DuraVent PolyPro User Manual

Page 1
Installation Instructions
PolyPro Single-Wall Gas Vent System for Category II & IV Gas-Burning Appliances
PolyPro
®
Page 2
A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE
TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO
THAT POLYPRO® BE INSTALLED ONLY IN ACCORDANCE WITH
THESE INSTRUCTIONS.
WARNING
CARBON MONOXIDE POISONING HAZARD. Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
Examine all components for possible
shipping damage prior to installation;
Read all instructions before beginning
the installation and follow these instructions exactly as written.
Proper joint assembly is essential for a
safe installation. Check the integrity of ALL joints upon completion of assembly
This venting system must be free to
expand and contract under normal operation.
Assure unrestricted vent movement
where required through walls, ceilings and roof penetrations.
This venting system must be supported
in accordance with these instructions.
Do not mix pipe, ttings, or joining
methods from dierent vent system manufacturers. Do not use adhesives of any kind with this venting system. insurance and safety listing of your appliance. Acceptance of the installed system is dependant on full compliance with these installation instrucitons
WARNING
Risk of carbon monoxide poisoning or re due to joint separation or pipe breakage.
Keep these instructions for future reference.
Dear Customer, Installer, or End User:
We welcome any comments regarding matters pertaining to our DuraVent products. We welcome any ideas, input or complaints to help improve our product oering. Send your emails to: president@duravent.com
If you are searching for tech support or product information, please phone us at 800-835-4429. Or email us at: techsupport@duravent.com
PolyPro® is one of M&G DuraVent's line of products.
Page 3
PolyPro Single-Wall Gas Vent System
For the most up-to-date installation instructions, see www.duravent.com
CONTENTS
LISTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . 4
APPLICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . 4
PERMITS . . . .. . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . 4
GENERAL INSTALLATION NOTES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
CLEARANCES TABLE 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . 4
CONDENSATE DRAIN . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . .4
JOINT CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .. . . . 5
EQUIVALENT LENGTH CHART TABLE 2 . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .. . . . 5
APPLIANCE CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . 6
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ENCLOSURE REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
HORIZONTAL TERMINATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
WALL AND CEILING PENETR ATION TABLE 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
VERTICAL TERMINATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
MULTIPLE VENT RUNS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ALUMINUM FLEX AIR INTAKE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
WARRANTY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
PolyPro
®
3
Page 4
LISTING
Listed to ULC S636 Rated Class IIA, IIB, and IIC vent system
maximum temperature 230°F (110 °C) maximum positive pressure 15 in-w.c.
Massachusetts Plumbers Board,
# G1-0811-42
APPLICATION
ANSI Category II and IV gas-burning appliances Appliances specically tested and listed to use M&G DuraVent PolyPro Venting
PERMITS
Check with your local Building Ocial, Fire Ocial, or other authority having jurisdiction regarding permits, restrictions, and installation inspections in your area.
GENERAL INSTALLATION NOTES Read these instructions before beginning.
You must use only authorized M&G DuraVent PolyPro vent parts, or other parts specically authorized in these instructions and/or listed by the appliance manufacturer in order to maintain a safe, approved system.
Do not ll any air space clearance
(Table 1) with insulation.
Do not mix parts or try to match with
other products or use improvised solutions.
Do not install damaged or modied
parts.
Table 1
Use soapy water to lubricate gaskets.
Never use Petroleum base lubricants.
If these directions and those of the appliance manufacturer dier, follow the more conservative requirements. If you have any questions, contact either your dealer or M&G DuraVent directly. A venting system must not be routed into, through, or within any other vent, such as an existing masonry or factory-built chimney ue, unless that vent or chimney is not being used to vent another appliance and is only used as a conduit for the gas-vent system. Plastic venting systems shall not pass through re rated separations without approved restopping.
