INLET FILTER HOUSING W/FILTER
1
9
DSC-121
ADAPTER R3/4" - JIC12
5
10
DSC-120
BONDED WASHER 3/4" BSPP
6
11
DSC-155
HEAT EXCHANGER
1
12
DSC-002046
OIL RETURN HOSE TO MANIFOLD
1
13
DSC-001346
OIL OUTLET HOSE TO HEAT EXCHANGER
1
14
DSC-002047
AIR OUTLET HOSE TO HEAT EXCHANGER
1
15
DSC-123
ADAPTER 1-1/4"BSPP(M) - JIC 16
2
16
DSC-122
BONDED WASHER 1-1/4"BSPP
2
17
DSC-002724
O-RING C-SERIES THERMOVALVE INLET
1
18
SS-725
5/16" HEX NUT
6
19
SS-1503
5/16" LOCKWASHER
6
20
SS-1524
5/16" FLAT WASHER
12
21
SS-13
5/16-18 X 7/8 HHCS
6
22
DSC-002015
H50 FAN PLATE
1
23
DSC-001987
H50 FAN ASSEMBLY 575V
1
24
SS-657
3/8-16 HEX NUT
7
25
SS-1502
3/8" LOCKWASHER
7
26
DSC-597
1/4-20 X 0.75" HHCS
8
27
SS-1505
1/4" MEDIUM LOCKWASHER
8
28
SS-02001
1/4-20 THREADED INSERT
8
29
DSC-002067
EXHAUST PIPE 24", 1-1/4"NPT TAP ENDS
1
30
SS-23
3/8-16 X 3/4 HHCS B/M
4
31
DSC-002881
MANIFOLD ASSEMBLY G-SERIES II
1
32
DSC-624
OIL FILTER
1
33
DSC-002051
H50 AIR/OIL SEPARATOR FILTER
1
34
DSC-002068
H50 SEPARATOR TUBE
1
35
DSC-288
MANIFOLD ASSEMBLY O-RING
1
36
DSC-628
MANIFOLD SCAVENGE LINE O-RING
1
37
SS-01926
3/8-16 X 1-3/4 SHCS
4
38
DSC-001667
COPPER SEALING RING 1/8"BSPP
2
39
DSC-002882
O-RING G-SERIES A/O INLET
1
40
DSC-618
OIL FILL PLUG 3/4" BSPP
1
41
DSC-001907
OIL SIGHT GLASS 3/4" BSPP
1
42
DSC-002259
COPPER WASHER 3/4"BSPP WD
1
43
SS-1525
3/8" FLAT WASHER
3
44
R-8504
PE TUBING 1/2" OD
1
45
DD-00091
3/8"NPT X 1/2"DIA PNEU. FITTING
1
46
DSC-002828
BALL VALVE 3/8" NPTF X 3/8" NPTF
1
47
DSC-163
STREET ELBOW 3/8" NPT
1
48
SS-2108
NIPPLE 3/8"NPT X 2" LG
1
49
DSC-001330
VIBRATION ISOLATOR
3
50
DSC-001393-2
AIR/OIL RECEIVER G-SERIES II
1
51
DSC-002918
FLEXI-HOSE H40-50 FIXED SPEED
1
52
DSC-002898
FLEXI-HOSE H50VSD
1
53
DSC-244
M12 HC LOCKWASHER
8
54
DSC-245
M12 X 40MM SHCS
4
55
DSC-002048 (VSD)
DSC-002278 (BELT-DR)
OIL RETURN HOSE TO AIR END
1
56
DSC-294
M12-1.75 X 30 SHCS
8
57
DSC-001146
G20-30 FLEXI HOSE GASKET
1
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC. It is not to be used
or reproduced in any manner, nor submitted to other parties for examination without the prior
approval of DV SYSTEMS, INC. DV SYSTEMS, INC. is continually trying to improve its products,
specifications subject to change without notice.
