DÜRR 51xx, 52xx User and service manual

INDEX
Important Information
1. Notes ...................................................... 30
1.1 CE - Labelling ................................. 30
1.2 Guidelines .......................................30
1.3 General Notes ................................. 30
1.4 General Safety Notes ..................... 30
1.6 Warnings and Symbols..................31
2. Product Information ............................ 32
2.1 Correct Usage ................................ 32
2.2 Use other than that for the
intended purpose ........................... 32
2.3 Product description ........................ 32
3. Delivery Contents ................................. 33
3.1 Special Accessories ....................... 33
3.2 Disposable material ........................ 33
4. Technical Data ...................................... 34
5. Function ................................................ 36
6. Functional Description ....................... 37
6.1 Compressor .................................... 37
6.2 Control unit with pressure switch ... 37
Installation
7. Storage and
transport requirements ....................... 38
8. Requirements for Set-up .................... 39
8.1 Environmental Requirements ......... 39
8.2 Compressed Air Connection .........40
8.3 Electrical connection ....................... 41
8.4 Pressure switch check and setting42
8.5 Motor circuit breaker adjustment ... 42
8.6 Commissioning ............................... 43
8.7 Draining off condensed water .......43
9. Repairs and Maintenance ................... 44
9.1 Draining off condensed water .......44
9.2 Safety valve .................................... 44
9.3 Filter change ................................... 44
10. Circuit Diagram ..................................... 45
Use
11. Operation............................................... 47
11.1 Turning on the compressor ............ 47
12. Maintenance .......................................... 48
12.1Pressure reducer (accessory) ...... 48
12.2Adjusting the pressure reducer ....48
12.3 Draining off condensed water ....... 48
12.4Safety valve ....................................49
12.5 Filter change ................................... 49
13. Maintenance intervals - Operator /
Technician ............................................. 50
14. Decommissioning ................................ 50
Trouble-shooting
15. Tips for Technicians ............................ 51
16. Tips for Operators ................................ 53
Disposal
17. Disposal of appliance .......................... 54
Parts list
Compressor 51../52.. ............................. 56-62
29
IMPORTANT INFORMATION
1. NOTES
1.1 CE - Labelling
CE-Symbol of conformity. This symbol of conformity guarantees that this appliance conforms to the relevant safety guidelines of the European Union.
1.2 Guidelines
This appliance conforms to the following safety guidelines:
• Machine guidelines 98/37EG, with amendments.
• Electro-magnetic Compatibility 89/336/ EWG, with amendments.
• Low-voltage guidelines 73/23/EWG, with amendments.
• Pressure vessel guidelines 87/404/EWG.
1.3 General Notes
• These Installation and Operating Instructions form an integral part of the unit. They must be kept close to the unit and in readiness whenever required. Precise observance of these instructions is a pre­condition for use of the unit for the intended purpose and for its correct operation. Die Montage- und Gebrauchsanweisung sollte gegebenenfalls an Nachfolger weiter gegeben werden.
• Safety for the operator as well as trouble­free operation of the unit are only ensured if use is made of original equipment parts. Moreover, use may only be made of those accessories that are specified in the technical documentation or that have been expressly approved and released by Dürr Dental for the intended purpose. Dürr Dental cannot guarantee for the safety or proper functioning of this unit in the case where parts or accessories are used which are not supplied by Dürr Dental.
• The guarantee does not cover damage to caused to this unit where parts or accessories are used which are not supplied by Dürr Dental.
30
• The guarantee is valid for 1 year commencing from the date of delivery. Any work performed under guarantee will neither extend nor renew the guarantee.
• Dürr Dental only regard themselves as being responsible for the equipment with regard to safety, reliability and proper functioning if assembly, resettings, changes or modifications, extensions and repairs have been carried out by Dürr Dental or an agency authorised by Dürr Dental and if the equipment is used in conformity with the Installation and Operating Instructions.