Refer to the appliance manufacturer's instructions for maximum and minimum vent lengths permitted with your specic appliance model. This information should include guidance on the maximum number of elbows and related pressure-drops. The total vent length from the appliance to the termination shall not be greater than specied by the appliance manufacturer. If specic guidance is not oered by the appliance manufacturer as to Equivalent Vent Lengths (EVL) for vent components, the general guidelines in Table 2 can be used.
CONDENSATE DRAIN (Fig.1)
Refer to the appliance manufacturer’s installation instructions for requirements of condensate drainage. Ensure proper system slope for drainage. (Fig.7)
Clearance to Combustibles
VENT PIPE ORIENTATION
Single Wall Vertical Horizontal
Up to 190°F 0" 0"
Up to 230°F 0" ¼" (6mm) all around
Concentric
Up to 230°F 0" 0"
4
IMPORTANT
The vent system must be compliant in accordance with local code requirements and appropriate National Codes: In the US: NFPA 54 / ANSI Z223.1 National Fuel Gas Code or the International Fuel Gas Code. In Canada: CAN/CGA-B149.1 Natural Gas Installation Code or CAN/CGA-
149.2 Propane Installation Code.
Page 5
IMPORTANT
To prevent possible recirculation of ue gases, the installer must consider the eects of prevailing wind conditions, eddy zones, nearby buildings, obstructions, or other obstacles such as shrubs when planning exhaust and air intake locations. M&G DuraVent can not be held responsible for poor appliance performance or damage to buildings due to an incorrect installation. The minimum clearances detailed within our instructions may not be adequate in some circumstances depending on the specics of the installation. For this reason we always recommend vertical venting.
SIPHON
P-TRAP
Figure 1
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow these installation
instructions could result in personal
injury or death
JOINT CONNECTIONS
Verify the gasket is seated evenly inside the groove in the female end. There are two versions of locking band available, one with stando legs (Fig.2), one without (Fig.3). For both: Slide Locking Band on male pipe section. Fig.2: For pipe without Locking Button: Slide pipe sections together until joint is bottomed out then slide apart
¼” to 5/8” (7.5 - 15 mm) for expansion. Clip the locking band clasp onto the female hub. Fig.3: For PP/Metal pipe with Locking Button: Insert locking button into locking band recess, rotate button away from Locking Band Clasp, insert pipe sections, push lock band clamp downward into socket, disengage button 1/4" from socket. Screws
are not allowed for joint connection. Never penetrate the wall of PolyPro vent pipe. (Exception- a SS screw may be used outside the building on exterior termination ttings to orient an elbow, etc).
IMPORTANT: Locking bands are
Table 2 - Equivalent Length Chart
2" Equivalent
Length
1-ft Vent Pipe 1-ft 1-ft 1-ft 1-ft 1-ft 1-ft
2-ft
1-ft Flex Pipe
1-ft Flex Pipe
45 Elbow 3-ft 3-ft 5-ft 6-ft 6-ft 13-ft
90 Elbow 5-ft 7-ft 12-ft 14-ft 14-ft 19-ft
Tee 9-ft 12-ft 19-ft 21-ft 22-ft 29-ft
(same diameter
as rigid)
0.4-ft
(updsized one
diameter)
3" Equivalent
Length
2-ft
(same diameter
as rigid)
0.6-ft
(updsized one
diameter)
4" Equivalent
Length
2-ft
(same diameter
as rigid)
0.6-ft
(updsized one
diameter)
5" Equivalent
Length
2-ft
(same diameter
as rigid)
N/A N/A N/A
6" Equivalent
Length
N/A N/A
8" Equivalent
Length
5
Page 6
MALE
FEMALE
END
LOCKING BUTTON
END
Figure 2
LOCKING BAND RECESS
LOCKING BAND CLASP
LOCKING BAND
PUSH DOWN
TO LOCK
VERIFY GASKET IS SEATED IN FEMALE END OF PIPE
PRY OUT
TO UNLOCK
CLICK!
APPLIANCE CONNECTION: 2" - 4"
1. If the appliance has a PVC/CPVC female
outlet use the Appliance Adapter/ PVC Adapter and Clamp. (Fig.4)
If the appliance has a PVC/CPVC
Male outlet use a matching PVC/ CPVC coupling to convert to a female outlet.