DESCRIPTION OF DRAWING
DRAWING NO.
SHT NO
REV.
NAME OF PROJECT
DRAWN BY
CHECKED BY
DATE
SCALE
H50 VSD SCREW COMPRESSOR
LT
1/31/12
N.T.S
SYSTEM COMPONENTS
H40-50 BD
H50VSD
D2
D
MANIFOLD O-RINGS
3/10/17
---
REV.
DSC-001393-2, 002898, 002918, SN.>085501
REVISION DESCRIPTION
C
A
DATE
17-04
DSC-002940 ADDED
6/18/14
7/21/15
PCN NO.
B
D
16-20
OIL DRAIN ASSEMBLY PARTS
15-05
10/27/16
Page 36
M1
H-SERIES FIXED SPEED COMPRESSOR WITH
CSC300 (200V & 230V)
ELECTRICAL SCHEMATICS
WITH MICROPROCESSOR
CSC300H-200/230
EH05/14/15N.T.S.
A2
A1
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC.
It is not to be used or reproduced in any manner, nor submitted to other parties
for examination without the prior approval of DV SYSTEMS, INC.
DV SYSTEMS, INC. is continuously trying to improve its products, specifications
subject to change without notice.
24 VAC
+
CSC300
20
0
X13
XO9
RELAY OUTPUTS
11
S
-
3 PHASE
X12
L1 L2 L3
a
CT1
X11
b
c
CT2
X10
a
C
CR1R2R3
XO8
RELAY OUTPUTS
CR4R5R6
XO7
PROGRAMMABLE
CR7 R8C
RELAY OUTPUTS
611
M2
A2
A1
345
M3
A2
A1
M3
AUX
M1
AUX
7
8
9
10
M4
A2
A1
12
L1 L2 L3
E
(DSC-002361)
STARTER CONTACTOR 1
L1L2L3
T2T1T3
STARTER CONTACTOR 3
L3L2
T3T2L1T1
STARTER CONTACTOR 2
T6
T5
MOTOR
T1T3
T4
T2
T1T2T3
L1L2L3
POWER CIRCUIT SCHEMATIC
L3
L2
L1
FUSIBLE DISCONNECT
BY CUSTOMER
1.75 X FULL LOAD MOTOR AMP MAX
GND
CT1
1
CT1
2
CT2
1
CT2
2
3
CT1
CT2
TK
TK
THERMALY PROTECTED
STARTER CONTACTOR 4
2
1
*WITHIN 20.4V AND 27.6V*
F4F5
F6
+24VAC
F1F2F3
4
5
200
230
40
40
50
50
4
3
7
7
7
ATDR, CC TIME DELAY ATQR, CC
5MM TIME DELAY
F1 F2 F3 F4 F5 F6 NA
VOLTAGE HP
FUSE TABLE
NA
NA
NA
NA
WARNING: USE THE SAME FUSE TYPE & RATING
MOTORMOTOR
FAN
L1L2L3
T1T2T3
E- EMERGENCY STOP
CT1 - CURRENT SENSOR #1
CT2 - CURRENT SENSOR #2
F1 - FAN FUSE #1
F2 - FAN FUSE #2
F3 - FAN FUSE #3
F4/F5 - TRANSFORMER PRI. FUSE
F6 - TRANSFORMER SEC. FUSE
M1 - STARTER COIL 1
M2 - STARTER COIL 2
M3 - STARTER COIL 3
M4 - FAN STARTER COIL
P- PRESSURE TRANSDUCER
S- SOLONOID N.C.
T- TEMPERATURE SENSOR
RSS - REMOTE START/STOP, N/O
(FIELD OPTION: INSTALL RSS TO
#21 AND #13 TERMINAL BLOCK.
INSTALL WIRE FROM #21 TO DI5.
ON P18 CHANGE P18.08 FROM
'OFF' TO 'DI REMOTE START'.