• These Installation and Operating Instructions conform to the relevant version of the equipment and the underlying safety standards valid at the time of going to press. All switches, processes, trade marks, software programs and appliances named in this document are registered names.
• Any reprinting of the technical documentation, in whole or in part, is subject to prior approval of Dürr Dental being given in writing.
1.4 General Safety Notes
This compressor has been designed and constructed by Dürr Dental so that correct usage of the appliance is virtually free of any possible injury or danger. In spite of this, we feel it is our duty to mention the following safety measures in order to prevent any possible danger to all personnel.
• When using this compressor all local and relevant regulations must be observed! In the interests of trouble-free operation the operator is responsible for observing these regulations.
• Retain the packaging for possible return of the product to the manufacturers. Ensure that the packaging is kept out of the reach of children. Only the original packaging provides adequate protection during transport of the unit. Should return of the product to the manufacturers be necessary during the guarantee period, Dürr Dental accepts no responsibility for damage occurring during transport where the original packaging was not used!
• Before every use the operator must check the functional safety and the condition of the appliance.
• The operator must be knowledgeable in the operation of the appliance.
• The product is not designed to be used in medical treatment areas where there exists the danger of explosion. Areas where explosions could occur are those where flammable anesthetic material, skin cleansers, oxygen and skin disinfectants are present. This appliance is not to be used in areas where the atmosphere could cause fire.
1.5 Electrical Safety Notes
• The compressor may only be connected to an earthed safety socket or CEE-socket, depending on model of compressor.
• Before connecting the appliance to the power supply check that the electrical current and the frequency of the device as described on the appliance are compatible with that of the power supply.
• Check the appliance and the power supply cables for possible damage before switching on. Damaged cables, plugs and sockets must be replaced before use.
• In danger situations or in cases of technical defect immediately separate from the power supply (unplug).
• In cases of repairs and/or maintenance the compressor must be disconnected from the mains supply, and the air supply hoses as well as the pressurized container must be depressurized.
1.6 Warnings and Symbols
In the Installation and Operating Instructions use is made of the following terms or symbols to denote information of special importance:
Information and/or mandatory regulations or prohibitions for the prevention of personal injury or substantial property damage.
Warning! High voltage.
Special information regarding the economical use of the equipment and other information.
CE-Labeling
Disconnect from mains supply.
Warning! Hot surface.
Warning!
Compressor starts automatically.
Check environment. The appliance should not be used in wet or damp conditions.
Recycling
Observe installation and operating instructions!
31
2. PRODUCT INFORMATION
2.1 Correct Usage
This compressor is only designed for providing compressed air for dental units or similar applications.
Mounting in medical treatment units:
During the development and production of this surgery compressor all requirements concerning medical products were taken into consideration wherever possible. Thus this appliance can be mounted in medical treatment units. Where this appliance is mounted in medical treatment units, then the requirements of guidelines 93/42 EWG must be observed on installation and operation.
2.2 Use other than that for the intended purpose
The compressed air provided by this unit is not suitable for use in breathing apparatus or similar facilities without the addition of special filters, such as those used in surgical areas.
• The compressors are designed for use in
dry, ventilated rooms with an ambient temperature of +10 to +40 °C.
• Do not set up the compressor in the rain.
The machine must not be used in wet or damp conditions. Furthermore, operation in the vicinity of gases or flammable fluids is forbidden.
• Before installing the compressor in medical
facilities it must be checked that that the available material is designed to satisfy the requirements of the purpose for which is intended. Please observe the technical data.
• Any classification and conformity evaluation
should be carried out by the manufacturer of the end product.
• Any other use or use beyond what is
specified is deemed to be not for the intended purpose. The manufacturer accepts no liability for damage resulting therefrom. All risk is borne solely by the user.
2.3 Product description
The Dürr Compressor 51../52.. provides an oil-free, dry and filtered pressurized air, for use in medical units.