2. If the appliance outlet has a rubber
boot or Fernco-style appliance adapter, then the PolyPro vent pipe may attach directly to the appliance (Fig.5).
3. If the appliance has a FasNSeal outlet
then use the FasNSeal to PolyPro adapter.
1/4"
POLYPRO PIPE
APPLIANCE ADAPTER CLAMP
APPLIANCE ADAPTER/ PVC ADAPTER
APPLIANCE EXHAUST OUTLET OR PVC UNION
Figure 3
mandatory on all exhaust vent joints on pipe sizes from 2" up to 4". (Fig.2, 3)
For 5"-8" diameter, Locking Bands are
not required but strongly recommended at every exhaust vent joint.
(Fig.2, 3)
Locking bands are optional for air inlet
vent joints.
POLYPRO TO DURAVENT / SECURITY CHIMNEY METAL VENT CONNECTION
Approved M&G Duravent / Security Chimney 1738/636 metal vent ttings can be used with PolyPro. For PolyPro (female) to Metal Vent (Male) connections, the metal ttings will have a Locking Button or Protrusion, and will be connected simliar to Fig. 3.
6
(Fig.2, 3)
APPLIANCE
Figure 4
Figure 5
POLYPRO VENT PIPE
TIGHTEN CLAMPS ON RUBBER COUPLER ADAPTER OR FERNCO STYLE ADAPTER TO SECURE VENT PIPE TO APPLIANCE
APPLIANCE OUTLET
Page 7
INSTALLATION
1. Pipe lengths may be cut to length
(Fig.6). Use an alternate clamp (Fig.4­PPS-PAC / PPS-LBC) for the connection if a locking button (Fig.3) is removed.
Cut square (not at an angle) to the
end of the pipe.
Remove burrs before assembly.
MARK
CUT WITH HACKSAW
TO APPLIANCE
5/8"
1/4"  5/8"
7.5mm  15mm
MIN
12"
Figure 7
IMPORTANT
PP Pipe sections must be disengaged 1/4"­5/8" per joint (to allow for expansion) and sloped 3°(5/8"per ft) back to the appliance per Fig.7 for proper condensate flow.
DEBURR
Figure 6
2. Check with appliance manufacturer for any restrictions or limits on vent length, number of elbows, etc.
3. The slope of the vent pipe must be at least 3° (5/8" per ft, 50mm per meter) back to the appliance. (Fig.7)
4. Every horizontal section must be supported. (Fig.8)
5. The venting system shall be securely supported using suitable hangers. Duravent hardware is recommended; eld supplied support hardware suitable to the AHJ is acceptable, hardware must not deform or damage the vent. (Fig. 7 and 8) Make sure the load of the vent system is not supported by the appliance.
On Duravent and other certain clamp
styles, ¼” or greater All-thread may be used as an extension.
6. Vertical installations must be supported every 10 feet (3 meters) or less. (Fig.8)
7. Do not install / enclose PolyPro in the stud space of a wall.
8. Elbows and Tees are suciently supported when a bracket is xed at the female end of the connected straight section. (Fig.8)
ALLTHREAD
LOCKING BANDS REQUIRED AT EVERY EXHAUST JOINT
MAX 10FT 3m
WALL STRAP
MINIMUM 1PER
HORIZONTAL PIPE
SECTION
Figure 8
9. Vertical components can be insulated in unconditioned space or when ran outside.
10. Use black UV protected components on venting installed on the exterior.
ENCLOSURE REQUIREMENTS Through Rooms: Interior vents shall be
enclosed where they extend through closets, storage areas, occupied spaces, or anyplace where the surface of the vent could be contacted by persons or combustible materials except when installed in the room with the
appliance.