ON P10 CHANGE P10.12 FROM
'KEYPAD' TO 'EQUIPMENT DI'.)
345
U1 U2W2V2V1W1
44
444
7
T
P
C
13 17 1614
+
BLK
WHT
-
RSS
21
15
ANA-O
ANA-G
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
C-AN1
AN1
AN2
AN3
C-AN2
C-AN3
X01
DIGITAL INPUTS
X02
ANALOGUE INPUTS
X03
E
1313
13
13
TK
22
XO6
L1L2
XO5
L1L2
BLK TO #20 TERMINAL
MASTER/SLAVE
WHT TO #19 TERMINAL
MASTER/SLAVE
(FOR SEQUENCING)
1
M2
M3
M1
8
7
6
3
4
9
23FAN FUSES F1, F2, F3
PRIMARY FUSES F4, F5
4
TRANSFORMER
5
SECONDARY FUSES F3
6
TERMINAL BLOCK
7
MOTOR STARTERS
8
CURRENT SENSOR
9
FAN STARTER
2
1 JUNCTION BLOCK
5
W1 - FAN LEAD (BLK)
W2 - FAN LEAD (ORG)
V1 - FAN LEAD (BLU)
V2 - FAN LEAD (GRY)
U1 - FAN LEAD (BRW)
U2 - FAN LEAD (RD)
TK - FAN THERMAL CONT. (WHT)
PANEL SCHEMATIC
3
22
Page 37
M1
H-SERIES FIXED SPEED COMPRESSOR WITH
CSC300 (460V & 575V)
ELECTRICAL SCHEMATICS
WITH MICROPROCESSOR
CSC300H-460/575
EH05/14/15N.T.S.
STARTER CONTACTOR 1
L1L2L3
T2T1T3
STARTER CONTACTOR 3
L3L2
T3T2L1T1
STARTER CONTACTOR 2
T6
T5
MOTOR
T1T3
T4
T2
T1T2T3
L1L2L3
POWER CIRCUIT SCHEMATIC
A2
A1
L3
L2
L1
FUSIBLE DISCONNECT
BY CUSTOMER
1.75 X FULL LOAD MOTOR AMP MAX
GND
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC.
It is not to be used or reproduced in any manner, nor submitted to other parties
for examination without the prior approval of DV SYSTEMS, INC.
DV SYSTEMS, INC. is continuously trying to improve its products, specifications
subject to change without notice.
24 VAC
T
P
+
C
CSC300
0
0
13 17 1614
+
BLK
WHT
-
RSS
21
X13
XO9
RELAY OUTPUTS
11
S
15
-
3 PHASE
X12
L1 L2 L3
a
CT1
X11
b
c
CT2
X10
a
C
CR1R2R3
XO8
RELAY OUTPUTS
CR4R5R6
XO7
PROGRAMMABLE
CR7 R8C
RELAY OUTPUTS
ANA-O
ANA-G
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
C-AN1
AN1
AN2
AN3
C-AN2
C-AN3
611
X01
DIGITAL INPUTS
X02
ANALOGUE INPUTS
X03
M2
A2
A1
E
1313
13
13
3 4 5
CT1
1
CT1
2
CT2
1
CT2
2
3
CT1
CT2
M3
A2
A1
M3
AUX
M1
AUX
7
8
9
10
E- EMERGENCY STOP
CT1 - CURRENT SENSOR #1
CT2 - CURRENT SENSOR #2
F1 - FAN FUSE #1
F2 - FAN FUSE #2
F3 - FAN FUSE #3
F4/F5 - TRANSFORMER PRI. FUSE
F6 - TRANSFORMER SEC. FUSE
M1 - STARTER COIL 1
M2 - STARTER COIL 2
M3 - STARTER COIL 3
M4 - FAN STARTER COIL
P- PRESSURE TRANSDUCER
S- SOLONOID N.C.