32
3. DELIVERY CONTENTS
Compressor with / out Dry Air System (DAS):
Compressor accessories .......... 5410-002-50
nstallation and
operating instruction ............. 9000-610-01/01
Compressor with Dry Air System (DAS) only:
Collection tank ............................ 3413-001-00
Operating instructions DAS ...... 9000-610-34
3.1 Special Accessories
The following parts are not standard and must be ordered separately.
Pressure reducer ....................... 3410-008-00
Wooden cabinet ......................... 5110-500-00
Dry Air System,
upgrade set ................................ 1640-500-52
3.2 Disposable material
Filter set compressor .................. 0832-982-00
Filter set DAS ............................... 1610-121-00
Sterile filter DAS ........................... 1640-981-00
33
4. TECHNICAL DATA
Model 5110-01 5111-01 5120-51 5121-51
Voltage V 230/1~ 230/1~ 400/3~ 400/3~ Frequency Hz 50 50 50 50 Current consumption at 7 bar A 3,8 3,8 1,5 1,5 Motor circuit breaking set at A 4,2 4,2 1,6 1,6 Power rating kW 0,68 0,68 0,71 0,71 R.P.M. min Mains fuse rating A16161010 Fuse type IP 44 IP 44 IP 44 IP 44 Noise level dB(A) 66 66 66 66 No. cylinders 1111 Flow rate at 5 bar l/min 55 53 55 53 * Charge time min3333 Open/Shutoff pressure bar 5,5 – 7,5 5,5 – 7,5 5,5 – 7,5 5,5 – 7,5 Safety valve setting bar8888 Vessel volume l25252525 Duty cycle %ED 100 50 100 50 DAS - yes - yes Filtration, filter (0832-982-00) compr. µm 10 10 10 10 Filtration, fine filter (1610-121-00) dry air µm - 3,5 - 3,5 Filtration, sterile filter (1640-981-00) dry air µm - 0,01 - 0,01 Weight kg 39 48 39 48 Dimensions Transport and storage conditions Temperature Relative humidity Operating conditions Temperature Relative humidity
(H x L x D) cm 68 x 40 x 39 68 x 39 x 40 68 x 39 x 4068 x 40 x 48
-25 °C to +55 °C 10% to 90% (no condensation)
+10 °C to 40 °C
up
to 70%
-1
1400 1400 1400 1400
* Time taken for the compressor to reach the shut-off pressure of 7.5 bar from start-up pressure of 0 bar
34
Model 5210-01 5211-01 5220-51 5221-51
Voltage V 230/1~ 230/1~ 400/3~ 400/3~ Frequency Hz 50 50 50 50 Current consumption at 7 bar A 3,8 3,8 3,5 3,5 Motor circuit breaking set at A 4,2 4,2 3,6 3,6 Power rating kW 0,68 0,68 1,5 1,5 R.P.M. min Mains fuse rating A16161010 Fuse type IP 44 IP 44 IP 44 IP 44 Noise level dB(A) 69 69 69 69 No. cylinders 2333 Flow rate at 5 bar l/min 115 110 155 110 * Charge time min 1,5 1,5 1,5 1,5 Open/Shutoff pressure bar 5,5 – 7,5 5,5 – 7,5 5,5 – 7,5 5,5 – 7,5 Safety valve setting bar8888 Vessel volume l25252525 Duty cycle %ED 100 50 100 50 DAS -ja-ja Filtration, filter (0832-982-00) compr. µm 10 10 10 10 Filtration, fine filter (1610-121-00) dry air µm - 3,5 - 3,5 Filtration, sterile filter (1640-981-00) dry air µm - 0,01 - 0,01 Weight kg 48 56 48 56 Dimensions
(H x L x D) cm 68 x 40 x 45 68 x 40 x 48 68 x 40 x 4568 x 40 x 48
Transport and storage conditions Temperature Relative humidity
-25 °C to +55 °C 10% to 90% (no condensation)
Operating conditions Temperature Relative humidity
+10 °C to 40 °C
up
to 70%
-1
1400 1400 1400 1400
* Time taken for the compressor to reach the shut-off pressure of 7.5 bar from start-up pressure of 0 bar
35
5. FUNCTION
17 18
1
2
8
3
16
14
13
15
12
10
11
4
7
6
5
36
6. FUNCTIONAL DESCRIPTION
6.1 Compressor