7
Page 8
Multi-Story: Consult local building or other applicable codes for requirements in your area. In the U.S., NFPA 211 10.6.3 (2013) states: “Vents that pass through the oors of buildings requiring the protection of vertical openings shall be enclosed within an approved enclosure. The enclosure walls shall have a re resistance rating of not less than 1 hour where a vent is located in a building less than four stories in height. The enclosure walls shall have a re resistance rating of not less than 2 hours where a vent is located in a building four or more stories in height."
If the vent system is not exposed to wind or lateral load within the enclosure and joints cannot buckle, wall straps are not required provided upper and lower supports are proper.
ENCLOSURE
FIRESTOP
FIRESTOP
FIRESTOPS (Fig. 9)
1. Firestops are required at each ceiling/ oor penetration including an attic. Firestops are not required at the roof deck penetration.
2. Cut and/or frame hole. (Table 3)
3. Slide the two halves together and attach
to the ceiling.
INTERIOR
WALL PLATE
ALIGN TABS WITH MOUNTS
EXTERIOR WALL PLATE
GASKET
Figure 10
TERMINATIONS:
Horizontal Single Pipe (Fig.10)
1. Locate penetration in wall.
2. Cut or cut and frame hole. (Table 3)
3. Attach Inner Plate to wall.
4. Attach / seal Outer Plate to outside wall.
5. Line up keyway, slide black pipe (UV Protected) or termination through plates.
6. If termination is used, attach with screws. Align tabs with pipe mounts.
REMOVE GASKET
FIRESTOP
INSERT BIRD GUARD
Figure 9
Figure 11
8
Page 9
Table 3 - Wall & Ceiling Penetration Sizing Table
VENT DIAMETER
Termination 2" 3" 4" 5" 6" 8"
CONCENTRIC VERTICAL OR HORIZONTAL
TWIN PIPE HORIZONTAL CLASS IIB
TWIN PIPE HORIZONTAL CLASS IIC (Framing Dimensions)
4 ⁄"
105mm
7 ⁄" x 2⁄"
187mm x
65mm
8" x 3"
200 x 77mm
5 ⁄"
130mm
8 ⁄" x 3⁄"
212 x 85mm
8 ⁄" x 3⁄"
225 x 98mm
6 ⁄"
155mm
9" x 4⁄"
228 x 100mm
9 ⁄" x 4 ⁄"
238 x 112mm
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
SINGLE HORIZONTAL CLASS IIB
SINGLE HORIZONTAL CLASS IIC (Framing Dimensions)
SINGLE WALL W/ LOCKING BAND VERTICAL
SINGLE PIPE NO LOCKING BANDS VERTICAL
2⁄"
65mm /
3"
77mm
3 ⁄" " 85mm
3 ⁄
98mm
3 ⁄" 4 ⁄" 5 ⁄" 6 ⁄" 7 ⁄" 9 ⁄"
3" 3 ⁄" 4 ⁄" 5 ⁄" 6 ⁄" 7 ⁄"
7. Add additional components to raise vent level if desired (vent to be 12" above grade or average snow level).
8. Remove gasket and install Bird Guard into end of pipe. (Fig.11)
9. Install Poly Pro venting system to/from termination to appliance.
POSITIONED HORIZONTALLY
INTERIOR
WALL PLATE
EXTERIOR WALL PLATE
EXHAUST PIPE
APPLY BEAD OF SILICON SEALANT AROUND FEMALE END OF PIPE TO SEAL AGAINST EXTERIOR WALL PLATE
EXHAUST TIP
4" "
100mm
4 ⁄
112mm
N/A N/A N/A
N/A N/A N/A
Horizontal Twin Pipe (Fig.12)
1. Locate penetration.
2. Cut or cut and frame hole. (Table 3)
3. Attach interior wall plate to inside wall.
4. Attach and seal exterior wall plate to outside wall.
5. Slide pipes through outer plate.
6. Rotate pipes to slide pipe past keyway.
POSITIONED VERTICALLY
AIR INLET PIPE
OUTER COVER PLATE
Figure 12
9
Page 10
7. Slide exhaust tip into exhaust pipe.
8. Mount outer cover plate to exterior wall plate.
9. install Poly Pro venting system to/from termination to appliance.