T- TEMPERATURE SENSOR
RSS - REMOTE START/STOP, N/O
(FIELD OPTION: INSTALL RSS TO
#21 AND #13 TERMINAL BLOCK.
INSTALL WIRE FROM #21 TO DI5.
ON P18 CHANGE P18.08 FROM
'OFF' TO 'DI REMOTE START'.
ON P10 CHANGE P10.12 FROM
'KEYPAD' TO 'EQUIPMENT DI'.)
X07 - R7 AND R8 FOR ROGRAMMABLE
1
M2
M3
M1
8
7
6
3
4
9
23FAN FUSES F1, F2, F3
PRIMARY FUSES F4, F5
4
TRANSFORMER
5
SECONDARY FUSES F3
6
TERMINAL BLOCK
7
MOTOR STARTERS
8
CURRENT SENSOR
9
FAN STARTER
U1V1W1
U2
V2
W2
TK
TK
THERMALY PROTECTED
M4
A2
A1
12
TK
22
STARTER CONTACTOR 4
L1 L2 L3
F
(DSC-002361)
2
1
*WITHIN 20.4V AND 27.6V*
F4F5
F6
+24VAC
2
F1F2F3
4
5
345
460
575
2.5
40
40
50
50
2
2.522.521
7
7
5
7
ATDR, CC TIME DELAY ATQR, CC
5MM TIME DELAY
F1 F2 F3 F4 F5 F6 NA
VOLTAGE HP
FUSE TABLE
NA
NA
NA
NA
WARNING: USE THE SAME FUSE TYPE & RATING
2
1 JUNCTION BLOCK
5
MOTORMOTOR
FAN
L1L2L3
T1T2T3
W1 - FAN LEAD (BLK)
W2 - FAN LEAD (ORG)
V1 - FAN LEAD (BLU)
V2 - FAN LEAD (GRY)
U1 - FAN LEAD (BRW)
U2 - FAN LEAD (RD)
TK - FAN THERMAL CONT. (WHT)
PANEL SCHEMATIC
XO6
L1L2
XO5
L1L2
BLK TO #20 TERMINAL
MASTER/SLAVE
WHT TO #19 TERMINAL
MASTER/SLAVE
(FOR SEQUENCING)
1
11
Page 38
H50 200V & 230V SCREW COMPRESSOR
WITH VARIABLE SPEED CONTROLS
ELECTRICAL SCHEMATICS
CSC300 & NXS INVERTER
CSC300-H50-200/230
E.HN.T.S.
TK - FAN THERMAL CONTACT
RSS - REMOTE START/STOP
(FIELD OPTION:
INSTALL RSS TO #18 AND #10
TERMINAL BLOCK. INSTALL WIRE
FROM #18 TO DI5. ON P18 CHANGE
P18.08 FROM 'OFF' TO 'DI REMOTE
START'. ON P10 CHANGE
P10.12 FROM 'KEYPAD' TO
'EQUIPMENT DI')
X07 - R7 AND R8 FOR PROGRAMMABLE
RELAY OUPUT FUNCTION
1
1
2
TRANSFORMER
FAN FUSES F1 / F2 / F3
3
PRIMARY FUSE F4
4
PRIMARY FUSE F5
5 SECONDARY FUSE F6
PANEL SCHEMATIC
MOTOR
T3T2
T1
T1T2T3
L1L2L3
POWER CIRCUIT SCHEMATIC
L1
BY CUSTOMER
FUSIBLE DISCONNECT
6 TERMINAL BLOCK
6
L2 L3
GND
CONTROL
PANEL
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC.
It is not to be used or reproduced in any manner, nor submitted to other parties
for examination without the prior approval of DV SYSTEMS, INC.
DV SYSTEMS, INC. is continuously trying to improve its products, specifications
subject to change without notice.