Atmospheric air is drawn into the cylinder chamber via a suction filter (17). The piston (18) in the cylinder then compresses this air. The inlet/outlet valve cuts off one flow route thereby forcing the air directly into the tank (10) via the non-return valve. Where a DAS is present (2), the compressed air is led through the spiral cooling pipe (3) to the dry air system (2). In this way the air, warmed on compressing, is now cooled whereby most of the water present in the air is extracted as condensated water. Each time the compressor motor is sitched ioff this condensated water is collected in the collection tank (5). The partially dry air is then fed through the drying agent (6), the Sintermetallfilter (4) and the fine filter (1) as dry and hygienic air into the compressor chamber (10). The non-return valve (7) ensures the compressed air cannot escape. The compressor motor (11) continues to provide compressed air until the pressure switch (16) registers that the pressure correct level has been achieved. (The actual pressure can be read off the pressure gauge (15).) If the maximum relative humidity in the tank (10) is exceeded, then the Polyamidband Hygrostat (8) expands, whereby a valve is opened and dry air from the tank flows in the reverse direction towards the DAS (2). During this phase the unit is regenerating. This means that the humidity present in the DAS is carried via the dry air to the collection tank (5). This regeneration procedure repeats irself until such time as the pre-set relative humidity at the Hygrostat (8) is reached.
6.2 Control unit with pressure switch
If a user appliance (turbine etc.) draws off compressed air, the tank pressure drops. If in the tank the pre-set minmum pressure as set at the pressure switch (16) is reached, then the compressor motor is activated. When the pre-set maximum pressure is reached, the compressor motor is switched off. The control unit is fitted with a pressure gauge (15) which displays the tank pressure. A safety valve (12) prevents the maximumm pressure from being exceeded, eg in case of a defect. The control unit is also fitted with a condensed water drain tap (13) and a shut­off valve (14).
37
INSTALLATION
7. STORAGE AND TRANSPORT REQUIREMENTS
The compressor is packed in a carton for transport. This prevents any damage to the appliance during transport. Always use the original packing for the machine wherever possible.
Transport the machine in an upright position.
During storage and transport, protect the appliance at all times from damp, dirt and extremes of temperature. Take special care to avoid any electrical parts from
becoming wet. The surgery compressor is ready for immediate installation. If the appliance is in its original packing it can be stored in a warm, dry and dust-free room. (see technical data)
Retain the original packing if at all
possible. If this is not possible
dispose of the packing in an
environmentally correct way. The
transport carton can be disposed of
as paper waste.
38
The compressor must be
transported in pressure-free state.
Before transport empty the
compressor and bleed the hoses.
Vor Before transport or storage any condensated water in the pressure vessel must be drained off. (See section 8.7 Draining condensed water off).
8. REQUIREMENTS FOR SET-UP
Set-up and commissioning should only be carried out by an authorized technician. Observe local rules and regulations
8.1 Environmental Requirements
• The appliance should only be installed and operated in a well-ventilated, dry and dust­free room.
• The compressor must be installed in a position that allows the identification plate to be easily visible at all times and where accessible for repairs and maintenance.
• The appliance must be placed on a smooth, flat and stable floor. (Note compressor weight, see technical data).
The air intake side and the ventilation grille on motor side must both be free and there must be adequate distance from the nearest walls (c. 20 centimeter). The power cable and the air hoses must not be bent or twisted.