Horizontal Concentric (Fig.13)
1. Locate penetration.
2. Cut hole. (Table 3)
3. Attach and seal exterior exterior wall plate onto outside wall.
4. Slide cap through exterior wall plate into hole from outside building. Cap must
not be installed sloped downward.
5. Orient termination so air intake slots face down.
6. Seal termination to exterior wall plate with silicone sealant.
7. Slide interior wall plate over termination and attach to wall from inside the room.
8. Attach interior wall plate to termination with provided hardware.
9. Install gaskets into Co-Linear Adapter.
10. Attach Co-Linear Adapter to Horizontal Termination.
11. Install Poly Pro venting system to/from termination to appliance.
INSTALL GASKETS
INTERIOR WALL PLATE
EXTERIOR WALL PLATE
POLYPRO PIPE
W/PVC ADAPTER
SUPPLIED WITH
TERMINATION KIT
BRACKET
Figure 14
Lochinvar 2" installation (Fig.14)
1. Slide PolyPro pipe w/ PVC adapter into oblong hole and down. Brackets will point away from the wall, on the exterior of the house, and rest between the two outward beads.
2. Install the termination assembly in accordance with appliance manufacturer’s instructions.
3. Verify exhaust pipe cannot be removed from termination cap.
POLYPRO PIPE
W/PVC ADAPTER
SUPPLIED WITH
TERMINATION KIT
COLINEAR
EXHAUST
AIR INTAKE
10
ADAPTER
SCREW TO
TERMINATION
Figure 13
HORIZONTAL TERMINATION
Figure 15
Lochinvar 3" & 4" installation (Fig.15)
1. Slide PolyPro Pipe w/ PVC adapter into small hole of retaining plate until it stops on the adapter collar.
2. Finish installing the termination assembly in accordance with appliance manufacturer’s instructions. PolyPro
Page 11
pipe is to be installed on the exhaust outlet.
3. Once securely installed to exterior, verify exhaust pipe cannot be removed from termination cap.
Stainless Horizontal (Fig.16)
1. Cut opening in the wall.
2. Add Trim Plates and locking band (if applicable) to nal pipe length before installing. Make sure anges are facing towards the wall. Use non-hardening sealant where necessary.
3. After exterior trim plate is mounted to wall, measure 3" from exterior plate and cut o female pipe end. Duburr. Seal pipe to exterior plate. Slide Bird screen over cut pipe end and tighten clamp.
THROUGH HOLE SIZING 4PPS: 4.125" 5PPS: 5.25" 6PPS: 6.125" 8PPS: 8.00"
EXTERIOR PLATE
FLANGES
CUT LINE
INTERIOR PLATE
INITIAL
TERMINATION
CAP
STORM COLLAR
FLASHING
SUPPORT CLAMP
Figure 18
EXHAUST
AIR INLET
BIRD SCREEN
CLAMP
Figure 16
Figure 17
PP PIPE
CENTERLINE OF EXHAUST OUTLET OF APPLIANCE
FINAL
Figure 19
Vertical Concentric (Fig.18)
1. Locate penetration. (Fig.17)
2. Cut hole in roof. (Table 3)
3. Cut hole in ceiling above appliance.
Cut hole(s) big enough for pipe in all
ceilings above appliance if installing in a multi story installation.
4. Firestop each ceiling penetration.
5. Attach ashing to roof. (Fig.18)
Slide storm collar onto ashing if
using the Adjustable Roof Flashing.
6. Slide vertical termination into ashing from above until seated on ashing.
7. Plumb Termination and mount support bracket to structure.
11
Page 12
8. Install gaskets into Co-Linear Adapter (if applicable). (Fig.13)
9. Connect Co-Linear Adapter to termination (if applicable). (Fig.19)
10. Install Poly Pro venting system to/from Co-Linear Adapter or termination to appliance.
BIRD GUARD
BLACK
UV PROTECTED PIPE
max length rectangle, 4 vent runs max per support. The listing requires clearance holes no larger than 5 1/8" Dia, with spacing 1 3/4" apart.