123456789
10
11 12 13 14 15 16 17 18 19
20
24 25 26
NXS INVERTER
CONTROL CONNECTION
BOARD OPT-A1
BOARD OPT-A2
3
4
6
5
8
10
NXS INVERTER
POWER CONNECTION
T1
T2
T3
L1L2L3
M
(FAN STARTER)
USE SEMI-CONDUCTOR TYPE
(FAST ACTING) FUSES WITH INVERTERS.
REFER TO H50 SALES DRAWING FOR FUSE
RATINGS
5
3
MAIN
8
7 GROUND TERMINAL BLOCK
05/06/15
24 VAC
T
P
+
C
CSC300
2
20
10 15 1412
+
BLK
WHT
-
RSS
X13
XO9
RELAY OUTPUTS
13
-
3 PHASE
X12
L1 L2 L3
a
CT1
X11
b
c
CT2
X10
a
C
CR1R2R3
XO8
RELAY OUTPUTS
CR4R5R6
XO7
PROGRAMMABLE
RELAY OUTPUTS
ANA-O
ANA-G
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
C-AN1
AN1
AN2
AN3
C-AN2
C-AN3
34
65
X01
DIGITAL INPUTS
X02
ANALOGUE INPUTS
X03
+24VAC
1
0
9
S
M
A2
A1
911
CR7 R8C
8
21 22 23
E
18
230
FUSE SIZE (AMPS)
F1 F2 F3 F4
FUSE TABLE
WARNING: USE THE SAME FUSE TYPE & RATING
ATDR, CC TIME DELAY
5MM TIME DELAY
TK
7
VOLTAGE
1
W1 - FAN LEAD (BLACK)
W2 - FAN LEAD (ORANGE)
V1 - FAN LEAD (BLUE)
V2 - FAN LEAD (GREY)
U1 - FAN LEAD (BROWN)
U2 - FAN LEAD (RED)
TK - FAN THERMAL CONTACTS (WHITE)
L1 L2 L3
FAN
MOTOR
U1 U2
TK
TK
THERMALY PROTECTED
W1W2V2V1
200
1.5
*WITHIN 20.4V AND 27.6V*
4
G
(DSC-002361)
F1 F2 F3
F4F5
F6
0
ATQR, CC
F5
1.555
F6 F7
NA
NA
44444
4
2
7
8 STARTER CONTACTOR
E- EMERGENCY STOP
F1 - FAN FUSE #1
F2 - FAN FUSE #2
F3 - FAN FUSE #3
F4/F5 - TRANSFORMER PRI. FUSE
F6 - TRANSFORMER SEC. FUSE
E- EMERGENCY STOP
P- PRESSURE TRANSDUCER
S- SOLONOID N.C.
M - FAN STARTER
T- TEMPERATURE SENSOR
XO6
L1L2
XO5
L1L2
BLK TO #20 TERMINAL
MASTER/SLAVE
WHT TO #19 TERMINAL
MASTER/SLAVE
(FOR SEQUENCING)
--F
03/17/17
PANEL SCHEMATIC NUMBERING
--
1
G
04/28/17
TRANSFORMER FUSE RATING UPDATED
Page 39
H50 460V / 575V SCREW COMPRESSOR
WITH VARIABLE SPEED CONTROLS
ELECTRICAL SCHEMATICS
CSC300 & NXS INVERTER
CSC300-H50-460/575
E.HN.T.S.
MOTOR
T3T2
T1
T1T2T3
L1L2L3
POWER CIRCUIT SCHEMATIC
L1
BY CUSTOMER
FUSIBLE DISCONNECT
L2 L3
GND
CONTROL
PANEL
IMPORTANT NOTE: This print is the confidential property of DV SYSTEMS, INC.
It is not to be used or reproduced in any manner, nor submitted to other parties
for examination without the prior approval of DV SYSTEMS, INC.
DV SYSTEMS, INC. is continuously trying to improve its products, specifications
subject to change without notice.
NXS INVERTER
POWER CONNECTION
FAN
MOTOR
U1 V1W1
U2
V2
W2
TK
TK
USE SEMI-CONDUCTOR TYPE
(FAST ACTING) FUSES WITH INVERTERS.