As the compressor starts operation automatically as soon as pressure falls below a set amount, a warning sign in accordance with ISO 7000-0017 must be displayed warning of automatic operation.
39
The room temperature must not be allowed to fall below 10 °C otherwise a trouble-free operation of the control unit within the machine cannot be guaranteed. If room temperatures exceed 40 °C, additio­nal ventilation must be provided by installing a fan (see Fig. 1).
The compressor unit gives off about 70 % of its electrical energy as heat energy causing the ambient temperature to rise if ventilation is inadequate.
The motor fan provides efficient cooling to the motor. For this to happen the air intake
1
and output must be unhindered. In extreme cases a separate ventilation system must be installed, see Fig. 1.
Do not place any objects on or against the compressor; by a room temperature of c. 40 °C the cylinder and cylinder heads can warm up to over 110 °C. Fire risk!
40
8.2 Tryckluftsanslutning
The compressor is fitted as standard with a control unit consisting of: Pressure switch (16), pressure gauge (15), safety valve (12), shut-off valve (14) and condensed water drainage tap (13).
16
15 12
14 13
20
2
In order to ensure a constant pressure flow, a pressure reducer (as accessory) is recommended.
The pressure connection is carried out at the connector nozzle (20) or the pressure reducer (as accessory).
• The flexible pressure hose LW10 should be pushed onto the connector nozzle and secured from slipping using a hose clip.
The use of a flexible hose between the fixed air connection and the compressor helps to prevent the transmission of vibration and noise.
8.3 Electrical connection
Electrical connections should only be carried out by a qualified electrician.
(with the exception of those models delivered supplied with either a standard EEC plug or a shockproof
domestic plug according to model) The compressor is supplied with a standard EEC plug in the 400 V configuration and with a shockproof domestic plug on the 230 V model. All local and national regulations concerning electrical connections must be observed. Mains voltage and frequency must coincide with those shown on the identification plate.
No cables should be laid on the
unit. The hot surface of the unit
will melt and destroy the cable
insulation.
If the unit is connected directly to the mains power supply then a power off switch must be located in the vicinity of the unit that has a minimum 3 mm contact gap (e.g. fuse box).
If the unit is connected to the mains power supply via a plug and socket then, for safety reasons, the socket must be easily accessible so that the unit can be disconnected in dangerous situations.
The relevant circuit must be fitted with a fuse of maximal 16 A.
Observe the correct turning
direction for the alternating
current compressor unit (400 V):
The direction is clearly indicated by
an arrow on the ventilator cover. If the
direction of rotation is incorrect, there
is danger of the compressor unit
overheating. If the turning direction is incorrect, disconnect the unit at the mains and swap the polarity of the two pressure switch power supply cables.
When connecting the appliance to
a different outlet, check direction
of rotation!
41
8.4 Pressure switch check and setting
The pressure switch (16) is factory-set. At 5.5 bar the motor is switched ON.
21
At 7.5 bar the motor is switched OFF.
If required, the working pressure of the compressor can be altered at the
pressure switch. To do this, first the shutoff pressure and then the connecting pressure must be set using
22
the pressure difference (
Before removing the protective
23
cap on the pressure switch, the
appliance must be disconnected
from the mains.
∆∆
P).
∆∆
3
Adjust cut-off pressure P
adjusting screw (22). (In direction of arrow (+) it increases and in direction of arrow (-) decreases). The pressure difference itself is not altered in this operation. Note maximum pressure (8 bar) as set at safety valve. The shut-off pressure must be at least 0.5 bar below that of the safety valve, otherwise the safety valve will open and the compressor motor runs continuously as it never achieves the shut off pressure.
Adjust pressure difference
connecting pressure and shutoff pressure at the adjustment screw (23), by turning it towards plus (+) or minus (-).
using the
∆∆
P
between
∆∆
42
The tank must be under pressure when this adjustment is carried out.