The upper support plate (with a ange for B vent and factory built chimney, Fig.22) must be axed to the top of the conduit via screws. Anchor bolts must be used when attaching a at support plate to the top of Masonry or other chase (not shown). Support plate must be weather tight. The SS Hanger Bracket is installed under the Gasket Plate and axed to the top of the support plate with screws (Fig.22). Use non-hardening sealant as required.
RUBBER FLASHING
Figure 20- Vertical Pipe Termination
Vertical single pipe (Fig.20)
1. Follow instructions for Vertical Concentric Termination.
2. Attach ashing to roof. (Fig.20)
Rubber boot ashing or similar,
ensure an eective, leak-proof seal is maintained.
Use BLACK UV protected pipe.
3. Maintain 12 in. (305mm) min. clearance above highest anticipated snow level, max 24 in. (610mm) above roof.
MULTIPLE VENTS IN ONE CONDUIT Fig.21
Multiple PolyPro Rigid/Flex vent systems may be installed within one conduit. Listed 2"-4" M&G components must be used, and the conduit (if pre-existing) must be inspected and deemed sound.
Upper supports may be eld supplied and listed, the listing requires: Min thickness of 24 ga (0.020") SS, no larger than 18" Dia or 18"
The lower portion of the vent system must be supported and restopped as detailed earlier in these and/or the PP Flex instructions (provided separately).
GASKET PLATE
/ HANGER
MOUNT
HARDWARE
GASKET
PLATE
1.75" MAT'L SPACE MIN
CLEARANCE
HOLE
STAINLESS
RELINE
HANGER
BRACKET
POLYPRO
FLEX LINER
RIGID BLACK UV PROTECTED POLYPRO
STAINLESS UPPER SUPPORT PLATE
FLANGE
RIGID POLYPRO
Figure 21
12
Page 13
Figure 22
HANGER MOUNTED TO TOP OF SUPPORT, BELOW GASKET PLATE
SEAL AS REQ'D
M&G DURAVENT
POLYPRO CHIMNEY CAP TERMINATION
COMBUSTION
AIR INTAKE
FLEX HANGER
BRACKET AND
HARDWARE
FLEX CLAMP
STORM COLLAR
M&G DURAVENT POLYPRO EXHAUST SYSTEM
ALUM FLEX AIR INTAKE (Fig.23)
Important: This section only applies to sourcing combustion air!
Reference Fig.23 for installation of air intake ex when used with the M&G DuraVent Chimney Cap Termination. Combustion air is drawn in under the storm collar. Ensure Aluminum ex is approx 1"-2" below termination base for unrestricted operation. See Fig.24 for the lower install.
MAINTENANCE
Have your venting system checked annually. This can be done easily by the same technician who inspects & services the appliance. Recommended areas to inspect are as follows:
- Check areas of the Venting System which are exposed to the elements for wear or damage. If damage is found, the components should be replaced immediately.
- Where possible, look into the Termination Cap to verify no foreign material is there to block the vent. Remove any foreign material found.
- Where practical, inspect joints to verify that no Pipe Sections or Fittings have been disturbed, and consequently loosened. Also check mechanical supports such as Wall Straps, support plates, etc for rigidity.
AIR INTAKE
AIR INTAKE
FLEX
AIR INTAKE
FLEX TO POLYPRO ADAPTER
FLEX
Figure 23- Upper Assy
Figure 24- Lower Assy
ENCLOSURE
M&G DURAVENT POLYPRO EXHAUST SYSTEM
POLYPRO PIPE TO APPLIANCE AIR INTAKE
13
Page 14
THIS PAGE INTENTIONALLY LEFT BLANK
Page 15
THIS PAGE INTENTIONALLY LEFT BLANK
Page 16
POLYPRO WARRANTY
M&G DuraVent, Inc. (“ DuraVent”) provides t his warranty for Po lyPro® for ten years. Subj ect to the limitati ons set forth b elow, DuraVent warrants that it s produc ts will be free fr om defects in m aterial or manufac turing, if proper ly installed, mainta ined and used. DuraVent pro ducts are fully wa rranted if install ed only by a profe ssional installer. This War ranty is transf erable from the or iginal homeowner to t he buyer of the home wit hin the warranted ten ye ars. This warrant y does not cover norma l wear and tear, smoke damage or damage c aused by chimney re s, acts of God, or any pr oduct that was: (1) purchase d other than f rom an authorized D uraVent dealer, retailer or distr ibutor; (2) modied or a ltered; (3) improperly ser viced, inspec ted or cleaned; or (4) subjec t to negligence o r any use not in accordance wit h the installation in structions i ncluded with the pr oduct as determin ed by DuraVent.