REFER TO H50 SALES DRAWING FOR FUSE
RATINGS
THERMALY PROTECTED
MAIN
05/06/15
H
TK - FAN THERMAL CONTACT
RSS - REMOTE START/STOP
(FIELD OPTION:
INSTALL RSS TO #18 AND #10
TERMINAL BLOCK. INSTALL WIRE
FROM #18 TO DI5. ON P18 CHANGE
P18.08 FROM 'OFF' TO 'DI REMOTE
START'. ON P10 CHANGE
P10.12 FROM 'KEYPAD' TO
'EQUIPMENT DI')
X07 - R7 AND R8 FOR PROGRAMMABLE
RELAY OUPUT FUNCTION
E- EMERGENCY STOP
F1 - FAN FUSE #1
F2 - FAN FUSE #2
F3 - FAN FUSE #3
F4/F5 - TRANSFORMER PRI. FUSE
F6 - TRANSFORMER SEC. FUSE
E- EMERGENCY STOP
P- PRESSURE TRANSDUCER
S- SOLONOID N.C.
M - FAN STARTER
T- TEMPERATURE SENSOR
123456789
10
11 12 13 14 15 16 17 18 19
20
24 25 26
NXS INVERTER
CONTROL CONNECTION
BOARD OPT-A1
BOARD OPT-A2
3
4
6
5
8
10
24 VAC
T
P
+
C
CSC300
2
20
10 15 1412
+
BLK
WHT
-
RSS
X13
XO9
RELAY OUTPUTS
13
-
3 PHASE
X12
L1 L2 L3
a
CT1
X11
b
c
CT2
X10
a
C
CR1R2R3
XO8
RELAY OUTPUTS
CR4R5R6
XO7
PROGRAMMABLE
RELAY OUTPUTS
ANA-O
ANA-G
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
C-AN1
AN1
AN2
AN3
C-AN2
C-AN3
34
65
X01
DIGITAL INPUTS
X02
ANALOGUE INPUTS
X03
+24VAC
1
0
9
S
M
A2
A1
911
CR7 R8C
8
21 22 23
E
18
TK
7
L1 L2 L3
*WITHIN 20.4V AND 27.6V*
(DSC-002361)
F5
F6
0
T1
T2
T3
L1L2L3
M
(FAN STARTER)
F1 F2 F3
575
FUSE SIZE (AMPS)
F1 F2 F3
F4
FUSE TABLE
WARNING: USE THE SAME FUSE TYPE & RATING
ATDR, CC TIME DELAY
5MM TIME DELAY
VOLTAGE
.5
W1 - FAN LEAD (BLACK)
W2 - FAN LEAD (ORANGE)
V1 - FAN LEAD (BLUE)
V2 - FAN LEAD (GREY)
U1 - FAN LEAD (BROWN)
U2 - FAN LEAD (RED)
TK - FAN THERMAL CONTACTS (WHITE)
460
ATQR, CC
F5
5
5
F6
F7
NA
NA
2.5
222
1
1
2
TRANSFORMER
FAN FUSES F1 / F2 / F3
3
PRIMARY FUSE F4
4
PRIMARY FUSE F5
5 SECONDARY FUSE F6
PANEL SCHEMATIC
6 TERMINAL BLOCK
6
5
3
8
7 GROUND TERMINAL BLOCK
4 2
7
8 STARTER CONTACTOR
.5
2.5 2.5
F4
XO6
L1L2
XO5
L1L2
BLK TO #20 TERMINAL
MASTER/SLAVE
WHT TO #19 TERMINAL
MASTER/SLAVE
(FOR SEQUENCING)
04/27/17
TRANSFORMER FUSE RATING CHANGED
H
--
.5 .5
G
03/17/17
PANEL SCHEMATIC NUMBERING
--
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.