8.5 Motor circuit breaker adjustment
The motor circuit breaker (21) has been factory-set. This value should be checked during installation. The motor circuit breaker is situated under the pressure switch cover (16). (See section 4. Technical Data).
• Measure max. current (value shortly before
shut off pressure is reached).
• Increase motor circuit breaker by adjusting
screw (21) approx. 0.3 A.
8.6 Commissioning
• Check all compressed air connections.
• The unit must be connected to the power
16
supply correctly.
• Check that air filters are fitted correctly.
• Turn compressor at switch (16) to on. (Position ‘I’)
• Check for abnormal noises from unit on first use.
• For 400 V - compressors check rotation of motor.
• Check on and shut-off pressures of the compressor. (Approx.5.5 and 7.5 bar).
4
• Check safety valve for correct function, (see 9.2 Safety valve).
8.7 Draining off condensed water
During transport condensated water may accumulate in the tank due to temperature differnces. Each time a compressor is set up, first drain off the condensated water – even from those compressors fitted with DAS. Proceed as follows:
• With the compressor switched on, and maximum tank pressure, open the condensated water drain tap (13) as far as possible.
13
• Wait for the condensated water to be blown completely out of the tank.
5
• Close the drain tap once more.
43
9. REPAIRS AND MAINTENANCE
Repairs and maintenance should only be carried out by a qualified and authorized technician. Only use parts and accessories approved by the manufacturer.
Before all repairs and maintenance the compressor must be switched off and disconnected from power supply (disconnect at mains).
The compressor surfaces are hot. Let the compressor cool before all repairs and maintenance.
9.1 Draining off condensed water
See 8.7.
9.2 Safety valve
The safety valve is set to 8 ba manufacturer and then tested and stamped.
It may not be readjusted!
The safety valve must be checked for correct functioning every six months. To do this, open the knurled screw (12) at
12
max. tank pressure until air escapes from the safety valve. Briefly allow air to blow freely through the safety valve. Retighten the knurled screw.
rr
r by the
rr
44
6
9.3 Filter change
The filter replacement interval will largely depend on the extent of dust in the air. Under normal conditions the filter needs changing once a year.
See Installation Instructions 9000-416-016
Filter order numbers:
Compressor
Filter set ....................................... 0832-982-00
Dry Air System
Fine filter ...................................... 1610-121-00
Sterile filter ..................................... 1640-981-0
10. CIRCUIT DIAGRAM
10.1 Version in 230 V 1~
Geräteliste Q1 Pressure switch
X1 Power supply 230 V 50 Hz M1 Compressor motor Y1 Solenoid valve
(only for compressors without DAS)
M2 Ventilator
(only with anti-noise cover)
45
10.2 Version in 400 V 3~
Parts list Q1 Pressure switch
X1 Power supply 3/N/PE AC 400V 50Hz M1 Compressor motor Y1 Solenoid valve
(only for compressors without DAS)
M2 Ventilator
(only with anti-noise cover)
46
USE
11. OPERATION
Operation of the compressor is relatively easy and for the most part automatic.
In case of any danger disconnect power supply (disconnect from mains).
The compressor surfaces get hot. Touching the surfaces could lead to burns.
Automatic start-up. If the pressure in the tank falls below a certain level the motor starts and continues to provide compressed air until the maximum pressure is
16
7
reached.
11.1 Turning on the compressor
The compressor is switched on by turning the handwheel on the control unit (16) to position ‘I’. The motor starts and the compressor fills to the maximum. On reaching the shut-off level the motor stops. The maximum permitted operating pressure must not be exceeded. The maximum permitted operating pressure is indicated on the pressure gauge with a red line. If the maximum permitted operating pressure is exceeded, the compressor motor must be disconnected from the power supply (unplug at mains socket). Inform the technician responsible.
47
12. MAINTENANCE
In order to check that the compressor is functioning absolutely correctly, the following
30
maintenance steps should be carried out regularly.