Installation instruc tions are available online at www.duravent.com under Support /Literature and th rough our Customer Se rvice Depart ment 800 -835-4429 or customerservice@duravent.com.
DuraVent provide s the following warr anties for PolyPro: On e Hundred Percent (100%) MSRP 10 years f rom the date of purchase .
All warrant y obligations of Dur aVent shall be limi ted to repair or replaceme nt of the defecti ve product pursu ant to the terms and condi tions applicable to each produc t line. These reme dies shall constitu te DuraVent’s sole obligatio n and sole remedy under t his warranty. This war ranty provides n o cash surrender value. The ter ms and conditions of th is warranty may not be m odied, altered or w aived by any action, ina ction or represe ntation, whether or al or in writing , except upon the exp ress, written au thority of an exe cutive ocer of DuraVent.
This produc t is intended for ven ting only categor y II & IV appliances burni ng Natural Gas, Propan e and Oil. All other fuels ar e not covered under this warranty.
LIMITATIONS ON POLYPRO INTE RNET SALES: Notw ithstanding any ot her terms or conditio ns of this PolyPro Warrant y, DuraVent provides no warra nty for PolyPro® if it is n ot installed by a qualie d professional ins taller.
DuraVent must be no tied and given the op portunity t o inspect defe ctive produc t prior to replacement und er the terms of this limit ed lifetime warra nty. All warrant y claims must be subm itted with proo f of purchase. Labor an d installation cost s are not covered under t his warranty. To obtain warr anty service contact : DuraVent Warranty Ser vice, 877 Cotting Ct., Vaca ville CA 95688, or call 8 00-835-442 9.
WHERE LAWFUL , DURAVENT DISCLAIMS AL L OTHER WARRANTIES, INCLUD ING BUT NOT LIMITED TO IMPLIED WARR ANTIES OF MERCHAN TABILIT Y AND FITNESS F OR A PARTICULAR PURPOSE. IN N O EVENT WILL DURAVENT BE L IABLE FOR INCIDENTAL, CONSE QUENTIAL, PUNITIVE O R SPECIAL DAMAGES OR DIRECT OR I NDIRECT LOSS OF ANY KIND, INCLU DING BUT NOT LIMITED TO PROPE RTY DAMAGE AND PERSONAL I NJURY. DURAVENT’S ENTIRE LIABIL ITY IS LIMITED TO THE P URCHASE PRICE OF THIS PRO DUCT. SOME STATES DO NOT ALLOW LIMITATIONS ON IMPLIE D WARRANT IES, OR THE EXCLUSION OR LIMITATION OF INCIDEN TAL OR CONSEQUE NTIAL DAMAGES, SO THE ABOVE L IMITATIONS AND E XCLUSIONS MAY NOT APPLY TO YOU. THIS LIMIT ED WARRANTY GI VES YOU SPECIFIC LEGAL RI GHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS THAT VARY FROM STATE TO STATE.
For the mos t up-to-date ins tallation instr uctions, see www. duravent.com
REV 9.4.2012
Customer Service Support 800-835-4429 707-446-4740 FAX www.duravent.com
PolyPro® is a registered trademark of M&G DuraVent, Inc. All rights reserved, ©2014 M&G DuraVent is a member of M&G Group.
820003161- L273 08/2014
Loading...