12.1 Pressure reducer (accessory)
The fitting of a pressure reducer is strongly recommended. (vor den Verbraucher) The pressure reducer regulates the pressure flow to achieve the desired operating pressure. The pressure reducer is mounted on the pressure switch.
31
8
12.2 Adjusting the pressure reducer
To adjust the pressure rate, operate the nozzle, turbine, etc., lift up the adjusting ring (30) and turn in the direction of the arrow + (increase flow rate) or in the direction of the arrow - (decrease flow rate), until the desired flow rate is displayed. When finished replace the adjusting ring, until it clicks gently in place and the pressure reducer is protected from unintentional adjustment. The desired flow rate is now set. It can be read on the pressure gauge (31). For correct flow rates, see the manufacturer’s operating instructions (e.g. turbine etc.).
48
12.3 Draining off condensed water
Condensated water is removed automatically in compressors fitted with a dry air system. For compressors without DAS the condensated water must be drained off at least once a month! In countries with high air humidity water must be drained off daily! Proceed as follows:
• With the compressor switched on, and maximum tank pressure, open the condensated water drain tap (13) as far as possible.
13
• Wait for the condensated water to be blown completely out of the tank.
9
• Close the drain tap once more.
10
12.4 Safety valve
The safety valve is adjusted to 8 bar by the manufacturer and then tested and stamped.
It may not be readjusted!
The safety valve must be checked for correct functioning every six months. To do this, open the knurled screw (12) at max. tank pressure until air escapes from the safety valve. Briefly allow air to blow freely through the safety valve. Retighten the
12
knurled screw (12).
12.5 Filter change
17
The filter replacement interval will largely depend on the extent of dust in the air. Under normal conditions the filter needs changing once a year.
11
1
35
See Installation Instructions 9000-461-016.
• Changing the suction filter (17). Pull out the filter unit by the cap. Change the complete filter unit.
• Changing the fine filter (1) of the DAS. Unscrew cover (35). Pull out the fine filter (1) and place new filter in position. Replace cover.
Filter order numbers:
Compressor
Filter set ....................................... 0832-982-00
Dry Air System
Fine filter ...................................... 1610-121-00
Sterile filter ................................... 1640-981-00
49
13. MAINTENANCE INTERVALS - OPERATOR / TECHNICIAN
Maintenance procedure Section Interval
Adjust pressure reducer 12.2 yearly Drain condensated water *) 12.3 monthly
Check safety valve 12.4 every six month Filter change 12.5 yearly
*) Only for non-DAS appliances. In countries with high air humidity water must be drained off daily!
daily
14. DECOMMISSIONING
If the compressor is not going to be used for a long period of time, it is recommended draining the condensated water from the tank. Allow the compressor to run for c. 10 minutes with the condensated water drain tap (13) open. Then switch off at the main switch, close the drainage tap and disconnect from the mains.
50
13
12
TROUBLE-SHOOTING
15. TIPS FOR TECHNICIANS
The following list of possible problem causes is designed for use by qualified technicians. Repairs must only be carried out by qualified personnel.
Problem Solution
does not switch on.
Probable cause
• No power.1. Compressor
• Pressure switch not on.
• Current higher than nominal rating.
• Current continuously equal to nominal rating.
• Ventilating valve defect, unit runs with back pressure (non­DAS compressors only)
• Check mains fuse, if necessary reset circuit breaker; if fuse is blown, replace it. Check mains current.
• Connect pressure switch and wait 30 seconds. If the pressure switch remains connected briefly and then switches the motor off, check the power consumption: for all three phases if three-phase and for one phase if AC.
• Undervoltage: measure voltage, call an electrician if necessary. Capacitor defective (230 V 1~): Check capacitor, replace if necessary.
• Unit blocked mechanically, piston seized (motor circuit breaker triggered): pull out mains plug, remove cover from crank housing of overheated compressor and turn fan wheel. In the event of this not being possible, replace piston and cylinder, or entire unit.
• Motor circuit breaker set too low (3~ only): measure current. Adjust motor circuit breaker accordingly (0.3 A higher than current measured). Motor circuit breaker defective: Check motor circuit breaker and replace if necessary.
• Check to ensure that ventilating valve opens after unit is switched on. Remove blockage or replace.
51
Probable causeProblem Solution
2. Compressor fails to switch off.
3. Compressor switches on intermittently without any air being drawn off by user.
4. Excessive compressor noise (e.g. knocking sound).
• Defective plate valve (inlet and/ or outlet valve) between cylinder head and cylinder.
• Air escapes at ventilating valve (non-DAS compressors only).
• Air blows through the DAS into the collection tank.
• Leakage in compressed air system
• Compressor capacity too low; excessive air drawn off per workstation, approx. 50 l/min.
• Worn piston compression seal.
Air escaping down through dry air system.
• Air escaping at non-return
valve.
• Leakage in connections.
• Damaged bearings
• Dismantle cylinder head and install new plate valve.
• Check ventilating valve. (The valve is open when power is off)
• Check dry air system control head.
• Open shut-off valve and subject tubes to pressure. Use spray to find leak if necessary. Seal leak.
• Determine air requirements, replace with larger compressor if necessary.
• Replace piston and cylinder, or entire unit.
• Dry air system is in regeneration phase, air humidity in tank is being reduced.
• Check non-return valve for air leaks. Clean or replace non­return valve.
• Locate leak and seal.
• Check motor shaft bearings and crankshaft bearings, replace if necessary.
5 Supply
performance loss, compressor takes longer to charge tank (For charging periods, see Technical Data).
6. Water drips from handset.
52
• Suction filter badly soiled.
• Defective plate valve (inlet and/ or outlet valve).
• Worn piston compression seal.
• Condensated water im tank.
• Suction filter should be replaced at least once a year. Never clean the filter with petrol or oil!
• Dismantle cylinder head and install new plate valve.
• Replace piston and cylinder, or entire unit.
• The condensed water must be drained off at least once a month. Or daily in tropical zones or locations with high air humidity. Observe ambient temperature of the compressor, (refer to the requirements in the set-up instructions.
16. TIPS FOR OPERATORS
Probable causeProblem Solution
1. Compressor does not switch on.
2. Compressor fails to switch off.
3. Compressor switches on intermittently without any air being drawn off by user.
4. Excessive compressor noise (e.g. knocking sound).
• No power.
• Pressure switch not on.
• Compressor capacity too low; excessive air drawn off per workstation, approx. 50 l/min.
• Air escaping down through dry air system.
• Air escaping at non-return valve.
• Leakage in connections.
• Damaged bearings.
• Check mains fuse, if necessary reset circuit breaker; if fuse is blown, replace it. Check mains current.
• Connect pressure switch and wait 30 seconds.
• Contact your technician.
• Determine air requirements, replace with larger compressor if necessary.
• Contact your technician.
• Dry air system is in regeneration phase, air humidity in tank is being reduced.
• Check non-return valve for air leaks.
• Locate leak and seal.
• Contact your technician.
• Contact your technician.
performance loss, compressor takes longer to charge tank (For charging periods, see Technical Data).
6. Water drips from handset.
• Suction filter badly soiled.5 Supply
• Condensated water im tank.
• Suction filter should be replaced at least once a year. Never clean the filter with petrol or oil!
• The condensed water must be drained off at least once a month. Or daily in tropical zones or locations with high air humidity. Observe ambient temperature of the compressor, (refer to the requirements in the set-up instructions).
53
DISPOSAL
17. DISPOSAL OF APPLIANCE
• Unplug the unit
• Drain the compressor tank of air by opening the condensated water tap. (See 8.7 Draining off condensated water)
• Dispose of the compressor according to local regulations concerning waste material.
54
55
Loading...